Bosch 210 Series User manual

PI − 34.53 enProduktinformation FMC−210−DM / SM / ESTLSN
Page 3 of 17
BDL−F.01U.066.176
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib
Table of contents
1. Product description 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. Features 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. Planning notes 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1. Maximum number of detectors that may be connected 5. . . . . . .
3.2. Norms, guidelines and planning recommendations 5. . . . . . . . . . .
3.3. Use in explosive areas 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4. Labelling variants 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4. Order contents 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1. Basic model 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2. Labelling foils 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3. Accessories / Spare parts 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5. Device structure 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6. Functional description 9. . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1. Manual call point 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2. Single action call point 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3. Functional test 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7. Installation 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1. Installation dimensions (view: housing rear wall interior) 10. . . . .
7.2. Cable duct 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3. Installation variants for fire hose cabinets 11. . . . . . . . . . . . . . . . . . .
7.4. Connection 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.5. Addressing 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8. Notes on maintenance and service 13. . . . . . . . . . . . . . . . .
8.1. Repair 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2. Disposal 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.3. Additional documentation 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9. Technical specifications 14. . . . . . . . . . . . . . . . . . . . . . . . . . .
10. Table of abbreviations 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11. Notes 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PI − 34.53 enProduktinformation FMC−210−DM / SM / ESTLSN
Page 4 of 17
BDL−F.01U.066.176
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib
1. Product description
The series 210 non−automatic fire detector is used for manual alarm triggering in the local
security network (LSN).
The Form H detectors are designed for exterior areas, the Form G detectors for interior areas.
Overview of non−automatic fire detectors, series 210
Manual call points
FMC−210−DM−G−R Manual call point for interior areas (Form G), red
FMC−210−DM−H−R Manual call point for exterior areas (Form H), red
Manual call points
FMC−210−DM−G−B Manual call point for interior areas (Form G), blue
FMC−210−DM−H−B Manual call point for exterior areas (Form H), blue
FMC−210−DM−G−Y Manual call point for interior areas (Form G), yellow
Stop device
FMC−210−EST−G−B Stop device for interior areas (Form G), blue
Single action call points
FMC−210−SM−G−B Single action call point for interior areas (Form G), blue
FMC−210−SM−G−R Single action call point for interior areas (Form G), red
2. Features
Manual call point and stop device: Trigger alarm by pushing the button. After alarm
triggering, the push button is adjusted.
Single action call point: Trigger alarm by breaking the glass pane.
Automatic or manual addressing is possible via the rotary switch.
Detector query routines with evaluation and multiple transmission.
Individual detector identification with display of the detector address,
for fast pinpointing of the triggered detector.
Display (LED) for triggered alarms or inspection evaluation.
Same design for interior use (Form G) and exterior use (Form H).
Available in different colour variants; see order overview.
For the red colour variants, a burning house" is applied to the detector housing in the
factory.
Variable labelling is possible with foil sets for the blue and yellow colour variants.
For exterior use in extreme environmental conditions, the detector is equipped with an
especially resistant PC board (parylene layering) and with a seal in the detector door.

PI − 34.53 enProduktinformation FMC−210−DM / SM / ESTLSN
Page 5 of 17
BDL−F.01U.066.176
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib
Additional LSN features
The LSN non−automatic fire detector series 210 offers all the features of the improved" LSN
technology:
Flexible network structures including T−taping" without additional elements.
Up to 254 LSN improved elements per loop or stub line.
Automatic or manual detector addressing can be selected via the rotary switch, in each
case with or without auto detection.
Power supply of up to 300 mA for the connected elements via LSN.
If using the LSN improved version" elements in conjunction with FPA−5000, unshielded
cable can be used. Otherwise, shielded cables must be used.
Cable length up to 1000 m.
Downwards compatibility to existing LSN systems and control panels in CL operating
mode CL00.
3. Planning notes
Non−automatic fire detectors must be mounted visibly along escape and rescue routes
(e.g. exits, passageways, stairwells) and be easily accessible.
An installation height of 1400 mm ($200 mm), measured from the middle of the push
button to the floor, must be maintained.
Non−automatic fire detectors must be sufficiently lit with sunlight or another light source
(including emergency lighting if present).
The distance between non−automatic fire detectors should not exceed 100 m according to
DIN 14 675 or 80 m according to VdS.
In high risk areas, non−automatic fire detectors should be installed at intervals of max. 40 m
(VDE 0833 Part 2, Point 7.2.6).
3.1. Maximum number of detectors that may be connected
The maximum number of LSN elements (LSN interfaces and LSN call points) that may be con-
nected depends on their current consumption from the LSN data line. The limit values should
be taken from the product information supplied with the fire panel used.
3.2. Norms, guidelines and planning recommendations
Additional norms, guidelines, and planning recommendations with respect to installation loca-
tion etc. must be taken into account (see fire detector manual).
The regulations of the local fire services must be observed.

PI − 34.53 enProduktinformation FMC−210−DM / SM / ESTLSN
Page 6 of 17
BDL−F.01U.066.176
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib
3.3. Use in explosive areas
All non−automatic detectors of types DM 210 LSN and SM 210 LSN
conform to device category 3G, gas group IIB and temperature
class T6 as per the European guideline 94/9/EG (ATEX). Thus the
detectors may be used in Zone 2 areas where there is danger of
explosion!
Limiting values:
Detectors may only be operated with central units whose line output is energy−limited
according to EN 50021.
This applies to all Bosch fire panels.
The line voltage (Umax) must not exceed 33 V!
The maximum current (Imax) must be limited to 130 mA!
Fire detector cable:
Only fire detector cables that conform to DIN VDE 0814 may be used.
The total cable capacity (Cmax) must not exceed 1 mF!
The total cable inductivity (Lmax) must not exceed 0.01 H!
The cable type J−Y(ST)Y08, in accordance with DIN VDE 0815 (table 10),
has a capacity of 120 hFat a length of 1000 m.
3.4. Labelling variants
The detectors have basic labelling and can be individually adapted to the location/applica-
tion with optional labelling variants. This excludes detector variants FMC−210−DM−G−R and
FMC−210−DM−H−R, to which the burning house" symbol has already been applied.
The self−adhesive labelling foils are stuck on the front panel of the detector.

PI − 34.53 enProduktinformation FMC−210−DM / SM / ESTLSN
Page 7 of 17
BDL−F.01U.066.176
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib
4. Order contents
4.1. Basic model
Product ID DU*Designation
F01U011956 Pc FMC−210−DM−G−R,
Manual call point for interior areas (Form G), red
F01U011958 Pc FMC−210−DM−H−R,
Manual call point for exterior areas (Form H), red
F01U011959 Pc FMC−210−DM−G−B,
Manual call point for interior areas (Form G), blue
F01U011960 Pc FMC−210−DM−H−B,
Manual call point for exterior areas (Form H), blue
F01U011961 Pc FMC−210−DM−G−Y,
Manual call point for interior areas (Form G), yellow
F01U012764 Pc FMC−210−EST−G−B,
Stop device for interior areas (Form G), blue
F01U027317 Pc FMC−210−SM−G−B,
Single action call point for interior areas (Form G), blue
F01U011962 Pc FMC−210−SM−G−R,
Single action call point for interior areas (Form G), red
4.2. Labelling foils
Product ID DU*Designation
F.01U.012.951 PAK FMC−FST−DE,
Pre−cut and labelled foil sets for the top labelling field
(1 PACK = 5 sheets with 12 labelling variants)
F.01U.033.169 PAK FMX−FSO−LSN,
Pre−cut foil sets for the top labelling field (1 PAK = 10
sheets with 6 labelling variants). Appropriate for
printing at standard laser printers. The required print
file is available on the WinPara disk.
4.3. Accessories / Spare parts
Product ID DU*Designation
3.790.170.005 Pc Out of order" − Metal stop sign
3.756.630.007 Pc Red plastic key (ASA) for detector door
F.01U.025.845 PAK FMC−SPGL−DEIL,
Replacement glass pane, dimensions 80 x 80 x 0.9 mm
(1 PACK = 5 pieces)

PI − 34.53 enProduktinformation FMC−210−DM / SM / ESTLSN
Page 8 of 17
BDL−F.01U.066.176
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib
5. Device structure
The non−automatic fire detector is available in several variants and essentially consists of the
following elements.
1
7
5
2
34
8
2
6
9
Pos. Designation
1Plastic housing
2Cable ducts (interchangeable), for cable inlet and outlet. The cable
can also be ducted through openings in the rear wall of the housing.
3Connection terminal strip
4Detector door with replaceable glass pane, hidden lock (and seal, for
Form H)
5Glass pane
6Display (LED)
7PC board (with protective coating for Form H) The PC board is
clipped onto the floor of the housing.
8Trigger mechanism (clipped onto the PC board), consisting of plastic
frame and push button with spring.
9Reset lever (locking mechanism only for manual call points)

PI − 34.53 enProduktinformation FMC−210−DM / SM / ESTLSN
Page 9 of 17
BDL−F.01U.066.176
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib
6. Functional description
6.1. Manual call point
Manual call point and stop device: In the event of an alarm, the glass pane (2) is broken
first, then the manual call point (3) is pressed hard.
This activates the microswitch for alarm triggering and the indicator LED (4) flashes.
A locking mechanism holds the pressed push button down.
The pressed push button is reset by manually activating the reset lever (5) or by opening
the detector door (1) ⇒The alarm is reset and the display LED goes out (4).
2
4
15
2
3
3
1
6.2. Single action call point
With single action call points, the alarm is triggered when the glass pane (2) is broken and
the button (3) springs up.
This activates the microswitch for alarm triggering and the display LED (4) flashes.
After a new glass pane (2) has been inserted, the call point (3) is reset by opening the
detector doors (1).
6.3. Functional test
Manual call point and stop device: To trigger the alarm, press the manual call point (3)
hard. The display LED (4) flashes. Use the reset lever (5) to return the manual call point to
the starting status.
Single action call point: To trigger the alarm, open the detector door (1). The display LED
(4) flashes. To reset the single action call point to its starting status, close the detector
door (1).
7. Installation
The non−automatic fire detector is designed for wall mounting.
The installation height, according to VdS regulations, is 1400 mm (±200 mm) from the
floor to the centre of the push button.
The connection cables can be surface or flush−mounted.
The cable ducting should be carried out using the intended openings in the housing
(see 7.2 Cable duct).
The installation location is to be selected so that approximately 38 mm space remains
free on the right−hand side for opening the door.

PI − 34.53 enProduktinformation FMC−210−DM / SM / ESTLSN
Page 10 of 17
BDL−F.01U.066.176
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib
7.1. Installation dimensions (view: housing rear wall interior)
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
60 mm
135 mm
37 mm
135 mm
approx. 38 mm
17 mm
13 mm
7.2. Cable duct
Surface−mounted cable duct Flush−mounted cable duct
via concealed box

PI − 34.53 enProduktinformation FMC−210−DM / SM / ESTLSN
Page 11 of 17
BDL−F.01U.066.176
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib
7.3. Installation variants for fire hose cabinets
135
140
2.5 mm
1
12,5
2
149,5
139
2
3
Pos. Description
1Installation depth version 1: min. 39 mm
2Installation depth version 2: 14 mm
3Installation depth version 3: approx. 30 mm
With this version, it is not necessary to open the door of the hose box
e.g. for maintenance.

PI − 34.53 enProduktinformation FMC−210−DM / SM / ESTLSN
Page 12 of 17
BDL−F.01U.066.176
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib
7.4. Connection
+U 0 V a b a b
LSN1 LSN2
3
E
2
14
+−
+
−
−++
−
Pos. Description Connector
1+U / 0 V For execution of the external power supply
2a b
LSN1
LSN in
3a b
LSN2
LSN out
4EEarth connection for the cable shielding

PI − 34.53 enProduktinformation FMC−210−DM / SM / ESTLSN
Page 13 of 17
BDL−F.01U.066.176
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib
7.5. Addressing
The detector address is set via three rotary switches in the detector housing. To set the address,
turn the rotary switch to the desired position using a pan head slotted screwdriver. Permissible
address range: 001 to 254. Settings between 255 and 299 trigger an error message on the fire pan-
el.
Manual addressing: All detectors in a loop or stub line receive an address between 1 and 254.
Automatic addressing: All detectors receive the address ’000’. The address is allocated automati-
cally by the fire panel.
Addressing for BZ 500 LSN, UEZ 2000 LSN, UGM 2020: For connection to these fire panels, all de-
tectors receive the address ’CL00’.
It is not permissible to use different addressing modes at the same time.
Address Mode
0 0 0 Loop/stub in LSN improved mode with automatic addressing
(T branches not possible)
001...254 Loop/stub/T branches in
LSN improved mode with manual addressing
CL 0 0 Loop/stub in Classic" LSN mode
Mode/
XXX XXXXXX
FPA−5000
BZ 500LSN
UEZ 2000 LSN
UGM 2020
−
−
CL 00
000
255...299 −−
001...254
If LSN "improved version" elements are used in conjunction with the FPA−5000, unshiel-
ded cables can be used. Otherwise, shielded cables must be used.
8. Notes on maintenance and service
For maintenance and inspection work on security systems, the regulations of DIN VDE 0833
apply in Germany; these regulations refer to the maintenance intervals as per the manufac-
turer’s instructions.
Bosch ST recommends a functional and visual inspection at least once a year.
Maintenance and inspection work should be carried out regularly and by trained personnel.
8.1. Repair
In the event of a defect, the entire unit is exchanged.
8.2. Disposal
Unusable units should be disposed of in accordance with regulations.

PI − 34.53 enProduktinformation FMC−210−DM / SM / ESTLSN
Page 14 of 17
BDL−F.01U.066.176
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib
8.3. Additional documentation
For those with the appropriate access authorisation,
see Bosch ST ExtraNet at
www.boschbest.de
for the updated product information and the installation manual as a downloa-
dable PDF file.
9. Technical specifications
Technische Daten / Technical specifications / Technische gegevens
Operating voltage 24 V DC (15 V DC to 33 V DC)
Current consumption 0.4 mA
Protection category as per EN 60529
− Form H (exterior)
− Form G (interior)
IP 54
IP 52
Permissible ambient temperature
− Form H (exterior)
− Form G (interior)
−25C to +70C / −13F to 158F
−10C to +55C / 14F to 131F
Standard (except FMC−210−DM−G−Y) EN 54−11
Standard for FMC−210−DM−G−Y EN 12094−3
Colours
RAL 5005 signal blue
RAL 1003 signal yellow
RAL 3001 signal red
Housing material Plastic, ASA (Acrylonitrile−Styrene−Acrylate Terpolymer)
Dimensions (W x H x D) 135 x 135 x 40 mm / 5.31 x 5.31 x 1.5 inches
Weight 235 g

PI − 34.53 enProduktinformation FMC−210−DM / SM / ESTLSN
Page 15 of 17
BDL−F.01U.066.176
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib
10. Table of abbreviations
AHB = Wiring diagram manual
BMZ = Fire panel
BM = Fire detector
DIN = German Institute for Standardization
DM = Manual call point
EMZ = Intrusion control panel
EN = European standard
GMZ = Danger detection system
KI = Customer service information
LED = Light Emitting Diode
LSN = Local Security Network
SM = Single action call point
UGM = Universal danger detection system
VDE = Association of German Electrical Engineers
VdS = VdS Schadenverhütung GmbH

PI − 34.53 enProduktinformation FMC−210−DM / SM / ESTLSN
Page 16 of 17
BDL−F.01U.066.176
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib
11. Notes
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−

Page 17 of 17
Bosch Sicherheitssysteme GmbH
Robert−Koch−Straße 100
D−85521 Ottobrunn, Germany
www.bosch−sicherheitssysteme.de
info.ser[email protected]