
ET2000 (500 SERIES) IRRIGATION CONTROLLER INSTALLATION ®
making
Controller wiring instructions (PD-1)
•Open cabinet door and remove the access
panel below the controller front panel.
•The Class 1 wiring (117 volt line input) may
be brought into the pedestal through a
conduit placed in the concrete base.
•The Partition in the pedestal separates
Class 1 and Class 2 wiring. The space on
the right of the partition is for the Class 2
wiring (valve and wiring other than Class 1
wiring). It is not necessary to run conduit
inside the pedestal.
•Follow the electrical hookup in the Model
ET2000 and ET2000e Wiring Diagram
sheet.
Controller wiring instructions (SSE, SSE-R)
•Bring 120 VAC line up to electrical 4 by 4
box via grounded conduit. Attach line
voltage to black, white, and green wires.
•A 120 VAC safety ground must be attached
to the GFI Ground terminal. Grounding must
be per national and Local codes.
•For increased irrigation controller protection
against lightning, a ground rod should be
used. Portions of the extended warranty
requires its use. Follow the Grounding
Instructions on the Grounding Sheet
provided with the controller. The lower left
lug of the terminal strip board (Transient
Protection Board TP-1) is for the grounding
rod.
Master valve (Blue wire)
•The master valve wire from the irrigation
controller provides a 24 VAC output to the
master valve. Connect the master valve wire
to the valve operating the main water supply
using the same common wire as the other
stations.
Pump Start Signal (Green wire)
•The green wire in the black wire harness
can be used to operate a 24 VAC relay
which turns on a pump. One side of the coil
of the relay should be connected to the
green wire of the black harness. The other
side should be connected to field common.
•Do not use relays which draw power causing
the total of all stations which can operate
simultaneously and the pump start relay to
exceed the 1.5A rating of the transformer.
Remote Control (Orange wire)
When connecting a Remote control interface cable,
use the same station wires and common as
connected to the field wires. The 24 volt wire on the
Radio Remote interface cable should be connected
to the orange wire on the black harness.
Flow Meter (Red and Black wires)
If a flow meter is used, it is to be connected to the
red and black wires on the black harness. Make sure
to connect the red wire from the controller to the red
wire on the flow meter, and the black wire from the
controller to the black wire on the flow meter. The
flow meter connections must be watertight or the
flow meter will not operate properly. NEVER use
buried splices. DO NOT connect flow meter to 24
VAC or 12 VAC outputs.
Rain Cups (Orange, White, Yellow wires)
Rain Cups are normally used to break the common
wire between the controller and the valves. DO NOT
install the rain cup in this manner with Calsense
irrigation controllers because it will disable some of
the controllers features. Installation should be done
according to the following diagram. Calsense
recommends either the Mini-clik or the WCS 4 wire
Rain Guard/ RG DCC which have mechanical
switches.
MINI-CLICK
YELLOW
CALSENSE CONTROLLER
BLACK WIRING HARNESS
BLUE
(SILVER WIRE)
BLUE
(COPPER WIRE)
WHITE
WHITE
BLUE
GREEN
RED
BLACK
ORANGE
Mini-clik wiring diagram