© 2008 Bosch Security Systems, Inc.
130 Perinton Parkway, Fairport, New York, USA 14450-9199
(800) 289-0096
02/08
D603/D604/D605 Installation Instructions
P/N: F01U071135-04 Page 4
6.0 Specifications
Product Description
•D603: 135°F (57°C) Electronic Fixed Temperature/Rate-of-Rise Heat Detector (base required)
•D604: 135°F (57°C) Electronic Fixed Temperature Heat Detector (base required)
•D605: 190°F (88°C) Electronic Fixed Temperature Heat Detector (base required)
•D278S: 12 volt POPIT Base
•D287: 2-wire Base
•D292: 4-wire Base
•D293A: 4-wire Base with Built-in Auxiliary Relay
•D293E: 4-wire Base with Built-in EOL Supervision
•D293S: 4-wire Base with Built-in Sounder
•D298S: 24 volt POPIT Base (single)
•D298M: 24 volt POPIT Base (multiple)
•D275: EOL Supervision Module for 4-wire Bases
•TP280: Trimplate for use with D287 Base
Detector Power Requirements
•2-wire Standby Voltage: 8.5 to 33.0 VDC
•4-wire Standby Voltage: 10.0 to 30.0 VDC
•Maximum RMS Ripple: 25% of DC input
•Start-up Current: 120 μA maximum
•Standby Current: 90 μA max @ 12 VDC; 110 μA max @ 24 VDC; 120 μA max @ 33 VDC
Note: D293E = 24 mA @ 12 and 24 VDC
• Alarm Current (D603, D604, D605)
• With 2-Wire bases (D287): Dependent on control panel. Panel must limit the alarm current to 100 mA
maximum.
•With 4-Wire bases:
-D292: 52 mA @ 12 VDC; 54 mA @ 24 VDC; 70 mA max @ 30 VDC
-D293A: 58 mA @ 12 VDC; 62 mA @ 24 VDC; 75 mA max @ 30 VDC
-D293E: 82 mA @ 12 VDC; 86 mA @ 24 VDC; 100 mA max @ 30 VDC
-D293S: 52 mA @ 12 VDC; 54 mA @ 24 VDC
Note: Sounder current not included for D293S alarm current.
Operating Temperature
• 32°F to 100°F (0°C to 38°C)
-D603, D604: These detectors are designed to detect temperatures greater than 135°F (57°C). Do not install
in areas where the normal ambient temperature exceeds 100°F (38°C) or drops below 32°F (0°C).
-D605: This detector is designed to detect temperatures greater than 190°F (88°C). Do not install in areas
where the normal ambient temperature exceeds 190°F (88°C) or drops below 32°F (0°C).
Rate-of-Rise:D603: ≥ 15°F (9°C) per minute
Power-up Time: 22 seconds maximum
Dimensions:Diameter: 4 in. (10.2 cm)
Height: 1.3 in. (3.3 cm)
Compatible Control Panels
•2-wire: See Technical Service Note P/N: 31866.
Bosch Security Systems, Inc. makes no claim written, oral, or implied that the D603 series heat detectors will work with
any 2-wire control panels except those specified in the Base Compatibility chart in Tech Note P/N: 31866.
•4-wire: Compatible with all UL Listed 4-wire control panels. Refer to the manufacturer's Installation
Instructions for proper End-of-Line resistor selection.
Not for use on zones that incorporate an alarm verification feature.