manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. CALEFFI
  6. •
  7. Control Unit
  8. •
  9. CALEFFI Z-one ZVR103 User manual

CALEFFI Z-one ZVR103 User manual

Function
The ZVR series is a multi-zone zone valve and boiler
operating control for multiple zone hydronic heating
systems. The ZVR series interfaces with low voltage
thermostats, or any other low voltage controllers having
a switching action. The ZVR series controls up to 3, 4,
5 or 6 zones, depending on model selected. In addition,
a system pump, secondary pump and a priority (DHW)
pump can also be controlled. LED indicators provide
functional status and easy system troubleshooting. The
ZVR series is a perfect match with Caleffi’s Z-one™
motorized zone valves.
t Compatible with low voltage 2, 3, or 4 wire thermostats
t R, W, C and TT Comm dual labeling at thermostat terminals
t Z-oneLink™ unlimited zone expansion to ZVR and ZSR series
t Selectable priority with 1 hour time-out feature
t System and secondary pump status selectable during ZONE 1 demand
t Circulator will start only after the zone valve end switch is closed
t Dry contact for ZONE 1 (DHW), capable of switching line voltage
t Dry contact AUX for signaling a variable speed self regulated pump or other controls
t Large terminal connections
t High Capacity 40 VA Transformer standard for 3 and 4 zone models-expandable to 80 VA,
and 80 VA standard for the 6 zone model
t Automatic resettable low voltage fuse
t Controls system pump, secondary pump, and priority pump
t Front LED Lights
t 100% Factory tested with 3 year warranty, ETL Listed / CSA Certified
Technical specifications
Materials
Housing plastic: ABS
Front display lights: LED
Electrical Knockouts: (12) 1/2" size
Performance
Power supply: 120 VAC, 50/60 Hz
Transformer voltage: 24 VAC
Maximum transformer load: 40 VA (ZVR103/4), 80 VA (ZVR106)
Electrical switch rating: 20A Max Combined
Electrical switch rating, AUX, ZONE 1, XX: 120 VAC, 2A each
Electrical switch rating pumps: 120 VAC, 5A each
Resettable Fuse: automatic
Working temperature range: 32°F (0°C)—115°F (45°C)
Maximum humidity: 90% non-condensing
Approvals: Conforms to UL873 / Certified to CSA C22 No 24, listed by ETL
NA10333 G2
Z-one™Relay Multi-Zone Valve Control
ZVR10X series
www.caleffi.com
© Copyright 2015 Caleffi North America
Product Range
Code ZVR103 Z-one™ Relay zone valve control...........................................................three zone
Code ZVR104 Z-one™ Relay zone valve control.............................................................four zone
Code ZVR106 Z-one™ Relay zone valve control...............................................................six zone
4009064
Certified to CSA C22-2 No.24
Conforms to UL Standard 873
SAFETY INSTRUCTION
This safety alert symbol will be used in this manual to draw attention to safety
related instructions. When used, the safety alert symbol means ATTENTION!
BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE
INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.
CAUTION: All work must be performed by qualified personnel trained in the
proper application, installation, and maintenance of systems in accordance
with all applicable codes and ordinances.
CAUTION: Electrical shock hazard. Disconnect power before installation to
prevent electrical shock or equipment damage. Make sure all connections
are in accordance with the electrical wiring diagram and in accordance with
national and local electrical codes.
WARNING: Avoid electrical noise interference. Do not install near large
conductors, electrical machinery, or welding equipment. Avoid locations
where excessive moisture, corrosive fumes, vibration, or explosive vapors are
present.
Caleffi shall not be liable for damages resulting from misapplication or misuse of it products.
Dimensions
POWER
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZVR106
Six zone switching - Input: 120VAC 50/60Hz 20A MAX
Conforms
to UL 873
4009064
CAUTION:
RISKOF ELECTRIC SHOCK - DISCONNECT ALL
INPUTPOWER PRIOR TO SERVICING
Milwaukee,WI 53208 USA
POWER
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
T-STAT
CALL
VALVE
OPEN
Code Zones A B C Wgt. (lbs)
ZVR103 3 9 1/4"11"3"3.2
ZVR104 4 9 1/4"11"3"3.2
ZVR106 6 9 1/4"11"3"3.2
A
BC
C
Inspect packages for damage. If damaged, notify the appropriate carrier immediately. If undamaged,
open the package and inspect the device for obvious damage. Return damaged products.
r Use only copper conductor supply wire suitable for at least 105° C
r All circuits must have a common disconnect and be connected to the same pole of the disconnect
Maintenance and Repair
The Caleffi Z-one™multi-zone valve control comes with a automatic resettable low voltage fuse
and requires no maintenance. If control fails or is damaged, replace control with functional one.
Mounting
Mount the Caleffi Z-one™switching relay box to a suitable surface. Slotted holes are provided for
mounting purposes. Do not mount to a surface that exceeds 115°F (45°C). The unit must be only
located in dry interior locations. It is not suitable for installation in hazardous locations and should
not be placed close to any electromagnetic fields.
Cover removal
Hold either the left or the right
end of the box up and at an
angle.
Insert screwdriver and push
tab inward, cover should
release from base.
Roll cover off base.
Transformer installation
Mount box on stable surface
using level.
Remove transformer(s) from
packaging. Slide bottom end of transformer
into bottom latch.
Snap top of transformer into
latch arms.
Feed wiring through hole near
the top of the transformer and
insert transformer plug into the
socket.
Repeat process for 2nd
transformer if six valve relay
box.
Installation
CAUTION: If unit is below 32
°
F (0
°
C), expose to room temperature for 15 minutes before
pressing cover release tabs. Failure to do so could cause damage to the enclosure.
When a zone has a demand from
a thermostat (T T / R W) the
control will send 24 VAC to the
corresponding zone valve. When
the zone valve end switch closes,
the system and secondary pump
will switch on and the (X X) dry
contact will close to signal the boiler of a heating demand. AUX dry contact will also close as a
signal to a variable speed self regulated pump or other controls. ZONE 1 can be used for priority
(either a priority pump or valve). When the priority dip switch is ON, a demand from T-STAT 1 will
activate 24VAC to VALVE 1 and the ZONE 1 pump relay, 120 VAC will switch on after the end switch
closes (requires a jumper in the end switch terminals if a valve is not used). The DHW (ZONE 1) dry
contact will also close.
Depending upon "Status During Zone 1 Demand" jumpers, the secondary and / or system pump
will either be ON or OFF.
Status During Zone 1 Demand ON / OFF: When
status jumper is placed on ON pins, the secondary
and / or system pump will continue to operate during
ZONE 1 demand. When jumper is placed on OFF pins,
the corresponding pump will be OFF during ZONE 1
demand.
XX = Dry contact rated up to 120 VAC, 2 Amps, which is typically
connected to T T on boiler control, closes when any zone calls including
priority. ZONE 1 / ES (DHW) = Dry contact, rated up to 120 VAC, 2
Amps, close with any call to ZONE 1. When priority is enabled and ZONE
1 is calling, it is typically used to close DHW contact on boiler controls
equipped with these features. AUX = Dry contact, rated up to 120 VAC,
2 Amps, close when any zone calls and can be used
as signal to a variable speed self regulated
pump. When there is a priority demand, then AUX will follow the selection of the AUX dip switch.
The ZVR series of controls is programmed by
positioning four dip switches for the following
operations.
Master / Slave: allows for unlimited expansion to
additional ZVR or ZSR relays boards.
Pump Exercise ON / OFF: When exercise mode is
ON, each circulator is switched on for 30 seconds
following 72 hours of inactivity.
Priority ON / OFF: When priority switch is ON, upon
demand to TSTAT 1 , ZONE 1 will operate as priority
and all other zones are temporarily switched off (with 1 hour time-out). When priority is OFF, any
zones that were active when ZONE 1 was switched on will remain on.
AUX ON / OFF: When AUX switch is ON, AUX dry contact is activated with a demand to any zone
including priority. When AUX is OFF, AUX dry contact is activated during any demand except priority.
L
ZONE #1
PUMP
NL
SEC
PUMP
N
STATUS DURING
ZONE #1 DEMAND
L
SYSTEM
PUMP
N
0
/
0
'
'
0
/
0
'
'
MASTER
PUMP EXERCISE ON
PRIORITY ON
AUX ON
SLAVE
OFF
OFF
OFF
DURING PRIORITY DEMAND
Dip switch settings
ZONE 1
E / S
XX
AUX
Boiler Connections
T-STAT 2
C
RW
TTCOM
T-STAT 3
C
RW
T T COM
T-STAT 1
C
RW
T T COM
T-STAT 4
C
RW
T T COM
Thermostats
Large screw terminals connections makes wiring easy with three pump screw terminal connections.
Pump terminals connection have 120 VAC outputs for simplified pump connections. Zone valve
connections can be 2, 3 or 4 wire.
Z-oneLink™ unlimited expansion allows connecting additional ZVR & ZSR
series relay controls to a Master ZVR. Communication is accomplished by
connecting three wires (thermostat wire) to the communication terminals
located in the upper right hand corner. The dip switch is positioned to Master /
Slave position. A demand for heat from any zone will fire the boiler and start the
pump. Only one relay board can be the Master and Priority, Slave is used for subsequent boards.
L
POWER IN
N
L
ZONE #1
PUMP
NL
SEC
PUMP
N
ZONE 1
EN
SWI
T
MOTOR
L
SYSTEM
PUMP
N
COMMS
DP
Wiring terminals
ZONE 1
END
SWITCH
MOTOR
Z
O
MOTO
R
Wiring 2 wire, 3 wire & 4 wire zone valves
The Taco 570 three wire zone valve presents a unique wiring
challenge. When connecting the Taco 570, the wiring of this
valve can only be done in one way. The left motor terminal on
the ZVR series control must be connected to terminal 2 on the
zone valve. The right motor terminal must be connected to
terminal 1 on the zone valve. Lastly, the left end switch terminal
must be connected to terminal 3 on the zone valve. Failure to
follow schematic will lead to damage of product.
Since a two wire actuator does not have an end switch for
feedback to the relay box, the end switch terminals must have
a jumper to simulate the end switch. If the end switch jumper
is not installed, no demand will be sent to the boiler and the
pumps will not turn on
1
2
3
2 1 3
The four wire zone valve is the most straight forward of the three
types of valves to wire. Simply connect the two motor leads to
motor leads, and the two end switches to end switches.
NE 2
END
SWITCH
ZONE 3
END
SWITCH
MOTOR M
O
ZONE 1
END
SWITCH
T
OR
ZONE 2
END
SWITCH
MOTOR
M
Example Wiring Diagram
VENT
L
N
SYSTEM pump
SECONDARY
pump
ZV1 ZV4ZV3ZV2 ZV5 ZV6
ZV1 ZV4ZV3ZV2 ZV5 ZV6
SYSTEM
pump
SECONDARY
pump
mod/con
boiler
6 Zone
ZVR106
L
POWER IN
N
POWER
T-SAT
CALL
ZONE 6
L
ZONE #1
PUMP
NL
SEC
PUMP
N
STATUS DURING
ZONE #1 DEMAND
ZONE 1
END
SWITCH
MOTOR
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
END
SWITCH
MOTOR
L
SYSTEM
PUMP
N
T-STAT 2
C
RW
TTCOM COMMS
DP
ZONE 1
E / S
XX
T-STAT 3
C
RW
TTCOM
T-STAT 1
C
RW
TTCOM
T-STAT 4
C
RW
TTCOM
T-STAT 5
C
RW
TTCOM
T-STAT 6
C
RW
TTCOM
AUX








VALVE
OPEN
ZONE 1
ZONE 2
ZONE 4
ZONE 5
ZONE 3
MASTER
PUMP EXERCISE ON
PRIORITY ON
AUX ON
SLAVE
OFF
OFF
OFF
DURING PRIORITY DEMAND
set to ON


Please reference Z-one™ Relay wiring guide for complete listing of wiring diagrams.
Mod-Con boiler with
Primary/Secondary
L
N
G
TT
ZR
ZC
outdoor
temperature
sensor
boiler
reset
controller
space heating thermostats
DHW
aquastat
space
heating
demand
domestic water
heating demand
SYSTEM
pump
ZV1 ZV2 ZV4ZV5 ZV6ZV3
indirectDHW tank
DHW
aquastat
VENT
ZV1
ZV2
ZV4
ZV5
ZV6
ZV3
SYSTEM
pump
6 Zone
ZVR106
L
POWER IN
N
POWER
T-SAT
CALL
ZONE 6
L
ZONE #1
PUMP
NL
SEC
PUMP
N
STATUS DURING
ZONE #1 DEMAND
ZONE 1
END
SWITCH
MOTOR
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
END
SWITCH
MOTOR
L
SYSTEM
PUMP
N
T-STAT 2
C
RW
T T COM COMMS
DP
ZONE 1
E / S
XX
T-STAT 3
C
RW
T T COM
T-STAT 1
C
RW
T T COM
T-STAT 4
C
RW
TTCOM
T-STAT 5
C
RW
TTCOM
T-STAT 6
C
RW
T T COM
AUX










VALVE
OPEN
ZONE 1
ZONE 2
ZONE 4
ZONE 5
ZONE 3
MASTER
PUMP EXERCISE ON
PRIORITY ON
AUX ON
SLAVE
OFF
OFF
OFF
DURING PRIORITY DEMAND
set to ON
L
N
Non-condensing boiler with
outdoor reset and indirect DHW
Caleffi North America, Inc.
3883 West Milwaukee Road
Milwaukee, WI 53208 USA
T: 414.238.2360 F: 414.238.2366
CALEFFI
L
N
"A"
pump
SYSTEM
pump "B"
pump
SYSTEM
pump
A4A3A2 A5 A6
"A"
pump
"B"
pump
A10A9A8 A11 A12A7
A1
A4A3A2 A5 A6A1 A10A9A8 A11 A12A7
L
N
6 Zone
ZVR106
L
POWER IN
N
POWER
T-SAT
CALL
ZONE 6
L
ZONE #1
PUMP
NL
SEC
PUMP
N
STATUS DURING
ZONE #1 DEMAND
ZONE 1
END
SWITCH
MOTOR
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
END
SWITCH
MOTOR
L
SYSTEM
PUMP
N
T-STAT 2
C
RW
TTCOM COMMS
DP
ZONE 1
E / S
XX
T-STAT 3
C
RW
TTCOM
T-STAT 1
C
RW
TTCOM
T-STAT 4
C
RW
TTCOM
T-STAT 5
C
RW
TTCOM
T-STAT 6
C
RW
TTCOM
AUX










VALVE
OPEN
ZONE 1
ZONE 2
ZONE 4
ZONE 5
ZONE 3
MASTER
PUMP EXERCISE ON
PRIORITY ON
AUX ON
SLAVE
OFF
OFF
OFF
DURING PRIORITY DEMAND
6 Zone
ZVR106
L
POWER IN
N
POWER
T-SAT
CALL
ZONE 6
L
ZONE #1
PUMP
NL
SEC
PUMP
N
STATUS DURING
ZONE #1 DEMAND
ZONE 1
END
SWITCH
MOTOR
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
END
SWITCH
MOTOR
L
SYSTEM
PUMP
N
T-STAT 2
C
RW
TTCOM COMMS
DP
ZONE 1
E / S
XX
T-STAT 3
C
RW
TTCOM
T-STAT 1
C
RW
TTCOM
T-STAT 4
C
RW
TTCOM
T-STAT 5
C
RW
TTCOM
T-STAT 6
C
RW
TTCOM
AUX










VALVE
OPEN
ZONE 1
ZONE 2
ZONE 4
ZONE 5
ZONE 3
MASTER
PUMP EXERCISE ON
PRIORITY ON
AUX ON
SLAVE
OFF
OFF
OFF
DURING PRIORITY DEMAND
set to ON set to ON
Mod-Con boiler with Primary/Secondary and
two secondary pumps
1
1
WIRING GUIDE
4009064
Certified to CSA C22-2 No.24
Conforms to UL Standard 873
The ZSR101 is a versatile single relay control with two outputs for operating a 120 VAC pump with boiler enable, or two 120
VAC devices without boiler enable. Features include rear knock outs for 4x4 junction box mounting, convenient pre-installed
jumper for pump operation, and 10 amp total load rating.
The ZSR Series of controls is for zoning using pumps. Up to 6 zone pumps (model dependent) along with a primary pump
can be operated. Zone priority is selectable with 1-hour time-out feature. Other features include pump exercising, selectable
post purge, and 3 pump ground terminals for simplifi ed wiring.
The ZVR Series of controls is for zoning using zone valves. Up to 6 valves (model dependent), along with a system pump,
secondary pump and zone 1 pump (typically used for DHW priority) can be operated. Zone priority is selectable with 1-hour
time-out feature. System pump and secondary pump status (on/off) during priority is also selectable. Replaceable snap-fi t 40
VA transformer standard for 3 & 4 zone models – expandable to 80 VA with 2nd transformer. 6 zone model has two 40 VA
(80 VA) transformers.
Form 031914 rev.2
3
INDEX
Z-one Relay thermostat connections
Thermostat wiring ........................................................................................................................................................................... 4
Zone valve wiring to ZVR series....................................................................................................................................................... 5
ZSR101 - single zone relay
Product overview ............................................................................................................................................................................ 6
Operation and cover removal ........................................................................................................................................................................7
A1 - Single thermostat ...................................................................................................................................................................................8
A2 - Multiple thermostats...................................................................................................................................................................10
A3 - Single master thermostat, with TRVs, variable speed pump.................................................................................................... 12
ZSR103, ZSR104 & ZSR106 - multi-zone pump relay
Product overview ........................................................................................................................................................................... 14
Circuit board .................................................................................................................................................................................. 15
Cover removal................................................................................................................................................................................ 16
Product details............................................................................................................................................................................... 17
B1 - Mod/Con boiler, hydro separator or buffer tank, zone pumps ................................................................................................. 18
B2 - Traditional boiler, indirect DHW w/ priority, zone pumps .......................................................................................................... 20
B3 - Mod/Con boiler, primary loop, closely spaced tees, zone pumps............................................................................................ 22
B4 - Mod/Con boiler, hydro separator or buffer tank, zone pumps with remote enable................................................................... 24
ZVR103, ZVR104 & ZVR106 - multi-zone valve control
Product overview ........................................................................................................................................................................... 26
Circuit board .................................................................................................................................................................................. 27
Cover removal, Transformer Installation .................................................................................................................................................28
Product details............................................................................................................................................................................... 29
C1 - Mod/Con boiler, hydro separator, zone valves ........................................................................................................................ 30
C2 - Mod/Con boiler, indirect DHW on primary side of hydro sep, zone valves............................................................................... 32
C3 - Mod/Con boiler, indirect DHW on load side of hydro sep, zone valves.................................................................................... 34
C4 - Mod/Con boiler, indirect DHW on primary side of hydro sep, master and slave control........................................................... 36
C5 - Traditional boiler, indirect DHW (no priority) with valve ............................................................................................................. 38
C6 - Traditional boiler with reset control, priority indirect DHW with valve........................................................................................ 40
C7 - Mod/Con boiler, hydro separator, zone valve (more than 6), multiple secondary pumps.......................................................... 42
C8 - Mod/Con boiler, indirect DHW on primary side of hydro sep, zone valves with ECM pump enabling....................................... 44
C9 - Mod/Con boiler, hydro separator, zone 1 low temp, 2 - 6 high temp zone valves.................................................................... 46
Caleffi shall not be liable for damages resulting from misapplication or misuse of it products.
4
All Caleffi Z-one controls use the same interface
to connect to thermostats. This interface is
very flexible and allows many different types
of thermostats to be connected to the control
including 2, 3 and 4 wire versions. In addition, any
type of switching device can be used to signal a
heat demand by connecting the R & W (T & T)
terminals together. The terminals are dual labeled
to help simplify wiring.
Z-one Thermostat Connections
L
PUMP 2
N
PRIMARY
PUMP
L
PRIORITY
PUMP 1
N
L
POWER IN
N
GROUNDS
L
PUMP 3
N
TRANSFORMER
LN
L
PUMP 4
NL
PUMP 5
NL
PUMP 6
N
POWER
ZONE1
ZONE2
ZONE3
ZONE4
ZONE5
ZONE6
T-STAT 2
C
RW
T T COM COMMS
DP
ZONE 1
E / S
X X
T-STAT 3
C
RW
T T COM
T-STAT 1
C
RW
T T COM
T-STAT 4
C
RW
T T COM
T-STAT 5
C
RW
T T COM
T-STAT 6
C
RW
T T COM
AUX
6 Zone
ZSR106
MASTER
PRIORITY ON
REMOTE ENABLE ON
EXERCISE ON
POST PURGE ZONE#1 ON
SLAVE
OFF
OFF
OFF
OFF
REMOTE ENABLE
24 - 120 VAC
LN
ON
OFF
STATUS
DURING
PRIORITY
Z-one T-stat interface
Description
R = 24 VAC Supply
W = Heat Call
C = 24 VAC Common
Function
R&W: When connected, signals a heat demand.
R&C: Provides 24 VAC to powered thermostats.
There are a few different types of 2 wire thermostats
including bi-metallic, power stealing and battery
powered. All of these thermostats connect in
the same manner to the Caleffi Z-one series of
controls. Connect R to R and W to W. See below.
2-Wire Thermostats
6 Zone
Z6P
T
HM 2
C
R
W
T
T COM COMMS
DP
DHW
ZR/ZC
X X
THM 3
C
RW
T T COM
THM 1
C
RW
T T COM
L
PUMP 2
N
PRIMARY
PUMP
L
PRIORITY
PUMP 1
N
LPOWER IN
NGROUNDS
L
PUMP 3
N
TRANSFORMER
12/20VA
LN
THM 4
C
RW
T T COM
L
PUMP 4
NL
PUMP 5
NL
PUMP 6
N
THM 5
C
RW
T T COM THM 6
C
RW
T T COM
PWR
ZONE1
ZONE2
ZONE3
ZONE4
ZONE5
ZONE6
DipSwitches
Master Slave
Priority OFF Priority ON
Primary OFF Primary ON
Exercise OFF Exercise ON
Post Purge OFF Post Purge ON
To connect a 4-wire thermostat to the Z-one
series controls, connect R to R, W to W and C
to C. A jumper in the thermostat is also required
between R & Rh as shown below. Similar to a
3-wire thermostat, R & C from the Z-one Control
supply constant 24 VAC to the thermostat.
4-Wire Thermostats
Three wire thermostats get their power from the
control they are connected to. R & C from the
Z-one Control supply 24 VAC to the thermostat at
all times while the W lead signals a heat demand.
3-Wire Thermostats
6 Zone
Z6P
TH
M 2
C
R
W
T
T COM COMMS
DP
DHW
ZR/ZC
X X
THM 3
C
RW
T T COM
THM 1
C
RW
T T COM
L
PUMP 2
N
PRIMARY
PUMP
L
PRIORITY
PUMP 1
N
LPOWER IN
NGROUNDS
L
PUMP 3
N
TRANSFORMER
12/20VA
LN
THM 4
C
RW
T T COM
L
PUMP 4
NL
PUMP 5
NL
PUMP 6
N
THM 5
C
RW
T T COM THM 6
C
RW
T T COM
PWR
ZONE1
ZONE2
ZONE3
ZONE4
ZONE5
ZONE6
DipSwitches
Master Slave
Priority OFF Priority ON
Primary OFF Primary ON
Exercise OFF Exercise ON
Post Purge OFF Post Purge ON
6 Zone
Z6P
TH
M 2
C
R
W
T
T COM COMMS
DP
DHW
ZR/ZC
X X
THM 3
C
RW
T T COM
THM 1
C
RW
T T COM
L
PUMP 2
N
PRIMARY
PUMP
L
PRIORITY
PUMP 1
N
LPOWER IN
NGROUNDS
L
PUMP 3
N
TRANSFORMER
12/20VA
LN
THM 4
C
RW
T T COM
L
PUMP 4
NL
PUMP 5
NL
PUMP 6
N
THM 5
C
RW
T T COM THM 6
C
RW
T T COM
PWR
ZONE1
ZONE2
ZONE3
ZONE4
ZONE5
ZONE6
DipSwitches
Master Slave
Priority OFF Priority ON
Primary OFF Primary ON
Exercise OFF Exercise ON
Post Purge OFF Post Purge ON
6 Zone
Z6P
THM 2
C
RW
T T COM
COMMS
DP
DHW
ZR/ZC
X X THM
3
C
RW
T T
COM
THM 1
C
RW
T T COM
L
PUMP 2
N
PRIMARY
PUMP
L
PRIORITY
PUMP 1
N
LPOWER IN
NGROUNDS
L
PUMP 3
N
TRANSFORMER
12/20VA
LN
THM 4
C
RW
T T COM
L
PUMP 4
NL
PUMP 5
NL
PUMP 6
N
THM 5
C
RW
T T COM THM 6
C
RW
T T COM P
WR
ZONE1
ZONE2
ZONE3
ZONE4
ZONE5
ZONE6
DipSwitches
Master Slave
Priority OFF Priority ON
Primary OFF Primary ON
Exercise OFF Exercise ON
Post Purge OFF Post Purge ON
C R Rh W1
A heat demand can also be initiated by any type
of device that has dry contacts (dry contacts are
a set of contacts that open and close but do not
have any voltage present until supplied from an
outside source). The end switch on a Z-one series
zone valve is an example of a dry contact. Using
a dry contact to connect R to W will initiate a heat
demand.
Dry Contacts
Always refer to the thermostat manufacturer’s instructions.
SAFETY INSTRUCTION
This safety alert symbol will be used in this manual to draw attention to safety
related instructions. When used, the safety alert symbol means ATTENTION!
BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE
INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.
CAUTION: All work must be performed by qualified personnel trained in the
proper application, installation, and maintenance of systems in accordance with all
applicable codes and ordinances.
CAUTION: Electrical shock hazard. Disconnect power before installation to prevent
electrical shock or equipment damage. Make sure all connections are in accordance
with the electrical wiring diagram and in accordance with national and local electrical
codes.
CAUTION: Avoid electrical noise interference. Do not install near large conductors,
electrical machinery, or welding equipment. Avoid locations where excessive
moisture, corrosive fumes, vibration, or explosive vapors are present.
Caleffi shall not be liable for damages resulting from misapplication or misuse of it products.
WARNING: NEVER CONNECT R & C DIRECTLY,
this will be a direct short on the 24 VAC supply
5
1
2
3
LPOWER IN
N
POWER
T-SAT
CALL
ZONE 6
L
ZONE #1
PUMP
NL
SEC
PUMPN
STATUS DURING
ZONE #1 DEMAND
ZONE 1
END
SWITCH
MOTOR
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
END
SWITCH
MOTOR
L
SYSTEM
PUMP
N
T-STAT 2
C
RW
T T COM COMMS
DP
ZONE 1
E / S
X X
T-STAT 3
C
RW
T T COM
T-STAT 1
C
RW
T T COM T-STAT 4
C
RW
T T COM T-STAT 5
C
RW
T T COM T-STAT 6
C
RW
T T COM
AUX
ON
OFF
ON
OFF
VALVE
OPEN
1
2
3
4
52
2 1 3
4 1 3
White Rogers
1361 Zone Valve
4 wire Zone Valve
2 wire Taco
570
2
Wiring a standard zone valve to Calef Z-one Relay
Since a two wire actuator does not have an end switch for feedback
to the ZVR control, the end switch terminals must have a jumper to
simulate the end switch. If the end switch jumper is not installed, no
demand will be sent to the boiler and the pumps will not turn on.
Wiring a Taco 570 valve to Calef Z-one Relay
When connecting the Taco 570 zone valve to the Caleffi Z-one Relay,
the wiring of this valve can only be done in one way. The left motor
terminal on the ZVR series control must be connected to terminal 2
on the zone valve. The right motor terminal must be connected to
terminal 1 on the zone valve. Lastly, the left end switch terminal
must be connected to terminal 3 on the zone valve. Failure to follow
schematic will lead to damage of product.
Wiring a White Rogers 1361 valve to Calef Z-one Relay
The White Rogers 1361 zone valve requires 24 VAC to terminal 2
at all times, therefor connect to the R terminal of the associated
T-STAT on the ZVR control. The left motor terminal on the ZVR
series control must be connected to terminal 4 on the zone valve.
The right motor terminal must be connected to terminal 1 on the
zone valve. Lastly, the left end switch terminal must be connected
to terminal 3 on the zone valve. The 1361 can not be used on any
zone when the ZVR control is set for priority.
Wiring zone valve to Calef ZVR control
6
Overview
•Compatiblewith2,3and4-wirethermostatsorother
low voltage controllers with switching action
•120VACinput
•Heavyduty,sealed,DPDT,fuseprotectedrelay 
(with spare fuse)
•Twodrycontactoutputs(Relay1andRelay2)for
operating 120 VAC pump with boiler enable or two
devices without boiler enable
•5Acapacityeachrelay-10Atotal
•Rearknock-outsformountingonto4”x4”junctionbox
•Highcapacity6VAtransformer
•Simpliedwiringwithpre-installedjumper
•100%factorytestedwith3yearwarranty
•ETLcertied
See technical brochure 01284 NA for more product
information.
4009064
Certified to CSA C22-2 No.24
Conforms to UL Standard 873
ZSR101 - Single Zone Switching Relay
7
When a zone has a
demand from a thermostat
(TT or R W) the relay will
close sending 120 VAC
to Relay #1 NO terminal
and switching the pump
on, and the C to NO dry
contact on relay #2 closes,
signaling the boiler of a heating demand.
1 Zone
ZSR101
C
RW
T T COM
L
POWER IN
NC
RELAY #1
NO NC C
RELAY #2
NO NC
TRANSFORMER
PWR
ZONE
1 Zone
ZSR101
C
RW
T T COM
L
POWER IN
NCRELAY #1
NO NC CRELAY #2
NO NC
TRANSFORMER
PWR
ZONE
Operating Principles
R, W, C and T T Comm dual labeling at thermostat terminals.
Compatible with low voltage 2, 3, or 4 wire thermostats
or any
other low voltage devices having a switching action.
Supply 120 VAC hot to terminal L and 120 VAC neutral to N.
A factory installed jumper from L terminal to the C terminal of
Relay 1 is supplied for simplified pump connection.
Dual labeled T-stat terminals.
Compatible with 2, 3 and 4
wire T-stats.
Replaceable fuses.
6 VA Transformer.
Keyhole mounting
which fits a 4X4
junction box.
Pre-installed jumper. Rear knockout for
4X4 junction box.
If dry contacts are desired from relay #1, remove the factory
installed jumper between L and C.
Cover removal
Hold either the left or the right end
of the box up and at an angle. Use
body for stabilizing relay box. Insert
screwdriver and push tab inward.
Turn box and repeat inserting
screwdriver and pushing tab inward
on opposite side, cover should
release from base.
Slide cover off base.
Mounting: Do not mount to a
surface that exceeds 115°F (45°C).
The unit must be only located in dry
interior locations. Use only copper
conductor supply wire suitable for
at least 105° C. All circuits must
have a common disconnect and
be connected to the same pole of
the disconnect. It is not suitable for
installation in hazardous locations.
120VAC input
power connection
8
T
T
RWC
TTcom
power
zone
transformer
N LL RELAY 1
C N/O N/C C N/O N/C
RELAY 2
CalefÞ!
single zone relay
L
N
A1 - Single thermostat
Hydronic diagram is for illustration purposes only, some components have been removed for simplicity.
9
Sequence of Operation / Settings
• A demand occurs from the thermostat closing
RtoWontheZSR101control.The“ZONE”
LED illuminates.
• The ZSR101 control will power relay #1 and
#2 closing C to NO.
• The NO terminal of relay #1 will send out
120 VAC to your pump. Relay #2 provides
a dry contact closure to signal the boiler of a
demand.
• NOTE: Relay #1 can be used as a dry contact
as well by removing the factory installed
jumper between L and C.
• When the thermostat demand is satisfied R to
Wwillopenandthe“ZONE”LEDwillturnoff.
• The control will remove power from relays #1
and #2 opening C to NO. This will drop 120
VAC to your pump and terminate the demand
to your boiler.
Description of terminals
= Ground
N = Neutral (Common leg of 120 VAC)
L = Line (live leg of 120 VAC)
C = Common terminal
NO = Normally Open terminal
NC = Normally Closed terminal
Note: There is a factory installed jumper between the 120
VAC line (L) and the common terminal of relay #1 (C).
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
WARNING: NEVER CONNECT R & C DIRECTLY,
this will be a direct short on the 24 VAC supply
10
RWC
TTcom
power
zone
transformer
N LL RELAY 1
C N/O N/C C N/O N/C
RELAY 2
CalefÞ!
single zone relay
4-wire zone valve
4-wire zone valve
4-wire zone valve
R W
24 VAC
T
T
RWRW
End switch wires
L
N
A2 - Multiple thermostats
Hydronic diagram is for illustration purposes only and could be missing system components.
11
Sequence of Operation / Settings
• A demand occurs from one of the thermostats
which sends power (from a separately sourced
transformer) to the corresponding zone valve.
• When the zone valve opens the end switch
will close R to W on the ZSR101 control. The
“ZONE”LEDilluminates.
• The ZSR101 control will power relay #1 and
#2 closing C to NO.
• The NO terminal of relay #1 will send out
120 VAC to your pump. Relay #2 provides
a dry contact closure to signal the boiler of a
demand.
• NOTE: Relay #1 can be used as a dry contact
as well by removing the factory installed
jumper between L and C.
• When all the thermostat demands are satisfied
the zone valves will close and the end switch
willopenR toW.The“ZONE”LEDwill turn
off.
• The control will remove power from relays #1
and #2 opening C to NO. This will drop 120
VAC to your pump and terminate the demand
to your boiler.
WARNING: NEVER CONNECT R & C DIRECTLY,
this will be a direct short on the 24 VAC supply
Description of terminals
= Ground
N = Neutral (Common leg of 120 VAC)
L = Line (live leg of 120 VAC)
C = Common terminal
NO = Normally Open terminal
NC = Normally Closed terminal
Note: There is a factory installed jumper between the 120
VAC line (L) and the common terminal of relay #1 (C).
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
12
buer tank
thermostatic
radiator valves
(TRV) on each
radiator
TRV
TRV
TRV
TRV
TRV TRV
RWC
TTcom
power
zone
transformer
NLLRELAY 1
C N/ON/C C N/ON/C
RELAY 2
ZSR101
T
T
L
N
A3 - Single master thermostat, panel radiators with TRVs, variable speed pump
Hydronic diagram is for illustration purposes only, some components have been removed for simplicity.

This manual suits for next models

5

Other CALEFFI Control Unit manuals

CALEFFI 200 Series User manual

CALEFFI

CALEFFI 200 Series User manual

CALEFFI 2521 Series User guide

CALEFFI

CALEFFI 2521 Series User guide

CALEFFI AutoFill 5350 Series User guide

CALEFFI

CALEFFI AutoFill 5350 Series User guide

CALEFFI ThermoBloc 281 Series User manual

CALEFFI

CALEFFI ThermoBloc 281 Series User manual

CALEFFI ThermoSetter 1164 Series User guide

CALEFFI

CALEFFI ThermoSetter 1164 Series User guide

CALEFFI SATK Series User manual

CALEFFI

CALEFFI SATK Series User manual

CALEFFI 5360 Series User manual

CALEFFI

CALEFFI 5360 Series User manual

CALEFFI 5213 Series User manual

CALEFFI

CALEFFI 5213 Series User manual

CALEFFI SATK series HIUs User manual

CALEFFI

CALEFFI SATK series HIUs User manual

CALEFFI 524 Series User manual

CALEFFI

CALEFFI 524 Series User manual

CALEFFI 573 Series User guide

CALEFFI

CALEFFI 573 Series User guide

CALEFFI 359 Series User manual

CALEFFI

CALEFFI 359 Series User manual

CALEFFI 639042 Guide

CALEFFI

CALEFFI 639042 Guide

CALEFFI Z-one ZVR10 Series User manual

CALEFFI

CALEFFI Z-one ZVR10 Series User manual

CALEFFI 5261 Series User manual

CALEFFI

CALEFFI 5261 Series User manual

CALEFFI 455 Series User manual

CALEFFI

CALEFFI 455 Series User manual

CALEFFI 5213TM series User guide

CALEFFI

CALEFFI 5213TM series User guide

CALEFFI FlowCal 121 Series User manual

CALEFFI

CALEFFI FlowCal 121 Series User manual

CALEFFI ThermoSetter 116 Series User guide

CALEFFI

CALEFFI ThermoSetter 116 Series User guide

CALEFFI 543 Series User manual

CALEFFI

CALEFFI 543 Series User manual

CALEFFI AIR190013 User manual

CALEFFI

CALEFFI AIR190013 User manual

CALEFFI 528 Series User manual

CALEFFI

CALEFFI 528 Series User manual

CALEFFI Altecnic SATK40103 Guide

CALEFFI

CALEFFI Altecnic SATK40103 Guide

CALEFFI 252169A Guide

CALEFFI

CALEFFI 252169A Guide

Popular Control Unit manuals by other brands

Sentiotec Pro B manual

Sentiotec

Sentiotec Pro B manual

Honeywell FY 30 installation instructions

Honeywell

Honeywell FY 30 installation instructions

WAREMA WMS WebControl manual

WAREMA

WAREMA WMS WebControl manual

TECshow MATRIXCOB LITE user manual

TECshow

TECshow MATRIXCOB LITE user manual

DUKER 3004 Operation instructions

DUKER

DUKER 3004 Operation instructions

ertex solar VSG Series installation manual

ertex solar

ertex solar VSG Series installation manual

ADLINK Technology Express-SL user manual

ADLINK Technology

ADLINK Technology Express-SL user manual

Emerson White Rodgers 36C94-303 installation instructions

Emerson

Emerson White Rodgers 36C94-303 installation instructions

Arbor Technology EmETXe-i2309 Quick installation guide

Arbor Technology

Arbor Technology EmETXe-i2309 Quick installation guide

LOVATO ELECTRIC GEX69 C Series manual

LOVATO ELECTRIC

LOVATO ELECTRIC GEX69 C Series manual

Monstertech MTX BASE FRAME instruction manual

Monstertech

Monstertech MTX BASE FRAME instruction manual

Vaillant auroMATIC VRS 560 OPERATING AND INSTALLATION Manual

Vaillant

Vaillant auroMATIC VRS 560 OPERATING AND INSTALLATION Manual

Bosch FLM-420-O2-D installation manual

Bosch

Bosch FLM-420-O2-D installation manual

TLV A-DR20-2 instruction manual

TLV

TLV A-DR20-2 instruction manual

IntelliSAW 400.00152.0001 Integration manual

IntelliSAW

IntelliSAW 400.00152.0001 Integration manual

Honeywell D05T quick start guide

Honeywell

Honeywell D05T quick start guide

Woodward easYgen 3000XT Series Option manual

Woodward

Woodward easYgen 3000XT Series Option manual

GEM 202 operating instructions

GEM

GEM 202 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.