CommScope DryLine ODPMT200 Series User manual

ODPMT200 SERIES DryLine®
DEHYDRATOR
USER MANUAL
Bulletin AE01B-A0467-001 Rev: E
© 2007 - 2013 CommScope, Inc. All rights reserved (01/13)

ODPMT200 Series DryLine®Dehydrator User Manual
2
TABLE OF CONTENTS
Section 1 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Introduction... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .3
1.2 Description ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .3
1.3 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.4 Triple Alarm Option ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .4
Figure 1 - Alarm Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Figure 2 - Changing Alarm Outputs: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
1.5 Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Section 2 Installation .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ..6
2.1 Inspection ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .6
2.2 Controls and Displays.. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .6
2.3 Installing the Dehydrator ... ... ... ... ... ... ... ... ... ... ... ... ... ... .7
2.3.1 Slab Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.4 Power Connections ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .7
2.4.1 AC Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.5 Connecting the Low Pressure Alarm Output .. ... ... ... ... ... ... ... ... ... .7
2.7 Connecting Dehydrator to the Transmission Line.. ... ... ... ... ... ... ... ... .8
2.8 Purging the Transmission Line .. ... ... ... ... ... ... ... ... ... ... ... ... .8
Section 3 Maintenance ... ... ... ... ... ... ... ... ... ... ... ... ... ... ..9
3.1 Maintenance .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .9
3.2 Regular Maintenance .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .9
3.3 Preventive Maintenance ... ... ... ... ... ... ... ... ... ... ... ... ... ... .9
3.4 6000 Hour Overhaul ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .9
3.5 Annual Maintenance... ... ... ... ... ... ... ... ... ... ... ... ... ... ...10
3.6 Parts Replacement and Dehydrator Overhaul. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.7 Dehydrator Filter Element Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.8 Service Restoration ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...12
Section 4 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 3 - Schematic With All Options ... ... ... ... ... ... ... ... ... ... ...14
Figure 4 - Alarm(s). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Section 5 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Section 6 Customer Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.1 Introduction... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...16
6.2 In Case of Trouble . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.3 Initial Steps by CommScope ... ... ... ... ... ... ... ... ... ... ... ... ...17
6.4 Repair Center Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.5 RoHS Inquiries ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...17
Figure 5 - Hole pattern for locateing J bolts in cement slab. ... ... ... ... ... ...19

ODPMT200 Series DryLine®Dehydrator User Manual
3
1.1 Introduction
This manual contains the information you need
to install, operate and maintain your ODPMT200
Series DryLine™ dehydrator. Please take the
time to read this manual before attempting to
operate or service the unit.
1.2 Description
ODPMT200 Series dehydrators provide dry air
for pressurizing small (up to 40 cubic feet, or
560 liters, in volume) antenna and transmission
line systems. The dehydrators produce -49ºF
(-45ºC) dewpoint dry air at an output rate of 0.2
cubic feet (1.4 liters) per minute.
Each dehydrator consists of an electrically-
driven air compressor, a membrane dryer
assembly, an automatic transmission line
pressure sensing system and a low-pressure
alarm output housed in a rigid metal chassis.
Theyaredesignedtomounttoaslaboor.
Optional brackets are available for pole
mounting capability. Their front panels feature
a pressure gauge, an indicating on/off switch, a
resettable circuit breaker, and a run time meter.
For easy serviceability, power connections,
alarmoutputconnectionsandalllterelements
are accessible from the front of the unit.
The ODPMT200 maintains transmission line
pressures at 5.0 lb/in2 (34 kPa). It is intended
for standard microwave antenna applications
and any other transmission line pressurization
requirement that supports a relatively high
pressure limit.
1.3 Operation
ODPMT200 Theory of operation.
The ODPMT200 series of DryLine™
dehydrators, while similar in moisture removal
technology, operates differently than the rest of
the DryLine™ series of dehydrators. In order to
provide a constant supply of dry air to small air
volume systems, and to maintain an acceptable
moisture level in the product air stream, a high-
pressure reservoir tank is needed. This reservoir
tank is connected to a pressure regulator and
oricetoyieldaxedoutputpressureof5.0psig
andanominalowrateof0.2CFM.Inaddition
to supplying the output air, the reservoir tank
also provides the dry air for the feedback loop.
The feedback loop is necessary to maintain the
dryness of the membrane cartridge.
During normal operation, the bleed air in the
feedback loop will cause the pressure to drop in
the internal reservoir tank, and the ODPMT200
compressor will cycle automatically. These
cycles will take place regardless of the system
volume or condition of the transmission line the
dehydrator is connected to. The rate of these
cycles, however, will vary. During the purge
cycle,thedehydratorwillcycleapproximately
every 2 to 4 minutes while showing 0 psig on
the pressure gauge and providing a constant 0.2
SCFM of dry air.
When connected to a very tight system, or
the output is capped, the dehydrator will
cycleapproximatelyevery60to90minutes
and maintain 5.0 psig system pressure while
providing close to 0 CFM of dry air. A system
that leaks will have a cycle time somewhere in
between, depending on the severity of the leaks.
Section 1
General Information

ODPMT200 Series DryLine®Dehydrator User Manual
4
Thepressuregaugewillalsoreectapressure
between0and5.0psigwhiletheoutputow
is between 0.2 and 0 SCFM. The pressure
gaugesensespressurebeyondtheowcontrol
oriceandwillshowtheactualpressureinthe
waveguide.
During the initial pressurization of the
transmission line, the dehydrator will cycle
every 2 to 4 minutes with the system at 0 psig
pressure. As the dehydrator pressurizes the
system, the cycle times will increase until the
dehydrator output is balanced with the system
leak, at which point the cycle times will stabilize.
1.4 Triple Alarm Option
This optional assembly is designed to provide
theadditionalExcessRun,HighHumidityand
Power Fail alarms to CommScope Dehydrators.
All alarms are Form C dry contacts and are
factory set for continuity at alarm.
Theexternalalarmmonitoringsystem(not
included) is connected to the terminal strip
located behind the cover. A small slotted
screwdriver is necessary to make the
connections.
The connection to the alarm strip is as follows,
and refer to Figure 1 for correct locations and
colors of the wires on the terminal strip.
Term. Function Wire Color
1 Power Fail Com Black
2 Power Fail Alarm Red
3 Humidity Com Green
4 Humidity Alarm Brown
5 ExcessRunCom Blue
6 ExcessRunAlarm White
7 Low Press. Com. Grey
8 Low Press. Alarm Orange
Alarm Denitions:
Low Pressure:
Ifsystempressurefallssignicantlybelowthe
low-pressure trigger point, the low-pressure
alarm sensor will activate an alarm contact.
Thisalarmisanindicationofasignicant
system leak or a dehydrator failure.
Excess Run:
User settable run time to be set in accordance
with the normal run time for the particular
application. Selectable times are 10, 30, 120
and 240 minutes. See Figure 2 for location of
JP3.
Power Fail:
Activates when power is removed from the
dehydrator. This includes turning the power off
at the switch.
High Humidity:
Activates when system or dehydrator output
humidity rise above 7.5% relative humidity.
At initial installation, this alarm will continue
to alarm until the system has been properly
purged.
ALARM
.5
*6*
*3*
*2*
*1*
*5*
*8*
*7*
*4*
L.P.
X.R.
H.H.
P. F.
Figure 1 - Alarm Label

ODPMT200 Series DryLine®Dehydrator User Manual
5
Figure 2 - Changing Alarm Outputs:
1.5 Specications
Output Pressure Constant 5.0 psig
Output capacity 12.0 SCFH (80Iiters/h)
(total,approx.)0.2
SCFH (1.5 liters/m)
Output Dew Point, -49°F (-45°C) or better
Operating Temperature -30° to +130° F
Range (-34° to +54° C)
Low Pressure Alarm 1.0 lb/in2 (6.9 kPa)
Electrical Input 115 Vac, 50/60 Hz
Output Connector 3/8” polytube,
compression
Dimensions 18.5”Wx32.0”Hx
10.0” D
Optional Alarms:
High Humidity Alarm
Set Point 7.5% RH, factory set
ExcessRunAlarm
Set Point 10 minutes, factory set
Power Fail Alarm loss of input power
Alarm Factory setting Where To
Reset
Low Normally Alarm switch
Pressure Closed (N.C.) center term.
N.O., bottom
term N.C.
Mains Normally Power Fail
(Power) Open (N.O.) Jumper JP6 on
Alarm PCB
Excess Normally JumperJP5on
Run Open (N.O.) Run Alarm
PCB
High Normally Jumper JP4 on
Humidity Open (N.O.) Alarm PCB

ODPMT200 Series DryLine®Dehydrator User Manual
6
Section 2
Installation
2.2 Controls and Displays
Familiarize yourself with the controls and
displays prior to installing or testing the
dehydrator.
Dehydrator Controls/Displays
2.1 Inspection
Open carton.
Remove the top piece of corrugated packing.
Carefully remove the installation accessories
and manual and dehydrator. Check the
dehydrator for shipping damage such as dents
or loose parts.
Pressure Gauge - indicates dehydrator output
pressure in psig and kPa.
ON/OFF Switch - controls compressor and
sensors. Light indicates power switch is ON.
Circuit Breaker - white tab indicates a circuit
overload. Push to reset.
To comes from compressor and
connectstothelterbowls.

ODPMT200 Series DryLine®Dehydrator User Manual
7
Un-Time Meter - provides a visual indication of
the number of hours of compressor operation
and provides validation for the 3000 hour
warranty.
2.3 Installing the Dehydrator
2.3.1 Slab Mounting
See the back of this manual page 21 for a
drawing showing hole placement and overall
size of the unit.
2.4 Power Connections
Conrmyourdehydratorelectricalinputmatches
the available power.
Ensure an electrical safety ground
is installed on the ground stud
located adjacent to the power input
connector. (It is intended to be
customer installed in the eld to your
halo grounding system.)
115 Vac
ODPMT200-89015
ODPMT200-89315
2.4.1 AC Power
AC units can be connected into a standard 15
amp power receptacle of the proper voltage.
Make sure the power circuit is properly
grounded.
Verify the power switch is OFF. Feed the power
cable (not supplied) through the liquid-tite
ttingonbottomofunit.Connectpowercable
toinputterminalstriponunit.Useasmallat
blade screwdriver to tighten connections on
the terminal strip. After power connections are
Proper electrical connection is
required. It is suggested a licensed
electrician be contracted to connect
the AC wiring to the unit, if it is
connected directly to the mains.
Failure to properly connect the power
wires could result in a dangerous
electrical shock hazard.
Test the Dehydrator
Turn the dehydrator ON and check the output
port inside the front cover to make sure air is
owing.
2.5 Connecting the Low Pressure Alarm Output
To connect the low pressure alarm, open the unit
and locate the terminal block (TB-1).
completed, tie-wrap power-cable in place and
tightentheliquid-titettingaroundpowercable.
See schematic on page 21 for input connections.

ODPMT200 Series DryLine®Dehydrator User Manual
8
Route the wires from the alarm control through
theliquid-titettingatbottomofunitintothe
chassis and up to the terminal block
Tighten the screws on the terminal block, tie
wrap the alarm cable, and tighten the liquid-tite
tting.
Whenalowpressurealarmconditionexistsdry
contacts are activated at terminal block TB-1.
Analarmconditionexistswhenpressurefalls
below 1.0 lb/in2 (6.9 kPa) for all ODPMT200
models. The relay contacts are rated at 2 A (non-
inductive), 30 Vdc.
Optional alarms (if purchased) will also be
located on this terminal block. The alarm
connection label, located inside of the front
cover, will provide terminal numbers for each
additional alarm.
2.7 Connecting Dehydrator to the Transmission
Line
Check the antenna and transmission
line system pressure rating before
connecting the dehydrator to the
system.
Insert one end of the 3/8” polytube feed line
tubingintothecompressionttingonthe
dehydrator inside wall, or one of the similar
ttings.Tightensecurelywitha9/16”wrench.
Be careful not to over tighten. Connect the other
end of the polytube to the transmission line.
Two air outputs are provided, with individual
shut-off valves on the front of the unit. Make
sure that the valve is open position for each
transmission line connection. If one of the
outputs connection is not used, close the valve
and leave the port capped.
Note:
If the transmission lines have not been
purged, continue with section 2.8. Otherwise
proceed to Section 3.
2.8 Purging the Transmission Line
Air in the transmission line system must be
replaced with dry air to ensure satisfactory
opera-tion of the transmitted signal.
1. Determine the total system volume.
2. Dividethesystemvolumebytheowrate
of the dehydrator (12 CFH) to determine the
number of hours needed for the purge cycle.
3. Open the far end of the transmission line.
4. Operate the dehydrator for one purge cycle.
If it is not possible to open the far end of the
transmission line:
1. Connect the dehydrator to the trans mission
line and pressurize the system.
2. Wait 45 minutes while the air absorbs
moisture in the system, then disconnect the
dehydrator from the transmission line and
allow the air to vent.
3. Repeat steps 1 and 2 three times to purge
the system.

ODPMT200 Series DryLine®Dehydrator User Manual
9
Section 3
Maintenance
3.1 Maintenance
The ODPMT200 Dehydrator requires relatively
little maintenance to ensure satisfactory
operation over long periods of time. This section
outlines the recommended annual preventive
maintenance for the unit and the suggested
overhaul for every 6000 hours of compressor
operation.
3.2 Regular Maintenance
The ODPMT200 Dehydrator will perform at an
optimum if it is routinely checked for correct
performance. This checking generally consists
of an annual inspection of the condition of the
airintakelterandanoverhaulafterevery6000
hours of compressor operation. Performance of
thesemeasuresissufcienttoensurecontinued
reliable operation.
3.3 Preventive Maintenance
The annual maintenance of an ODPMT200
consists of a preventative maintenance
inspection of the dehydrator and cleaning (or
replacement)ofthefoamairintakelter.
These tasks can easily be performed in the
eldwiththeunitconnectedtothetransmission
line system and with only the front access door
opened for maintenance.
3.4 6000 Hour Overhaul
A run-time meter is provided on the front of the
ODPMT200 to indicate the actual number of
hours the compressor inside the dehydrator has
run.
The dehydrator overhaul kit includes parts
to overhaul the compressor and critical
components in the dehydrator that often become
worn over time.
Theseincludereplacementwaterlterelements
with new o-rings, and a length of white nylon
tubing.
A compressor overhaul kit is also part of the
dehydrator overhaul kit.
This kit contains a new cylinder and piston,
along with new gaskets and head screws.
In Case Of Difculty: If the dehydrator is not
operating, refer to the sections on installing and
troubleshooting the unit.

ODPMT200 Series DryLine®Dehydrator User Manual
10
3.5 Annual Maintenance
Inspection includes checking for loose
ordamagedhoses,ttingsandelectrical
connections. Open the front door and verify that
thereisnowaterbuild-upinthetwolterbowls
located inside the front cover of the dehydrator.
There may be some droplets of water vapor in
thelterbowls(thelowerportionofeachbowl),
but there should be only a small amount of liquid
in either bowl.
Ifthereisexcessivewater,refertothe
troubleshooting section. Replacement of the
lterelementsinthewaterlterandcoalescing
lteriscoveredintheoverhaulsectionofthis
manual.
Check the electrical connections
Check the screw in power input terminals to
ensure that the AC power cord is securely
terminated. Check the screw-in alarm terminals
to ensure that all wire connections are tight.
Check the run-time meter
Check the run-time meter on the front panel to
determine the duty cycle of the dehydrator.
If the dehydrator has been running for more than
10-15% of its installed time, check the system
for leaks. Also check the time on the meter to
determine if it is time to perform the 6000-hour
overhaul.
3.6 Parts Replacement and Dehydrator Overhaul
CommScope ODPMT200 Dehydrators are
designed to give may years of trouble-free
service and require very minimal maintenance.
The dehydrator contains, as a standard feature,
a run-time meter that records compressor
run hours. To ensure continuous and reliable
operation, the dehydrator must be overhauled
A loose or damaged connection may result in
erratic operation and unnecessary downtime.
Refer to the troubleshooting section if an
electrical problem is encountered.
Check the ground wire
Check that an electrical safety ground is
installed on the stud inside the front cover of the
dehydrator. This connection point is adjacent
the power input connector. (It is intended to be
customerinstalledintheeld.)

ODPMT200 Series DryLine®Dehydrator User Manual
11
every 6000 hours of compressor operation. The
kit listed below, contains all of the necessary
parts to perform this overhaul.
Maintenance Parts
1. Dehydrator Overhaul Kit 1 ea.
AE01K-C0398-015
2. Compressor Air Intake Filter bag of 6,
EFLTR-91101
Tools
The following tools are used in the maintenance
and overhaul procedures.
A ballpoint pen, an adjustable open-end wrench,
a socket wrench with a 7/16-inch (or 11mm)
socket, a No. 2 Phillips screwdriver and a small
at-bladescrewdriver.
Overhaul Procedure
When the ODPMT200 compressor run time
reaches 6000 hours (or a multiple of 6000
hours) it is time to replace certain items in the
compressor and the air path of the dehydrator.
These include the piston cups, piston seals
andheadgasketsofthecompressor,thelter
elementsinthewaterandcoalescingltersand
the tube section connecting the compressor
outputtothewaterlterinput.
Unit Shutdown and Removal
In order to perform an overhaul on the
ODPMT200, the unit must be turned off and
removed from service. As this is being done
the low pressure alarm may activate through a
reporting alarm system. Personnel monitoring
suchanalarmshouldbenotiedinadvance
so that they are aware of the fact that service
is being performed. It is also necessary to
disconnect the dehydrator dry air output from the
waveguide system during the overhaul.
3.7 Dehydrator Filter Element Replacement
Clean/replacetheairintakelter
Theairintakelterprotectsthecompressor
from contamination and dust. Periodic cleaning/
replacementextendsthelifeofthecompressor.
Thelterismadeofopen-cellfoammaterial.It
should be cleaned or replaced once a year (or
more frequently, if the operating environment is
very dusty.)
Pullofftheltercoverandremovethefoam
element. (The cover is held in place by two
tabs. Use a small screwdriver or a ballpoint pen
to release them.)
Washthelterinrunningwater,squeezingit
betweenthengers.

ODPMT200 Series DryLine®Dehydrator User Manual
12
Squeezeandshakeoutanyexcesswaterand
returntheelementtothelterhousing.
Do not apply oil or other chemicals to
the lter element.
make sure the element is seated completely in
the housing and then replace the cover. If a new
element is used, discard the old element.
3.8 Service Restoration
RECOMMENDATION: If the dehydrator
overhaul process has taken more than a few
hours, it is recommended that the unit be run for
one hour into the room, to purge the membrane
dryer and tank of any acquired moisture, before
reconnecting to the transmission line system.
Reverse the steps followed initially to remount
the dehydrator. To reconnect the dry air lines; to
reconnect the power and alarm cabling; to turn
theunitbackon;andnally,toopenthevalves
to the waveguide system so that the dehydrator
is again providing dry air under pressure to the
transmission line system.

ODPMT200 Series DryLine®Dehydrator User Manual
13
Ifyouexperiencedifcultywithyourdehydrator,usethetroubleshootingproceduresdescribedbelow.
Caution: Electrical troubleshooting requires access to potentially dangerous voltages and
should only be performed by a licensed electrician.
Section 4
Troubleshooting
Problem/Condition Solution
Dehydrator on/off switch does not light, unit does
not run.
Check the breaker adjacent to the on/off switch. If the breaker
istripped,(whiteindicatorexposed)thenresetthebreaker.
If the ON/OFF switch light still falls to light, make sure the unit
is plugged in and power outlet is operating.
If you still have no light, unplug the unit, remove the unit cover
and check for loose connections. Refer to the wiring diagram
for proper connections. (See Figure 3 Summary Alarm, Figure
4 Discrete Alarm Wire Diagrams)
Dehydrator on/off switch does not light, unit runs.
Disconnect power, remove cover, check for loose connections
per the wiring diagram. Replace cover and reconnect input
power.
If condition persists, replace ON/OFF switch.
Low-pressure alarm activated.
Pressurize lines with the dehydrator, turn shut-off valve to the
off position and observe pressure gauge. The pressure gauge
shouldreadapproximately5.0psigandthealarmshouldclear.
If alarm does not clear, remove cover and verify wiring to low
pressure alarm switch.
If the pressure does not stay constant after shutting off the
valve, apply leak detector to isolate the leak in the dehydrator
(exercisecarewhenapplyingsolutionnottowetwiringor
electronics). (See Figure 6 Pneumatic Diagram)
With dehydrator isolated from transmission line, observe
pressure in transmission line. If pressure drops, use a leak
detector solution to locate leaks in the transmission line.
Repair leaks if possible. (See section 6)
If the problem persists contact CommScope Customer Service.
Compressor does not turn.
Check the breaker adjacent to the on/off switch. If the breaker
istripped,(whiteindicatorexposed)thenresetthebreaker.
Check power switch to make sure that it is on and lighted.
Check input power polarity and voltage per wiring diagram.
Circuit breaker tripped.
Check wiring connections per wiring diagram. If breaker trips
again, replaces the breaker. If the replacement breaker trips
contact CommScope Customer Service. (See section 6)
Filter bowls show excessive water.
Assurethatthedrainlinetubing(exitingthebottomofthe
unit) is not clogged. When the compressor cycles off, air
and moisture should run out of the drain line. (See Figure 6
Pneumatic Diagram)

ODPMT200 Series DryLine®Dehydrator User Manual
16
6.1 Introduction
CommScope provides in-warranty and out-
of-warranty repairs as well as dehydrator and
compressor overhauls from several Repair
Centers. Coordination of these services is
providedthroughthenearestSalesOfceor
Customer Service Center. The Center is also
prepared to help you with the following:
• Technical Assistance
• Troubleshooting
• Repairs
• Loaner Units
• Spare Parts
• Installation Materials
• System Accessories
6.2 In Case of Trouble
Therststepyoushouldtakeiftrouble
develops using a dehydrator is to read the
operators manual and follow the trouble isolating
procedures given in it.
If the steps in the manual do not identify
and remedy the problem, then contact an
CommScope Customer Service Center for 24–
hour telephone assistance. Record the Model
Number (e.g. ODPMT200) and Serial Number
from the product label, as you will be asked for
these when you call. Two main locations are
currently available to help:
From North America
Telephone: 1-800-255-1479
Fax(U.S.A.):1-800-349-5444
International
Telephone: +1-779-435-6500
FaxNumber:+1-779-435-8579
Web Access
Internet: www.commscope.com
Section 5
Replacement Parts
Section 6
Customer Service
The following is a list of the replacement parts for the
ODPMT200 series dehydrators:
Description
(For units before Rev J mantain existing lters)
Inlet Filter EFLTR-20201
ODPMT200-8XXXX AE01J-A0731-001
Filter Bowl (only) AE01J-A1978-101
Water Filter Element AE01J-A1978-203
0.01 micron Coalescent Element AE01J-A1978-201
Overhual or Upgrade
(For units before Rev J to bring them up to Rev J)
Upgrade Kit AE01K-A0873-001
(For units Rev J and above)
Overhual Kit PMT200B-KIT-OVRHL
Solenoid Kit PMT200B-KIT-SOLND
Filter Element Kit PMT200B-KIT-ELMNT
Compressor AE01J-A2022-001

ODPMT200 Series DryLine®Dehydrator User Manual
17
6.3 Initial Steps by CommScope
Whenyourcallorfaxcommunicationis
received, the CommScope staff will work with
you to pinpoint the possible cause of trouble. If
the pressurization equipment is suspect, they
will:
• ask for your unit Model Number and Serial
Number
• check the warranty status of the unit
• advise the availability of a loaner unit
• provide an estimate of the cost for inspection
and repairs, if the unit is out–of–warranty
• faxaReturnMaterialAuthorizationSheetto
you.
6.4 Repair Center Process
A method of Payment must be provided prior
to issuing of RMA regardless of warranty
status.
IN–WARRANTY REPAIR: Most CommScope
pressurization products carry a warranty of one
to three years, depending upon model number.
Warranty details are available on our web
page. If your unit falls within its warranty period,
inspection and repairs will be performed at no
charge and the unit will be promptly returned
to you. If a warranty unit is deemed no problem
found an inspection fee and freight will be
charged to the customer.
OUT–OF–WARRANTY REPAIR: We will inform
you with the cost of repair and obtain your
approval to proceed with repairs or, if you elect
not to have the unit repaired, your instructions
on disposition of your unit. When repairs are
complete, we will return your unit and invoice
you for the inspection charge, materials used
for the repair and labor applied to complete the
repair. If you elected not to repair the unit, we
will invoice you for the inspection and freight
charge if unit is to be returned.
LOANER UNITS: Loaner units are available
from the repair center to maintain your system
while repairs are being performed. If you feel
you need a loaner, please contact us at at one
of the numbers listed under contact numbers.
A P.O. for the full value of the unit must be
issued prior to shipment. Also contact us when
the loaner is ready to be returned so that we
can issue a NEW RMA number to identify your
return and create the appropriate credit to your
account. Damages to loaner will be deducted
from the P.O.
PACKING INSTRUCTIONS: Pack your unit
securely for shipment to the Repair Center.
If you received a loaner unit, we suggest you
usetheboxandpackingmaterialstoreturn
your unit. Otherwise we have factory packing
materials available for a nominal fee. Enclose a
completedcopyofthisforminsidetheboxand
clearly mark your Company Name and RMA:
XXXXXXXonoutsideofthebox.Addressthe
boxtothefollowingShip–ToAddress:
CommScope PRESSURIZATION SERVICE
CENTER
RMA# XXXXXXX
11312 S. PIPELINE RD.
EULESS, TX. 76040-6629
Please note, Units received with Biological/
animal contamination will be returned
unrepaired or scraped after notication
and you will be invoiced for inspection and
freight.
CONTACT NUMBERS: If you have any
questions about the repair process or status of
your unit, please contact us directly through one
of the following methods – Telephone (below)
TEL: 817-864-4150
817-864-4155
FAX: 817-864-4179
6.5 RoHS Inquiries
For inquiries on RoHS please contact the
following:
CommScope Inc.
Corke Abbey, Bray Co.,
Dublin, Ireland
Attn: Legal Department

ODPMT200 Series DryLine®Dehydrator User Manual
18
This page was left blank

ODPMT200 Series DryLine®Dehydrator User Manual
20
This page was left blank
Table of contents
Other CommScope Industrial Equipment manuals

CommScope
CommScope FMT-D User manual

CommScope
CommScope FIST-RSKG-16 User manual

CommScope
CommScope 864 FDH RESKIN KIT User manual

CommScope
CommScope NG3 User manual

CommScope
CommScope ION-M7P/17EHP User manual

CommScope
CommScope DryLine MT Series User manual

CommScope
CommScope FIST-GSS2 User manual

CommScope
CommScope EPX G2 User manual

CommScope
CommScope HELIAX FiderFeed DFJ-4S112B User manual

CommScope
CommScope DryLine PMT200B Series User manual