Cooper Scantronic 65 User manual

INSTALLATION
INSTRUCTIONS
HARDWIRED
CONTROL UNIT

65 Hardwired Control Unit Installation Instructions
© Cooper Security Ltd. 2007
Every effort has been made to ensure that the contents of this book are correct. However, neither the authors nor Cooper Security
Limited accept any liability for loss or damage caused or alleged to be caused directly or indirectly by this book. The contents of this book
are subject to change without notice.
Printed and published in the UK.

11763087 Issue 1 Page i
Contents
1. INTRODUCTION.......................................................................................... 1
2. INSTALLATION ........................................................................................... 5
Fitting and Wiring Procedure ............................................................................................. 5
General Wiring Considerations.......................................................................................... 5
Cable Type....................................................................................................................... 5
Cable Segregation ........................................................................................................... 6
Cables Routed inside the Control unit ............................................................................. 6
Initial Power-Up Procedure and Checks............................................................................ 6
Zone Wiring........................................................................................................................ 7
Anti-Masking Zone Connections...................................................................................... 8
Network 1 Connections...................................................................................................... 9
Network 2 Connections...................................................................................................... 9
Telephone Connections................................................................................................... 10
Approved Usage ............................................................................................................ 11
Digital Communicator Outputs......................................................................................... 12
Transistor Outputs ........................................................................................................... 12
Relay Outputs .................................................................................................................. 13
External Bell/Sounder Connections................................................................................. 14
Auxiliary Tamper Input..................................................................................................... 15
Line Fault Input ................................................................................................................15
Communicator Line Fault............................................................................................... 15
Remote Reset Input......................................................................................................... 16
Extension Loudspeaker Connections .............................................................................. 16
AC Input Connector ......................................................................................................... 17
Battery Connector............................................................................................................ 17
12Vdc Auxiliary Power Terminals .................................................................................... 17
Back Tamper Connector.................................................................................................. 17
Factory Restart Connector............................................................................................... 18
Engineer Keypad Connector............................................................................................ 18
USB Connection to PC .................................................................................................... 19
Power Availability............................................................................................................. 19
Connecting to the Mains Supply ...................................................................................... 20
LEDs ................................................................................................................................ 21
Polyfuses ......................................................................................................................... 21
3. 9950/9951 KEYPAD INSTALLATION.......................................................22
9950 Mounting Locations................................................................................................. 22
Network Wiring................................................................................................................. 22
Zone Wiring (Optional)..................................................................................................... 23
Output Wiring (Optional) .................................................................................................. 23
Loudspeaker Wiring (Optional)........................................................................................ 23
Setting the Address ......................................................................................................... 24
Links................................................................................................................................. 24
4. TECHNICAL DESCRIPTION ..................................................................... 25
Technical Specifications .................................................................................................. 25
Electromagnetic Compatibility ......................................................................................... 26

List of Figures 65 Installation Instructions
Page ii 11763087 Issue 1
List of Figures
Figure 1. 65 Control Unit Layout ........................................................................................2
Figure 2. Control Unit PCB.................................................................................................3
Figure 3. Overview of Network Wiring Options ..................................................................4
Figure 4. Zone Wiring (Double Pole)..................................................................................7
Figure 5. Zone Wiring (FSL)...............................................................................................7
Figure 6. Wiring a Zone that uses Anti-Masking ................................................................9
Figure 7. Keypad Connections .........................................................................................10
Figure 8. PSTN Connections............................................................................................11
Figure 9. Examples of using Switched-Negative Outputs................................................13
Figure 10. Examples of using Switched-Positive Outputs ...............................................13
Figure 11. Example of using the Relay Programmable Output .......................................14
Figure 12. External Sounder Connections .......................................................................14
Figure 13. Extension Loudspeaker Connections .............................................................16
Figure 14. Battery Connections........................................................................................17
Figure 17. Engineer Keypad Connections .......................................................................18
Figure 18. Mains Connections..........................................................................................20
Figure 19. 9950/9951 Network Wiring..............................................................................22
Figure 20. 9950/9951 Zone Wiring...................................................................................23

11763087 Issue 1 Page 1
1. INTRODUCTION
The layout of the 65 control unit and the main features of the printed-circuit
board (PCB) are shown in Figure 1 and Figure 2 respectively.
The panel includes a wealth of features, including:
• Eight on-board zones.
• Two network ports for the connection of keypads, LEC2s, MSNodes,
MRNodes and MSPSU Nodes (see Figure 3). The additional network
devices enable the system to be expanded up to 40 zones.
• A USB connector for local connection of a PC running the Downloader
configuration and monitoring software.
• An on-board modem connected to PSTN and RJ11 ports to enable remote
connection to a remote alarm receiving centre or to a PC running the
Downloader software.
• Switched-positive, switched-negative and voltage-free programmable
outputs.
• 8-channel digital communicator outputs for connection to an alarm
receiving centre or to provide additional programmable outputs.
• Engineer keypad port.
This leaflet describes how to install the control unit. If you need a general
overview of its features, please refer to the 95/65 Engineering Manual. If you
require details of how to install keypads or other ancillary devices, please
refer to their separate installation instructions.
Note: Before connecting any external devices to the control unit, make sure
that it is able to provide sufficient current to power such devices, as
described on page 19.

1. Introduction 65 Installation Instructions
Page 2 11763087 Issue 1
Figure 1. 65 Control Unit Layout

65 Installation Instructions 1. Introduction
11763087 Issue 1 Page 3
Figure 2. Control Unit PCB
Ref Description See Page Ref Description See Page
1. Zone connectors 7 13. Extension loudspeaker connections16
2. Network 1 connector 9 14. AC input connector 17
3. Network 2 connector 9 15. Battery connector 17
4. PSTN (Telephone) terminals 10 16. 12Vdc auxiliary power terminals 17
5. RJ11 (Telephone) socket 10 17. Back tamper connector 17
6. Digital communicator outputs 12 18. Factory restart connector 18
7. Transistor outputs 12 19. Engineer keypad connector 18
8. Relay outputs 13 20. USB connection to a PC 19
9. External bell/sounder connections 14 LEDs 1-7 21
10. Auxiliary tamper input 15 Polyfuses 21
11. Line fault input 15
12. Remote reset input 16

1. Introduction 65 Installation Instructions
Page 4 11763087 Issue 1
Figure 3. Overview of Network Wiring Options
Note:
• Zones connected to a 9950 or 9951 keypad must be wired as FSL.
• Using a Networker Interface Board (NIB) (with power supply) enables the maximum distance from a
control unit to the nodes, MSNode or keypad to be increased to 1km.
• The supply voltage at each Network 1 or 2 device must not drop below 10.5V (recommended to be at
least 12V). Refer to the 95/65 Engineering Manual for details of how to calculate and overcome voltage
drops.
• Direct connection of an LEC6 (6-zone) expander to Network 1 or 2 is supported for existing systems that
are being upgraded. Ensure that the number of zones does not exceed the number that would be
provided by keypads alone.

11763087 Issue 1 Page 5
2. INSTALLATION
Fitting and Wiring Procedure
To install the control unit:
1. Remove the front cover by releasing its three retaining screws.
Caution: Mains voltages may be present at the mains terminal
block (see Figure 1).
2. Connect any optional modules to the PCB.
3. Slide the back tamper switch mounting plate into the slots shown in
Figure 1.
4. Route all cables through the cable-entry holes located on the base of the
control unit. All holes used must be fitted with a rubber grommet to
protect against sharp edges. The mains cable must use its own cable-
entry hole.
5. If required, secure the control unit to a wall using not less than 30mm x
No 10 screws through the three fixing holes shown in Figure 1.
6. Connect all wiring except to the standby battery (connect during power-
up procedure).
General Wiring Considerations
Cable Type
In general, the control unit requires standard 7/0.2 un-screened alarm cable
for wiring to MSNodes, keypads, LEC2s, MRNodes, MSPSUs and zone
sensors. The number of cores varies, depending on the device being
connected.
Screened cable may prove necessary if the installation site has equipment
that produces high levels of R.F. (Radio Frequencies), e.g. heavy industrial
plant such as welding equipment, etc. If screened cable is required, you
should adhere to the following guidelines:
1. The screen on the cable should be connected only to mains earth at the
control unit to avoid earth loops.
2. The continuity of the cable screen is most important and screens MUST
be continuous along the full length of the network.
3. If the network cable enters any metal enclosure, ensure the screen is
isolated from the case.

2. Installation 65 Installation Instructions
Page 6 11763087 Issue 1
Cable Segregation
All network and zone wiring must be segregated from any other wiring, such
as mains supply cables, telephone cables, computer network cables and R.F.
cables. It is recommended that cable ties are used to keep cables separated.
The network and detection cables should be kept clear of cables supplying
sounders or extension loudspeakers. It is also advisable to avoid running
more than one network down a single cable.
Cables Routed inside the Control unit
Cables routed inside the product must be:
• Kept as short as possible.
• Routed close to the housing.
• Kept as far as possible from the electronics.
Initial Power-Up Procedure and Checks
1. Place a small screwdriver blade between the FACTORY RESTART
terminals ("18" on Figure 2). When you switch on the mains, this will
ensure that the factory default settings are used, as documented in the
95 Engineering Manual.
2. Switch on the mains supply and remove the screwdriver blade only when
heartbeat LED (LED1, next to the Digital Communicator terminals)
flashes. This may take up to 30 seconds.
3. Check that the power LED on the control unit PCB is lit. The keypad
sounders and extension loudspeakers may operate (tamper alarm).
4. Enter your engineer passcode (default 7890). The sounders are silenced
and the system prompts to confirm the network devices used (as
described in the 95/65 Engineering Manual). Press [ESC] to enter the
Engineering menus.
5. Connect the standby battery.
6. Switch off the 230V mains supply and ensure that the DC voltage at
each device on each network is greater than 11.5V while the system is
powered from its standby battery.
7. Switch on the mains supply and measure the DC voltage between the
mains earth connection and AUX +12V ("16" on Figure 2).
Caution: Do not make contact with live or neutral!
Then measure the DC voltage between the mains earth connection and
0V. In both cases, the measurement should be 1V or less. If the voltage
is greater than 1V, the system has an "Earth Fault" and all cables should
be checked for isolation to earth.
8. Replace the cover of the control unit.

65 Installation Instructions 2. Installation
11763087 Issue 1 Page 7
9. Use the Engineer menu options to set up the system, as described in the
95/65 Engineering Manual.
10. Test system operation.
Zone Wiring
("1" in Figure 2.)
The control unit has a set of eight on-board terminal blocks for the connection
of alarm sensors, such as door contacts and PIR detectors.
Each terminal block can connect to one or more sensors, wired using either
the "double-pole" method (see Figure 4) or "Fully-Supervised Loop (FSL)"
method (see Figure 5).
Note: Zones connected to 9950/9951 keypads must be wired as FSL.
100 Ohms
Max. 10 devices per circuit (not recommended)
Alarm
Tamper
Alarm
Tamper
Alarm
Tamper
CIRCUIT 1
Z1 T1
CIRCUIT 2
Z2 T2
100 Ohms
Alarm
Tamper
4K7
2K2
Max. 10 devices per circuit (not recommended)
Alarm
Tamper
Alarm
Tamper
4K7
2K2
CIRCUIT 1
Z1 T1
CIRCUIT 2
Z2 T2
Figure 4. Zone Wiring (Double Pole) Figure 5. Zone Wiring (FSL)
By default, alarm contacts are normally closed. Zones with normally-open
contacts must be programmed with the "Inverted" attribute set.
The FSL method uses resistors at the end of the line and across the alarm
contact, which enables the cables to be supervised for short-circuit or open-
circuit conditions to guard against cable tampering. The resistors can have the
values shown in Table 1 (the values used must be specified when
programming the zone).

2. Installation 65 Installation Instructions
Page 8 11763087 Issue 1
Alarm Shunt Resistor
( ±5%)
End-of-Line Resistor
( ±5%)
4K7 2K2
1K0 1K0
4K7 4K7
2K2 2K2
Table 1: Resistors for Zones Wired using the FSL Method
When using the FSL method, two cores are used for each zone. When using
the "double-pole" method, four cores are used.
It is recommended to use only one detector per zone, otherwise when an
alarm or tamper condition arises, the source of the alarm/tamper will not be
known.
If you are powering devices such as PIR detectors from the control unit, an
additional two cores are required for connection to the 12Vdc power output
terminals (labelled "16" in Figure 2).
Whichever method is used, the wiring resistance must be less than 100 Ohms
(with the end-of-line resistor shorted in the case of the FSL method).
If you are not using a zone, you should program the zone as "Not Used".
Anti-Masking Zone Connections
Some microwave detectors are fitted with an "anti-masking" facility to detect
cases where the detector has been obscured. The masking status can be
conveyed by one of two methods:
• By an open/closed contact wired to a separate zone programmed as type
"Masking". Two zones are therefore needed: one for the masking status
and the other for alarm/tamper status.
The sensor can connect using the double-pole or FSL method. If double-
pole is used for the Masking zone, the zone's tamper terminals must be
shorted at the panel.
• By a specified resistance value to a zone programmed as a "normal" zone
type (e.g. Normal Alm or Entry). The zone must be wired as shown in
Figure 6, which also shows the resistance values used to convey the
normal, alarm, masking and tamper status. The zone must have the
"Masking" attribute.

65 Installation Instructions 2. Installation
11763087 Issue 1 Page 9
Figure 6. Wiring a Zone that uses Anti-Masking
Network 1 Connections
("2" in Figure 2.)
Network 1 can support up to eight zones, provided by a combination of
keypads and LEC2s (two zones each), connected in a star or daisy chain
configuration. Figure 7 shows connection details. Network 1 does not support
any other device.
Please refer to the devices Installation Instructions.
Network 2 Connections
("3" in Figure 2.)
Network 2 can connect to one of the following (see Figure 3)
• A combination of up to four keypads and/or LEC2s. Wiring is the same as
Figure 7.
• A maximum of three MSNodes, MRNodes or MSPSU Nodes. Please refer
to the individual Installation Instructions for connection details.
Note: MRNodes, MSNodes or MSPSUNodes must not connect directly to the
same panel network as a keypad, or LEC2.

2. Installation 65 Installation Instructions
Page 10 11763087 Issue 1
Control Panel Network
Spare core used to double
up "B" to reduce voltage
6 Core
Alarm Cable
Power for
detectors
Power for
detectors
Power for
detectors
Power for
detectors
I/D=2
I/D=1
I/D=3
I/D=4
Remote
Keypad
A
B
C
D
E
Remote
Keypad
A
B
C
D
E
Remote
Keypad
A
B
C
D
E
Remote
Keypad
A
B
C
D
E
ABCDE
100
m
e
tr
e
s (
M
a
x
.)
Note: "C" may be marked
"C/F", and "E" may be
marked "E/G" on the PCB
Figure 7. Keypad Connections
Telephone Connections
("4" and "5" in Figure 2.)
The control unit contains a built-in modem, which enables direct connection to
a PSTN telephone network or PABX exchange.
This allows the system to be controlled and monitored from a remote PC
running the Downloader software, and enables alarm status information to be
transmitted to an Alarm Receiving Centre.
You can connect the panel to a telephone network using one of the following:
• The RJ11 telecom socket (labelled "5" in Figure 2). Use only a pre-
manufactured and approved cable between the RJ11 socket and telephone
outlet socket.
• The PSTN terminal block (labelled "4" in Figure 2). Connection details are
shown in Figure 8. Do not make any other connections to the telephone
network.

65 Installation Instructions 2. Installation
11763087 Issue 1 Page 11
A
B
B1
Optional connection to only one other item
of equipment (e.g. fax or answer machine).
While the control panel is communicating,
any device connected to the "Diverted Line"
is automatically disconnected.
Ensure polarity
is correct.
Use cable type
1/05mm CW1308
BT Master Box
(Exclusive line)
Control Panel
Do not connect
Diverted
Line
Primary
Line
2 or B
A1
5 or A
Figure 8. PSTN Connections
The control unit is not suitable for connection as an extension to a payphone
or to "1+1" carrier systems.
The control unit has a Ringer Equivalence Number (REN) of 0.2. For any one
line, the sum of REN values should not exceed 4.
Note: If you are in any doubt regarding connection to the telephone network,
seek advice from a competent telephone engineer. If you are using the
PSTN terminal block, the wiring should be carried out by an installer
authorised by the network supplier (e.g. British Telecom).
Approved Usage
This product is manufactured to meet all European Economic Area
telecommunication networks requirements. The equipment has been tested
and conforms to ETSI TBR 21 and the associated ATAAB Advisory Notes.
In the event of problems, first check to confirm the functionality of the line,
then contact your equipment supplier/installer.
The built-in modem has been approved for the following usage:
• Automatic call initialisation and dialling.
• Operation in absence of proceed indication.
• Modem.
• Serial connection.
• Multiple repeat attempts.
• Line Status Monitoring.

2. Installation 65 Installation Instructions
Page 12 11763087 Issue 1
Usage other than approved usage or failure to comply with the instructions
may invalidate any approval given to the apparatus, if, as a result, the
apparatus ceases to comply with the standards against which approval was
granted.
Digital Communicator Outputs
("6" in Figure 2.)
The control unit provides 8 programmable outputs, which could be used to
operate a digital communicator – a device that transmits the status of each
channel to an Alarm Receiving Centre (where each channel could represent a
zone alarm status). Alternatively, low-power devices such as LEDs could be
switched on or off by these outputs (see Figure 9).
By default, each output is switched negative, i.e. normally at +12Vdc and
switches to 0V when active. When at 0V, up to 100mA can flow into the output
from an external source.
If required, the sense can be reversed during system configuration, i.e.
normally at +0V and switches to 12Vdc when active. In this case, when
switching to +12Vdc, each output can deliver up to 5mA to an external load.
The terminal block labelled "16" in Figure 2 can provide a +12Vdc supply to a
digital communicator.
Transistor Outputs
("7" in Figure 2.)
The programmable transistor outputs provide control for external equipment
such as LEDs, buzzers and relays. The following outputs are provided:
• One switched-negative output (-2). This can switch from 12Vdc to 0V on
activation, and is able sink up to 500mA from a 12Vdc source. See Figure
9 for examples.
• One switched-positive output (+3). This switches from 0V to 12Vdc on
activation, and can deliver up to 500mA to an external load. See Figure 10
for examples.
Each output can be programmed to activate when, for example:
• There is an alarm in a specified zone.
• There is a panic alarm.
• Mains is disconnected from the control unit.
• A specified user passcode is entered.
• A combination of specified conditions occur.
The 95/65 Engineering Manual provides full details of output programming.

65 Installation Instructions 2. Installation
11763087 Issue 1 Page 13
Relay
12V relay capable
of switching
mains voltages
Aux 12 V
-ve O/P
(Programmed as Alarm / Bell / etc)
Smoke
Detector
+ 12 V
(Programmed as Detector Reset)
-Ve O/P
Aux 12V
0V
Diode (IN4001)
1K0 Ohm Resistor
LED (Light Emitting Diode)
-Ve O/P
Aux 12V
-Ve O/P
Aux 12V
12V Buzzer
Figure 9. Examples of using Switched-Negative Outputs
Smoke
Detector
+ 12 V
(Programmed as Detector Reset)
Aux 0V
+ve O/P
0V
Aux 0V
1K0 Ohm Resistor
LED (Light Emitting Diode)
+ve O/P
Aux 0V
12V Buzzer
+ve O/P
Relay
Aux 0V
+ve O/P
(Programmed as Alarm / Bell / etc)
Diode (IN4001)
12V relay capable
of switching
mains voltages
Figure 10. Examples of using Switched-Positive Outputs
Relay Outputs
("8" in Figure 2.)
The relay output provides a voltage-free changeover contact, which can be
programmed to switch external equipment on or off.
Connect one side of the external device to the COM terminal, and the other to
either N/O or N/C. The effect is as follows:

2. Installation 65 Installation Instructions
Page 14 11763087 Issue 1
• If you connect to N/O, the contact between COM and N/O is normally
open, and is closed only when the output is active.
• If you connect to N/C, the contact between COM and N/C is normally
closed, and is opened only when the output is active.
See Figure 11 for an example.
Figure 11. Example of using the Relay Programmable Output
External Bell/Sounder Connections
("9" in Figure 2.)
If required, an external sounder can be connected to the control unit.
Connection details are shown in Figure 12.
Typical
External Sounder
Control Panel
H/O + 12V +
H/O - 0V
Tamper In
TR -
STB - Tamper Out
TRG - Strobe +ve
Strobe -ve
Trigger -ve
Figure 12. External Sounder Connections
The meaning of each terminal is as follows:
H/O + This is used to provide a permanent +ve hold off to external sounders,
strobes, etc.
H/O - This is used to provide a permanent -ve hold off to external sounders,
strobes, etc.
TR - This is the negative tamper return connection from the external
sounder unit.
STB - This is the strobe trigger output, which switches to 0V on alarm and is
rated at 500mA. Normally, this output is connected to the strobe -ve;
the strobe +ve is connected to H/O+.

65 Installation Instructions 2. Installation
11763087 Issue 1 Page 15
TRG - This is the bell trigger output, which switches to 0V on alarm and is
rated at 500mA. This output can be programmed for SAB or SCB
operation, and operates as follows:
SAB switches to 0V on alarm and provides a maximum of 500mA.
SCB provides a negative hold off (500mA), which is removed on
alarm.
Additional external sounders can be driven from MSNodes (using an RM3A
relay module).
Auxiliary Tamper Input
("10" in Figure 2.)
The AUX TMP terminals provide a tamper-switch input for an auxiliary device
such as a remote power supply unit or extension loudspeaker. If the input is
not used, it must be linked out.
Line Fault Input
("11" in Figure 2.)
The system generates a line fault alert if +12Vdc is applied to the LINE FLT
input. If the system is unset when this occurs, a "Chime" tone is generated
every minute until the condition is reset. If the system is set, any programmed
bell delay is cancelled.
Communicator Line Fault
If a standalone communicator, such as a RedCARE STU, is being used,
connect the Line Fault output of the communicator to the LINE FLT input of
the panel. The communicator must provide +12Vdc to indicate a line fault (e.g.
if the Line Fault output at the communicator uses a relay, connect the
common terminal of the relay to +12Vdc and the normally-open terminal to the
LINE FLT input of the panel).
If the communicator is dual-path (i.e. has landline and mobile communication),
you also need to connect a panel output programmed as type "ATS Test" to
the ATS Test input of the communicator. Invert the sense of the output at the
panel if a "positive applied" input sense is used at the communicator.
The panel generates an "ATE L.F. Single" alert if only one of the networks is
not available, or "ATE L.F. All" if both networks are not available. For a single-
path communicator, a line fault generates "ATE L.F. All".

2. Installation 65 Installation Instructions
Page 16 11763087 Issue 1
Remote Reset Input
("12" in Figure 2.)
For alarms that require an engineer or remote reset, the system can also be
reset by applying 0Vdc to the REM RST input terminal. This can be achieved
by routing 0V from terminal block ("16" in Figure 2) through a switch to the
REM RST input.
This input could be connected to the "Control" output from a RedCARE
Subscribed Terminal Unit (STU) to enable the central station to provide a
"Remote Reset" facility.
Extension Loudspeaker Connections
("13" in Figure 2.)
An extension loudspeaker can be connected to the SPKR terminals of the
control unit. Connection details are shown in Figure 13.
The speaker output is designed to drive up to two 16Ωloudspeakers.
However, when using two speakers, you must wire them in series to reduce
current consumption.
Note: Extension loudspeakers are common to all partitions.
Note: Extension loudspeakers MUST NOT be wired in the same cable as
used for network or zone wiring.
1 x 16 Ohm Loudspeaker
2 x 16 Ohm Loudspeakers
SPEAKER SPEAKER
+
+
0V
0V
Figure 13. Extension Loudspeaker Connections
Table of contents
Other Cooper Control Unit manuals

Cooper
Cooper Scantronic 8750 User manual

Cooper
Cooper CEAG Webmodule ZB-S User manual

Cooper
Cooper Crouse-Hinds IF 1589 Setup guide

Cooper
Cooper Scantronic 9 5 Series User manual

Cooper
Cooper Scantronic 95 User manual

Cooper
Cooper S280-79-10 User manual

Cooper
Cooper Scantronic 9 5 Series Operating instructions

Cooper
Cooper Scantronic 8844 User manual

Cooper
Cooper 9930 User manual

Cooper
Cooper Scantronic 770r User manual