  9. Chenzhu CZ3055 User manual

Chenzhu CZ3055 User manual

CZ3055
Isolator The frequency transducer, frequency signal will be set according to the user to
convert the linear range 4~20mA (or 0~20mA)output.The product has one relay
alarm output.This product need be supplied independently,and the power
supply,input and output are isolated from each other.
1 2
Number of channels: 1
Supply voltag: 20~35V DC
Current consumption: (24V power supply,20mA output Relay closure)≤90mA
Input:
Signal type:
1) 3-wire PNP/NPN sensor output:
Sensor distribution: 14V DC, current: <20mA
Input frequency: 0.1Hz~100kHz
2) Frequency input signal:
Input frequency: 0.1Hz~100kHz
Maximum input voltage: 30Vp-p
Minimum input level: 2V, (2Hz~100KHz)
2V, (0.1Hz~100KHz)
3) Proximity switch, dry contact switch input:
Sensor distribution: approx≈8V; short-circuit current: approx≈8mA
Input frequency: 0.1Hz~100kHz
Output:
Current: 0~20mA/4~20mA
Load resistance: ≤400Ω
Voltage: 0~5V/1~5V
Load resistance: ≥300kΩ
Transfer accuracy: 0.1% F.S.
Temperature drift: 0.01%F.S./℃
Relay characteristics:
Response time: ≤20ms
Drive ability: 250V AC/2A or 30V DC/2A
Load type: Resistive load
Pulse width: ≥2μs
Input signal fault detection function:
If the input signal exceeds the top measuring range set,output current 22mA(or
output voltage 5.5V), the relay aets as the input, SPH LED ON, faceplate display “full”.
If the input signal fallen below the measuring range set, output current 3mA (or
output voltage 0.75V), the relay aets as the input, SPL LED ON, faceplate display
“nfull”.
If the input signal fault and input signal can’t transmission,output current2mA(or
output voltage 0.5V),the relay aets as the input, SPH.SPL ON,faceplate display “no in”.
input signal model is: in2.H/in2.r:
If the input loop-current I<0.1mA, proximity switch alarm(break line), output current
2mA,the relay aets as the input,SPH.SPL LED ON, faceplate display “inopn”.
If the input loop-current I>6mA, proximity switch alarm(shout circuit)output current
2mA, the relay aets as the input, SPH.SPL LED ON, faceplate display “insot”.
Note: If input signal top limit overflows or lower limit overflows or input signal
faults, the output current can be configured to any value of 0~24mA (0~6V for
voltage) separately.
Start delay time: 0~9999s
When the output relay is set to alarm mode with under-speed, the instrument
will not output an alarm signal during the launch delay time after power on due to the
under speed of input signal.
Input fault response time: 0.1~999.9s
The input signal pattern choice:
in H:Frequency input for NAMUR(2、3、4-wire sensor, dry contact
switch,incremental encoders)at Hz.
in r: Frequency input for NAMUR(2、3、4-wire sensor, dry contact
-1
switch,ncremental encoders) at min .
in2 H: Switching input for NAMUR,with input wirebreak and input short-circuit
recognition. at Hz.
in2 r: Switching input for NAMUR,switching input for NAMUR,with input wirebreak
-1
and input short-circuit recognition.at min .
-1
Not: If users need to switch measurement display unit, (Hz or min ), you need to
set measuring range、alarm、alarm hystersis and so on.
The LED indicator light instructions:
SPH: If the input signal exceeds the top alarm(contains dead band) LED ON.
SPL: If input signal fallen below the alarm(contains dead band) LED ON.
SPH、SPL ON: Input signal fault.
RAL ON: Output relay closure.
User Manual
YEAR
YEAR
WARRANTY
WARRANTY
Please read the instruction manual carefully before use the product,
and please safekeeping.
Caution
Please check whether the product type on the package accords
to the ordering contract;
Read this manual carefully before installation or using. If there is
something unclear,please dial technic support hotline-400 881 0780;
Supply voltage is 24VDC, 220VAC is forbidden;
Users are not allowed to dismantle or repair the Isolator otherwise
it will induce malfunction.
Add: Building 6, 201 Minyi Road, Caohejing Hi-Tech Park
Songjiang New Industrial Park, Shanghai 201612, P.R. China
Tel : +86-21-64513350 Fax : +86-21-64846984
Email:chenzhu@chenzhu-inst.com
http://www.chenzhu-inst.com
Summarize
Specification
CZ.CZ3055.11(S)E-5.0/17.11
3
Electromagnetic compatibility: According to GB/T 18268(IEC 61326-1)
Dielectric strength:
1500V AC;1minute(among power supply input and output )
Insulation resistance:
≥100MΩ;500V DC(among power supply,input,output and the shell)
Weight: Approx.150g
Suitable is apparatus:
Dry contact or DIN19234 standard NAMUR proximity switch input field devices
(including the intrinsically safe type pressure switch, temperature switches, liquid
level switch). Level pulse signal, 3-wire system PNP/NPN sensor output,
incremental encoder
1) Proximity switch, Input connection diagram:
Note: switch input, need to break and short circuit monitoring of the need to switch
to 10Ωresistors in parallel on both sides, and the switch side of the 400Ω~2kΩ
resistor in series.
2) 3-wire PNP output sensor connection diagram:
3) 3-wire NPN output sensor connection diagram:
4) PNP transistor output connection diagram:
Input connection diagram
10(-)
9(+8.2V)
9
10
10kΩ
400 2kΩ~Ω
5) NPN transistor output connection diagram:
6) Incremental encoders with HTL logse connection diagram:
7) Incremental encoders with push-pull connection diagram:
12(GND)
14(+14V)
BN
13(S)
BK
BU
Detection circuit
BN
BK
BU
24V
5 30V~
0V
OFF: Relay normally open
NCHSH: If input signal is higher than the top alarm(contains dead band), the output relay
closes.
NOHSH: If input signal is lower than the top alarm(contains dead band), the output relay
closes.
NCLSL: If input signal falls below the alarm(contains dead band), the output relay closes.
NOLSL: If input signal falls below the alarm(contains dead band), the output relay closes.
NCOUS: If input signal exceeds the top alarm, or falls below the alarm(contains dead
band),the output relay closes.
NOOUS: If input signal exceeds the top alarm, or falls below the alarm(contains dead
band),the output relay closes.
Alarm relay
Relays are normally open and SPST type. after power, After power up, the relay is set to
normally open or normally closed state according to the user about the configuration of the
relay by microcontroller. Relays can be arbitrary, independent setting one of seven kinds of
alarm modes. The alarm states of relay for measurement exceeds the range and for
measurement exceeds the alarm point are the same.
Normally open output: two relay contacts normally open(OFF)when the measered value
in normal.
Normally close output: two relay contacts normally closed(ON) when the measered value
in normal.
The relationship between relay actiens and measured values:
4
BN
BK
BU
12(GND)
14(+14V)
BN
11
BK
BU
RL≥2k
Mearsurement Relay alarm relationship with measured values
RANGH
SPH+HYSTH/2
SPH
SPH-HYSTH/2
SPL+HYSTL/2
SPL
SPL-HYSTL/2
RANGL
OFF
NCHSH
NOHSH
NCLSL
NOLSL
NCOUS
NOOUS
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
CZ3055
24V DC
+
DCS PLC、
-
-
+RL
3(+ ) 4(- )
1(+ )
2(- ) OUT1
OUT2
6
5
Dry contact
Frequency
pulse signal
PNP/NPN Transistor
+8.2V
F
GND
+14V
9(+ )
10( -)
12( -)
11( +)
14( +)
13(S )
9
9
10
10
Time
Operation Conditions
(1). The air should not contain any medium corrupting the coat of
chrome,nickel and silver.Moreover,violent quiver and impact or any cause
of electromagnetic induction (such as big current or spark,etc.)must be
avoided when using.
(2). Operating temperature: -20℃~+60℃
(3). Storage temperature: -40℃~+80℃
(4). Relative humidity: 10%~90%
Application
4~20mA
Proximity
detector
10kΩ
400~2kΩ
9
10
Detection circuit
12(GND)
14(+14V)
13(S)
12(GND)
14(+14V)
11
RL≥2k
12(GND)
11
12(GND)
11
CZ.CZ3055.11(S)E-5.0/17.11
User Manual
Symbols explain of relay alarm
5 6
During power-up delay relay contact output status:
When the relay is set to OFF,NCHSH or NOHSH, no start delay function, the
relay action based on measurements;
When the relay is set to NCLSL or NCOUS,the during power-up delay period,
the relay maintain open, after the power-up time, the relay action based on
measurements;
When the relay is set to NOLSL or NOCUS,the during power-up delay period,
the relay maintain close, after the power-up time , the relay action based on
measurements.
Instrument factory Settings
Input signal pattern: in.H
lower limit range: 0.100 Hz
Maximum range: 100.0 kHz
One alarm relay mode: OFF
Two alarm relay mod: OFF
Alarm low: 10.00 kHz
Alarm high: 90.00 kHz
Alarm low dead band value: 4000 Hz
Dead zone alarm high value: 4000 Hz
Start delay time: 10.0 s
Filter coefficients: 1
Input signal failure response time: 100.0s
Output signal: 4~20 mA(or 0~5V)
Fault alarm input current: 2.00 mA(or 0.5V)
The overflow alarm limit current: 22.00 mA(or 5.5V)
Overflow alarm limit current: 3.00 mA(or 0.75V)
M3
8.0
1
2
1
2
3
User Manual
Connections
(1)The isolators adopt knock-down terminals.
(2)The wires are single or multiple cables with cross section of 0.5
2 2
mm ~2.5mm .
(3)A length of 8mm bared wire is locked by the M3 bolt, As shown in
figure.
Mount the module on a 35mm DIN rail
(1) Make the upside of the isolator to the rail;
(2) Push the downside of the isolator towards the rail.
Installation
(1) Use a screwdriver (edge length≤6mm)insert the metal lock which at the
downside of the isolator;
(2) Push the screwdriver upwards,and pull the metal lock downwards;
(3) Take out the isolator from the rail.
Disassembly
(1) Every product has been tested strictly before delivery.If users find any
abnormality,please contact the nearest agent or our company.
(2) In 5 years from delivery date,if the product performs abnormally under
normal use conditions,we will repair it for free.
Maintenance
Dimensions
114.5mm×99.0mm×22.5mm
CZ.CZ3055.11(S)E-5.0/17.11

Other Chenzhu Relay manuals

Chenzhu GS8512-EX.12 User manual

Chenzhu

Chenzhu GS8512-EX.12 User manual

Chenzhu CZ3074 User manual

Chenzhu

Chenzhu CZ3074 User manual

Chenzhu CZSR8401-1A User manual

Chenzhu

Chenzhu CZSR8401-1A User manual

Chenzhu CZ3383.11 User manual

Chenzhu

Chenzhu CZ3383.11 User manual

Chenzhu GS8547-EX User manual

Chenzhu

Chenzhu GS8547-EX User manual

Chenzhu GS8572-EX.R User manual

Chenzhu

Chenzhu GS8572-EX.R User manual

Chenzhu CZ3038 User manual

Chenzhu

Chenzhu CZ3038 User manual

Chenzhu CZ3093 User manual

Chenzhu

Chenzhu CZ3093 User manual

Chenzhu CZSR8801-8A4B User manual

Chenzhu

Chenzhu CZSR8801-8A4B User manual

Chenzhu GS8536-EX User manual

Chenzhu

Chenzhu GS8536-EX User manual

Chenzhu CZ3047T User manual

Chenzhu

Chenzhu CZ3047T User manual

Chenzhu CZSR8001-3A1B User manual

Chenzhu

Chenzhu CZSR8001-3A1B User manual

Chenzhu GS8500 EX Series User manual

Chenzhu

Chenzhu GS8500 EX Series User manual

Chenzhu CZSR8201-3A1B User manual

Chenzhu

Chenzhu CZSR8201-3A1B User manual

Popular Relay manuals by other brands

Pilz PNOZ s30 operating manual

Pilz

Pilz PNOZ s30 operating manual

EOS SBM-LSG-IR installation instructions

EOS

EOS SBM-LSG-IR installation instructions

CARLO GAVAZZI RF1 Series quick start guide

CARLO GAVAZZI

CARLO GAVAZZI RF1 Series quick start guide

Leuze electronic MSI-SR-LC21DT03 Series Original operating instructions

Leuze electronic

Leuze electronic MSI-SR-LC21DT03 Series Original operating instructions

LVS LUT-SHUNT-FM installation instructions

LVS

LVS LUT-SHUNT-FM installation instructions

ABB KF Instruction leaflet

ABB

ABB KF Instruction leaflet

Siemens 3SK1120 Series Original operating instructions

Siemens

Siemens 3SK1120 Series Original operating instructions

Siemens 3RU7136 Series operating instructions

Siemens

Siemens 3RU7136 Series operating instructions

WEG PSRW user manual

WEG

WEG PSRW user manual

Eaton ZB12/XTOB BC1 Series manual

Eaton

Eaton ZB12/XTOB BC1 Series manual

GE T60 instruction manual

GE

GE T60 instruction manual

ELMON 31-33 operating manual

ELMON

ELMON 31-33 operating manual

Siemens 7SR210 Argus quick start guide

Siemens

Siemens 7SR210 Argus quick start guide

Pilz PNOZ s7 operating instructions

Pilz

Pilz PNOZ s7 operating instructions

GE IJS52D instructions

GE

GE IJS52D instructions

Climax CL-DR-RL16X8A installation guide

Climax

Climax CL-DR-RL16X8A installation guide

MICROENER ELR-3B instruction manual

MICROENER

MICROENER ELR-3B instruction manual

Fermax 2013 manual

Fermax

Fermax 2013 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.