CMP DEL AOP 25 User manual

4-2794-01 Rev.A
C-M-P.COM/DEL
OR VISIT C-M-P.COM/TECH
®
DEL AOP® 25 / DEL AOP® 40
INSTALLATION INSTRUCTIONS & PRODUCT MANUAL
53000-025-000
53000-040-000
®
Scan for
Step-by-step
instructions

2 Online Instructions: c-m-p.com/tech
IMPORTANT WARNINGS & SAFETY INSTRUCTIONS
READ AND FOLLOW ALL INSTRUCTIONS.
• Read this manual completely before attempting installation. Failure to install in accordance with the
installation instructions could void warranty and result in injury or death.
• All permanent electrical connections should be made by a qualied electrician.
• A pressure wire connector, labeled “bonding lugs”, is provided on the outside of the unit to permit
connection to a minimum No. 6 AWG (13.3 mm2) solid bonding conductor between this point and any
metal equipment, metal enclosures of electrical equipment, metal water pipes, or conduit within 5 feet
(1.5 meters) of the unit as needed to comply with local requirements.
• Install at least 5 feet (1.5 meters) from wall of pool. Install in accordance with the installation instructions.
• Follow all applicable electrical codes.
• DANGER ELECTRIC SHOCK HAZARD: Be sure to turn power OFF and disconnect from power
source before any service work is performed. Failure to do so could result in serious injury or death.
• The DEL AOP must be installed in an outdoor location, or indoors in a forced air ventilated room, and
installed so that the orientation is exactly as shown in following instructions. Install to provide water
drainage of generator to protect electrical components.
• Mount the DEL AOP so that it is inaccessible to anyone in the pool. Never attempt any servicing while
unit is wet.
• WARNING Short-term inhalation of high concentrations of ozone and long term inhalation of low
concentrations of ozone can cause serious harmful physiological eects. DO NOT inhale ozone gas
produced by this device.
• DANGER For your safety, do not store or use gasoline, chemicals or other ammable liquids or
vapors near this or any other appliance.
• NOTICE To maintain cosmetic integrity, protect this unit from direct prolonged sunlight exposure.
• WARNING To reduce the risk of injury, do not permit children to use this product.
• WARNING If unit is not operated according to instructions, high dosages of harmful substances may
potentially be released.
• ENVIRONMENTAL NOTICE - Hg-Lamp CONTAINS MERCURY. Manage in accordance with disposal
laws. See: www.lamprecycle.org
SAVE THESE INSTRUCTIONS!

Need help? c-m-p.com/support 3
TABLE OF CONTENTS
1: SYSTEM INFORMATION
1A. Description........................................................................................................................... 4
1B. Specications ...................................................................................................................... 5
2: INSTALLATION
2A. Location................................................................................................................................ 6
2B. Mounting.............................................................................................................................. 7
2C. Plumbing .............................................................................................................................. 7
2D. Electrical ............................................................................................................................... 9
3: OPERATION
3A. Pool Preparation................................................................................................................10
3B. Initial System Start-Up .....................................................................................................10
3C. Smart Status Indicators.................................................................................................... 11
3D. System Shut-Down............................................................................................................ 11
3E. Winterizing..........................................................................................................................12
4: MAINTENANCE & SERVICE
4A. System Electromechanical Overview ............................................................................13
4B. Ozone System Maintenance............................................................................................15
4C. UV System Maintenance..................................................................................................16
4D. Contact Information .........................................................................................................19
4E. Ordering Information...................................................................................................... 20
4F. Standard Replacement Parts List.................................................................................. 20
5: TROUBLESHOOTING & FAQS ......................................................................................................... 21
APPENDIX
Appendix A: Installation Plumbing ..................................................................................... 24
Appendix B: Pressure Drop Curve........................................................................................ 25
Appendix C: In-Place Quartz Tube Cleaning .................................................................... 26
Covered by one or more U.S. patents or pending patent applications. See c-m-p.com/patents for details.

4 Online Instructions: c-m-p.com/tech
1A. AOP 25/40 OVERVIEW
The DEL AOP Sanitizer System (Figure 1) is designed to provide the benets of ozonated and UV treated water in an
environmentally safe and eective manner. The system is certied to NSF 50 as a supplemental sanitizer and tested for
eectiveness to kill active microbes and bacteria. Operated according to the instructions, the DEL AOP virtually eliminates
the unpleasant eects of traditional chemicals. DEL AOP products are safe and harmless to your equipment when installed
properly.
Lamp Access Panel
Labels
2in Outlet
2in Inlet Smart
Status LEDs
Grounding Lugs
Access for
1/2in Conduit
Quarter-Turn
Camlock
Figure 1: System Exterior Overview
1. SYSTEM INFORMATION

Need help? c-m-p.com/support 5
1B. SPECIFICATIONS
Power Requirements:
• 110V/ 240V
• 60 Hz / 50 Hz
• AOP 25: 0.7 Amps, AOP 40: 1.1 Amps
Weights:
• Shipping Weight: 55lbs/25kg
• Dry Weight: 50lbs/23kg
• Wet Weight: 64lbs/29kg
Location Requirements:
• Mounting: Ground or Wall mounted
• Ambient Recommended Temperature: 30°F - 120°F (0°C - 50°C)
•
CAUTION
Water Level: Additional system back pressure created in certain applications or by certain accessories may
impact the system’s ability to pull vacuum properly. (Example: equipment below water level, in-oor cleaning system, spa
mode, etc) This can result in water pushing back into the ozone gas line and possibly into the ozone cell(s). Please consult
CMP if conditions exist that may introduce higher than normal back pressures (>3 psi).
Recommended Flow Rates
SYSTEM MIN FLOW NSF TESTED MAX FLOW
AOP 25 - 53000-025-000 10 GPM 30 GPM
AOP 40 - 53000-025-000 20 GPM 40 GPM
• The unit must meet the minimum ow rate to activate the internal ow switch. Below this ow rate the system will not
turn on.
• The NSF Tested max ow is the rate at which a 3-log disinfection rate is achieved to meet the supplemental sanitizer
requirements.
• Operation above the NSF Tested max ow the level of undissolved ozone in the system may increase. A Mixing De-gas
Vessel can be installed after the AOP system to remove excess ozone from the system.
NSF Testing
This product is designed for supplemental disinfection when operated according to these instructions, and should be used
with registered or approved disinfection chemicals to impart residual concentrations. NSF/ANSI 50, Section 13 disinfection
ecacy testing for 3-log (99.9%) or greater of Pseudomonas, Aeruginosa and Enterococcus Faecium. Specic residual levels of
EPA registered disinfection chemicals may be required by the regulatory agency having authority.
1. SYSTEM INFORMATION

6 Online Instructions: c-m-p.com/tech
2A. LOCATION
2A-1. Environment
Locate the unit in a clean, protected area, either indoors or outdoors (preferably out of direct sunlight). If possible, locate the
unit out of reach of sprinklers or drainage spouts.
2A-2. Clearance
Allow sucient access for maintenance (2 ft clearance above and 1 ft on either side of the unit) and all plumbing and electrical
hookups. Front clearance for door swing is approximately 14 inches.
24-1/4in
616mm
19in
481mm
20-3/8in
516.5mm
12-1/2in | 317mm
15-7/16in | 391mm
14-7/8in | 377mm
13-7/8in | 270mm
10-5/8in | 270mm
13.-3/8in | 340mm
3in
76mm
Figure 2: AOP 25 Installation Related Dimensions
3in
76mm
10-5/8in | 270mm
13-3/8in | 340mm
13-7/8in | 270mm
14-7/8in | 377mm
19-1/4in
488mm 20-5/16in
516mm
15-11/16in | 398mm
24-1/4in
616mm
12-1/2in | 317mm
Figure 3: AOP 40 Installation Related Dimensions
2. INSTALLATION

Need help? c-m-p.com/support 7
2B. MOUNTING
2B-1. Ground Mounting
The DEL AOP is shipped with the mounting brackets installed in the ground mounting position.
Adjust the position of the bracket if necessary and tighten the screws.
Mount the unit to the equipment pad through the slots provided on bracket using appropriate hardware for the mounting
surface.
2B-2. Wall Mounting
Four ¼”-20 screw holes are located on the back of enclosure for wall mounting as shown in Figure 4.
1. Remove plastic screws from back of the unit.
2. Remove mounting brackets from bottom of enclosure, re-assemble them to back of enclosure.
3. Mount unit to wall through the slots on brackets using appropriate hardware for the mounting surface.
Four 1/4in - 20
Screw Holes
for Wall Mounting
10-5/8in | 270mm
10-5/8in | 270mm
Figure 4: Wall Mounting Hole Pattern
2C. PLUMBING
The DEL AOP can easily be added into the pool plumbing loop. All system components are inside the enclosure. Only the
water inlet and outlet need to be installed into the pool return line.
2C-1. Plumbing Location
• Install in the pool main return line after all other pool equipment (pump, lter, heater, and cleaner).
• The outlet must be at least 10 feet from the rst return to the pool. If installing a mixing de-gas vessel (MDV), allow 10
feet from the outlet of the MDV to the rst pool return.
• Use the union ttings provided to connect the DEL AOP inlet and outlet to pool plumbing as shown in Figure 5.
• For installation with additional sanitizers and pool cleaners, see Appendix A. Figures 2 & 3 show related dimensions.
Figure 5 shows a simplied plumbing diagram.
2. INSTALLATION

8 Online Instructions: c-m-p.com/tech
HeaterFilterPump DEL
AOP 25/40
MDV XL
(if required)
Backflow
Check Valve
(optional)
From Pool
Return to Pool
Powerclean
Tab Feeder
Figure 5: DEL AOP Typical Location in Pool Plumbing Loop
2C-2. About the Mixing De-gas Vessel (optional)
Under normal operation, bubbles will appear in the return ow to the pool. To remove the bubbles from the ow, an
accessory Mixing De-gas Vessel, or MDV, can be installed downstream of the DEL AOP. The MDV is designed for use with the
DEL AOP and is recommended on indoor, covered, or vinyl-lined pools. It should also be used if a tab feeder in installed after
the AOP system. For more information, please visit c-m-p.com/support.
2C-3. Above Water Level Installation: Water Backow Check Valve
If the pool equipment is mounted above the water line, install a 2 inch CMP Hydroseal check valve (25830-400-000) between
the pump outlet and the inlet of DEL AOP to prevent the pump from draining and losing prime when not in use.
2C-4. High Return Pressure Installation: Orice Plate (AOP 25 ONLY)
The AOP 25 will function best when the pool equipment is above water level and there are no accessories introducing
additional pressure on the return line. In cases where the return line pressure prevents proper operation, an orice plate may
be added to the inlet of the spring-loaded check valve. This can improve injector performance.
1. Flow Meter Test (Fig 6a) : If there is any question whether the injector is performing properly, a ow meter is provided in
the parts kit to check for proper suction through the ozone cell.
a. Operate the pool in the mode expected to introduce the highest return pressure.
b. Remove the air lter from the ozone module.
c. Attach the tubing from the ow meter to the ozone module.
d. Hold the ow meter vertically and observe that the ball is above the “MIN” line. The ball may be bouncing but
should average mostly above the line. The “MAX” marking can be ignored for this test.
e. If the ball is not moving or is consistently below the “MIN” line, Install the orice plate.
Air Filter
Ball
Flow Meter
Assembly
Ozone Module
Figure 6a : Flow Meter Test
2. INSTALLATION

Need help? c-m-p.com/support 9
2. Orice Plate Installation (Fig 6b).
a. Loosen the union ttings on both the inlet and outlet of the check valve to remove it from the system.
b. Insert the orice plate on top of the check valve with the cone shape downward.
c. Reinstall and tighten union ttings.
Check Valve
Orifice Plate
Figure 6b : Orice Plate Installation
2C-5. Leak Test
Turn on pool circulation system and run at highest normal operating pressure. Check for leaks outside and inside of the AOP
system. Correct any leaks outside of the system. If any leaks are found inside the AOP, contact Customer Service at c-m-p.
com/support.
2D. ELECTRICAL
2D-1. Main Power
• Connect to the pool timing clock so that the DEL AOP operates simultaneously with the pool pump.
• An access hole is provided for a 1/2” conduit tting. Install tting (not provided) and run wire to terminal block inside
unit.
• Connect Line 1, Line 2 or Neutral, and Ground to the terminal block as indicated by the label on the electrical panel
located on the inner right side of enclosure (see Figure 7).
• If there is no timing clock or automation system available, the system can be installed on the line voltage along with
the variable speed pump.
Refer to the IMPORTANT SAFETY INSTRUCTIONS at the beginning of this manual for important wiring information.
2D-2. Grounding Lug
Using a solid copper conductor, connect to the grounding lug on the right side of the DEL AOP to an appropriate earth
contact.
2. INSTALLATION

10 Online Instructions: c-m-p.com/tech
Terminal
Block
Label for
Wiring
Instructions
Access for
1/2in Conduit
Figure 7: Terminal Block and Wiring Instructions
3A. POOL PREPARATION
To achieve optimal performance the pool must be as clean as possible to start with.
1. Backwash or clean lters one day before starting the AOP System.
2. Raise chlorine level to APSP recommended levels so the water has a sustained 1-3 ppm free chlorine level.
3. Test pool chemistry and adjust pH between 7.4 and 7.6. Adjust total alkalinity between 80 and 120 ppm.
4. Run pool ltration continuously for 24 hours prior to starting the AOP system.
3B. INITIAL SYSTEM START-UP
Upon completing all of the system connections and cleaning the pool as outlined in SECTIONS 2C through 3A, you are ready
to start the DEL AOP.
1. Check electrical connections at breaker box.
2. Turn on pool circulation system and the Smart Status LEDs will turn on automatically.
3. OPERATION

Need help? c-m-p.com/support 11
Blue
Green
Purple
Figure 8: LED Indications at Normal Operation
3C. SMART STATUS INDICATORS
The DEL AOP has indicator lights to indicate its working condition. The lights should display the correct colors after the pump
has reached steady ow (see chart on page 5). During normal operation, refer to the chart below for status information.
STATUS POWER INDICATOR UV-C INDICATOR OZONE INDICATOR
REGULAR OPERATION GREEN PURPLE BLUE
OZONE SERVICE DUE GREEN PURPLE YELLOW
UV-C SERVICE DUE GREEN YELLOW BLUE
OZONE ERROR/FAULT RED PURPLE RED
UV-C ERROR/FAULT RED RED BLUE
OZONE SERVICE OVERDUE YELLOW PURPLE BLINKING RED
UV-C SERVICE OVERDUE YELLOW BLINKING RED BLUE
SYSTEM ERROR/FAULT RED RED RED
For more detailed status information refer to Trouble Shooting Section (SECTION 5).
3D. SYSTEM SHUT-DOWN
The following sequence of steps must be followed for servicing or for storage.
1. Shut o power at the breaker.
2. Shut o water to the unit.
3. OPERATION

12 Online Instructions: c-m-p.com/tech
3E. WINTERIZING
If the pool will be shutting down for the winter months and the DEL AOP will remain exposed to freezing temperatures, the
unit must be drained to prevent freeze damage. Follow the steps below to drain.
1. If mounted below the water level, bypass valves must all be CLOSED to prevent excess water from draining through the
unit.
2. Open the enclosure door.
3. Locate the 1” NPT drain plug (Refer to Figure 9) and remove to drain the remaining water.
4. Water will drain through holes in the bottom of the unit. Alternatively a connection can be made at the 1” NPT drain to
run water away from the unit.
5. Allow all the water to drain before threading the plug back into the plumbing. Be sure to clean any excess water that
may have collected in the bottom of the unit.
Winterizing
Plug
Figure 9: Winterization Plug Location
3. OPERATION

Need help? c-m-p.com/support 13
4A. SYSTEM ELECTROMECHANICAL OVERVIEW
CAUTION Disconnect power before performing service. Refer to the IMPORTANT SAFETY INSTRUCTIONS displayed
in the front of this manual.
UV-C
Reactor
Flow
Switch
Variable
Speed
Check Valve
Smart
Status
Reset
Injector
Manifold
Power
PCB Board
APG2
Air Filter
APG2
Ozone
Modules*
Ozone
Gas Line
UV-C Lamp
Ozone
Check
Valve
Figure 10: DEL AOP Electro-Mechanical Overview
(AOP 40 Shown)
4A-1. Ozone Module Description
*The DEL AOP is constructed with one (AOP 25) or two (AOP 40) APG2 corona discharge ozone modules. Blue ozone light on
system smart status LEDs indicate ozone modules are operating properly (refer to Figure 8 for a more detailed view).
4A-2. Injector Manifold Description
Water owing through the injector manifold generates the vacuum that draws ozone into the water. The spring-loaded valve
automatically adjusts for various water ow rates to keep the DEL AOP operating over a wide range of conditions.
4A-3. Ozone Gas Line Description
Gas from the ozone modules is drawn through the ozone gas Line by the injector and into the water. The ozone check valve
(refer to Figure 12) in this line prevents water from migrating back to the ozone modules when the DEL AOP is not running.
4A-4. Ozone Module Air Filter Description
The air entering the ozone modules passes through the air lter (refer to Figure 11) on each module inlet. The lter is held in
place by the rubber lter cap.
4. MAINTENANCE & SERVICE

14 Online Instructions: c-m-p.com/tech
4A-5. Injector Tube Adapter Description
This component connects the ozone gas line to the injector manifold (refer to Figure 12). When servicing this component, do
not tighten past 10 in-lbs torque or the component may be damaged.
APG2
Ozone
Modules
Orthographic View Angle View
Air
Filter
Ozone
LED
Indicator
Air
Filter
Ozone
Gas Line
Check
Valve
Injector
Tube Adapter
Figure 11: Ozone Generator System Overview
4A-6. Ultraviolet Lamps Description
There are two lamps in each Del AOP unit. The violet UV-C light on system smart status LEDs indicates UV lamps are
operating properly (see Fig 10). If the UV lamp access panel is removed while the unit is running, the unit will be shut down
automatically. (see Fig 12). The lamps are each housed in a quartz tube that protects the lamp.
.
Panel Switch
Figure 12: Panel Switch Protection for UV Lamps
4. MAINTENANCE & SERVICE

Need help? c-m-p.com/support 15
4B. OZONE SYSTEM MAINTENANCE
4B-1. Ozone Module Replacement
• Ozone module life expectancy is three (3) to ve (5) years. All ozone cells should be replaced at the same time.
• The Smart Status LED for Ozone will change to yellow when it is time to replace the ozone module.
• There is also an LED indicator on the ozone module itself. However, even if the ozone module light(s) are glowing, the
module should be replaced when the Smart Status indicates it is time to change. The ozone module may be producing
little or no ozone after this period of time.
To replace ozone module:
1. Shut o power at the breaker.
2. Unplug the connector from power PCB board by unlatching hook Tab on connector (refer to Fig 13).
3. Take o old ozone module from ozone generator mounting panel using an Allen Wrench.
4. Disconnect air lter and tubing from old ozone module.
5. Reconnect air lter and tubing to new ozone module.
6. Mount new ozone module to the panel.
7. Plug connector of new ozone module to the mating connector on power PCB board.
8. Reset ozone indicator by pressing button on the inside door behind the Smart Status indicators. (Fig 10)
Ozone Generator
Connector
Figure 13: Ozone Generator Connector Location
4. MAINTENANCE & SERVICE

16 Online Instructions: c-m-p.com/tech
4B-2. Ozone Gas Line Replacement
Replace the ozone gas line every year or sooner, if needed. (P/N 9-1352-01) If there is evidence of water leaking past the
ozone check valve toward the ozone modules, shut down the DEL AOP immediately and replace the ozone gas line.
1. Shut o power at the breaker.
1. Shut o water to the unit.
2. Loosen tubing clamps on both ends of the ozone gas line. Remove tubing assembly from air barbs of injector tube
adapter and T-tting adapter.
3. Orient ozone gas line as shown in Figure 11. Re-connect it on both ends and clamp tight.
WARNING Trace amounts of nitric acid may be present in the ozone gas line. Wear proper safety equipment (gloves
and eye protection) and avoid direct contact with any condensation in the line.
4B-3. Ozone Air Filter Replacement
1. Air lter should be replaced yearly.
2. Remove worn or dirty ozone air lter from air barb on ozone generator.
3. Install new ozone air lter (P/N 9-0858-01) on ozone generator air barb as show in Figure 11.
4B-4. Injector Tube Adapter Replacement
• Remove if worn or dirty
• Loosen or remove the tubing clamp. Use pliers if necessary to twist and unlock the clamp.
• Pull the tubing from injector tube adapter and unthread the adapter from the injector.
• Apply Teon® based thread sealant and install new connector. (P/N 7-1434-01)9
• Do not tighten over 10 in*lb.
4C. UV SYSTEM MAINTENANCE
4C-1. UV Lamp Replacement
Life expectancy of UV lamp is about 16,000 hours.
• The Smart Status LED for UV-C will change to yellow when it is time to replace the lamps. It is recommended to
replace all UV lamps at the same time.
• AVOID TOUCHING THE UV LAMP GLASS WITH YOUR BARE HANDS. Oils on your hands can cause hot spots on the
UV lamp and shorten its life. Use a soft clean cotton cloth or clean cotton gloves to handle the UV lamp.
To remove the UV lamp from UV reactor, follow below steps.
1. Shut o power at the breaker.
2. Locate the UV lamp access Panel on the top of the DEL AOP. Remove the 4 screws with a Phillips head screwdriver, and
remove the panel.
3. After allowing adequate time for the lamps to cool, disconnect the lamp connectors from ballast wire connector.
4. Grasp the UV lamp wires and gently pull until the top of the UV lamp has pulled past the lamp retainer tabs.
5. While holding the UV lamp white ceramic cap, slowly pull the UV lamp until the bottom has pulled past the lamp retainer
tabs. (Twisting the lamp may help facilitate removal.) Do not touch glass, as oils on your hands will damage the bulb.
4. MAINTENANCE & SERVICE

Need help? c-m-p.com/support 17
Lamp
Connector
Ballast
Wire
Connector
Lamp
Retainer
Figure 14: UV Lamp Replacement
To re-install the UV lamp:
1. Conrm power is o at the breaker.
2. Do not touch glass, as oils on your hands will damage the bulb. By holding the UV lamp white ceramic cap, slowly
press the UV lamp fully past the lamp retainer tabs and into the quartz tube until it is seated on the lamp cushion in the
bottom of the tube.
3. Connect the lamp connector to the connector on the ballast.
4. Install UV lamp access panel.
5. Reset UV indicator by pressing button on the inside door behind the Smart Status indicators. (Fig 10)
4C-2. Quartz Tube Removal and Cleaning (Every Six Months)
The UV lamps are housed in a quartz tube. If the quartz tube becomes dirty, its ability to transmit UV rays from the lamp will
be diminished. The quartz tube(s) should be removed from the UV reactor every six (6) months and cleaned if necessary.
Note: For instructions on cleaning without mechanical disassembly, see Appendix C.
Note: If the DEL AOP is installed below water level, the bypass valves must all be CLOSED to prevent excess pool water from
draining into the open unit when a quartz tube is removed.
4. MAINTENANCE & SERVICE

18 Online Instructions: c-m-p.com/tech
Drain Plug
Lamp Retainer
Retainer Screws
& Washers
Ceramic
Endcap
Sealing
O-ring
Figure 15: UV Reactor Subassembly
1. Before continuing, allow adequate time for the quartz tubes to cool. Drain the water from the UV reactor by removing the
drain plug. Replace the plug once water has stopped exiting the UV reactor.
2. After removing the lamps, remove the top lamp retainer screws using the hex key included in the parts bag. Place the lamp
retainer screws, washers and the lamp retainer aside in a safe place.
3. Using the hex key included in the parts bag, loosen the bottom lamp retainer screws two full rotations.
4. Grasp the quartz tube from the top of the UV reactor. Pull to remove it from the UV reactor.
5. Remove the sealing O-ring from the top of the quartz tube. Set aside in a safe place. NOTE: O-Rings in the bottom
endcap of the reactor do not need to be removed for quartz tube service.
6. Clean the quartz tube exterior with a mild solution of muriatic acid (available at all pool supply stores) and water in a ratio
of four parts water to one part acid (4:1). If lime or hard water calcium deposits are encountered, use a household tub
and shower lime remover.
7. After cleaning the quartz tube, wash it o and wipe dry. Inspect the quartz tube for cracks. Replace if cracks are found.
Make sure the inside of the quartz tube is dry before replacing the UV lamp(s).
CAUTION Follow the directions for use and handling of muriatic acid on the acid bottle label, being careful to
protect your eyes, wear rubber gloves, and avoid breathing acid fumes.
Note: DO NOT USE ABRASIVE CLEANERS as they can scratch the high quality quartz glass. Note: DAMAGE CAUSED BY
BROKEN QUARTZ TUBES ARE NOT COVERED UNDER YOUR LIMITED WARRANTY.
4C-3 Quartz Tube Installation
1. Holding the quartz tube so it is oriented straight up and down. Insert the quartz tube into the UV reactor until it is fully
seated in the bottom of the UV reactor.
Note: If the end of the quartz tube is protruding from the UV reactor, the alignment is o. Remove and re-insert the
quartz tube to seat it properly as shown in Figure 16.
2. Place a sealing o-ring approximately 1/2in (12.5mm) from the end of the quartz tube protruding from the top of the UV
reactor.
4. MAINTENANCE & SERVICE

Need help? c-m-p.com/support 19
3. Place the lamp retainer over the quartz tube. Use the hex key included in the parts bag to attach the lamp retainer to the
UV reactor, using the lamp retainer screws and washers as shown in Figure 15. Make sure the lamp retainer anges are
fully seated against the UV reactor.
4. Turn the circulation pump ON and check the quartz tube seal for leaks.
5. Turn the circulation pump OFF once you have conrmed that the quartz tube is not leaking.
CAUTION Wear proper eye and skin protection for servicing glass components. If broken glass is trapped in the
pool system, do not operate the pool. Contact a service professional to have the glass removed.
Properly
Seated
Quartz
Tube
Improperly Seated
Quartz Tube
Figure 16: UV Quartz Tube Installation
4D. TECHNICAL CONTACT INFORMATION:
For technical assistance call: 1 (800) 733-9060 or visit our website: www.c-m-p.com/support
Be prepared with the following information:
• Name
• Address
• Model #
• Date Purchased
4. MAINTENANCE & SERVICE
OR VISIT C-M-P.COM/TECH
Scan for
Step-by-step
instructions

20 Online Instructions: c-m-p.com/tech
4E. ORDERING INFORMATION:
To locate a dealer nearest you call 1 (800) 733-9060 or visit www.c-m-p.com.
4F. STANDARD REPLACEMENT PARTS LIST
DESCRIPTION AOP 25 AOP 40
UV-C LAMPS 9-1626-02 9-1626-01
OZONE GAS LINE 9-1352-01
OZONE CELL 9-1565-01 (ONE PER UNIT) 9-1565-01 (TWO PER UNIT)
INJECTOR TUBE ADAPTER 7-1434-01
AIR FILTER 9-0858-01
Note: The warranty is void if the parts listed above are not replaced at recommended intervals.
4. MAINTENANCE & SERVICE
This manual suits for next models
3
Table of contents
Other CMP Accessories manuals