Daikin BACnet Manual

Installation and Maintenance Manual IM 1040
Group: Controls
Part Number: IM 1040
Date: April 2015
BACnet®VAV Actuator
Electronic Output
Start-up Procedures

IM 1040 • VAV ACTUATOR 2 www.DaikinApplied.com
Table of ConTenTs
Table of ConTenTs
Introduction..................................3
Revision History .............................3
Reference Documents ........................3
Limited Warranty .............................3
Notice .....................................3
General Information ..........................3
Hazard Identication Messages .................3
Start-Up Procedures...........................4
Before you begin .............................4
Communication and DO indicators ...............4
Setting controller address ......................4
Setting the application.........................4
Enabling actuators ...........................5
Specifying motor setup ........................5
Verifying actuator setup........................5
Setting the number of heat stages or valves........5
Selecting automatic calibration option.............6
Setting room temperature setpoints ..............6
Setting override time ..........................6
Enabling Wall Switch..........................6
Setting Duct Area ............................6
Setting ow coefcient ........................7
Setting airow setpoints .......................7
Setting room temperature offset (optional) .........7
Performing the automated checkout ..............8
Conguring BACnet parameters .................8

InTroduCTIon
www.DaikinApplied.com 3 IM 1040 • VAV ACTUATOR
InTroduCTIon
Revision History
Manual Date History
IM 1040 3/5/2010 Initial release
Reference Documents
Number Company Title Source
OM 1063 Daikin Applied
VAV Actuator
Owners
Manual
www.
DaikinApplied.
com
Limited Warranty
Consult your local Daikin representative for warranty
details. To nd your local Daikin representative, go to
www.DaikinApplied.com.
Notice
Copyright © 2010 Daikin Applied, Minneapolis MN. All rights
reserved throughout the world.
Daikin Applied reserves the right to change any information
contained herein without prior notice. The user is responsible
for determining whether this software is appropriate for his or
her application.
® ™ The following are tradenames or registered trademarks of
their respective companies: BACnet from the American Society
of Heating, Refrigerating and Air-Conditioning Engineers, Inc.;
Windows from Microsoft Corporation; Daikin and MicroTech III
from Daikin Applied.
General Information
This manual contains the information you need to setup the
electronic outputs and calibrations for the BACnetVAV Actuator
on a VAV box.
Hazard Identication Messages
DANGER
Dangers indicate a hazardous situation which will result in
death or serious injury if not avoided.
WARNING
Warnings indicate potentially hazardous situations, which can
result in property damage, severe personal injury, or death if
not avoided.
CAUTION
Cautions indicate potentially hazardous situations, which can
result in personal injury or equipment damage if not avoided.
NOTICE
Notices give important information concerning a process,
procedure, special handling or equipment attributes.
DANGER
Electric shock hazard. Can cause personal injury or
equipment damage.
This equipment must be properly grounded. Connections and
service to the MicroTech® III Chiller Unit Controller must be
performed only by personnel knowledgeable in the operation
of the equipment being controlled.
WARNING
Static sensitive components. Can cause equipment
damage.
Discharge any static electrical charge by touching the bare
metal inside the control panel before performing any service
work. Never unplug cables, circuit board terminal blocks, or
power plugs while power is applied to the panel.
NOTICE
This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance
with this instruction manual, may cause interference to radio
communications. It has been tested and found to comply with
the limits for a Class A digital device, pursuant to part 15 of the
FCC rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment
is operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct
the interference at his or her own expense. Daikin Applied
disclaims any liability resulting from any interference or for the
correction thereof.

IM 1040 • VAV ACTUATOR 4 www.DaikinApplied.com
sTarT-upproCedures
sTarT-upproCedures
Before you begin
NOTICE
WinCIS version 2.1.4 or later must be used to congure Daikin
BACnet controllers.
If WinCIS does not communicate (through the HMI port / RTS
sensor), try a different baud rate. The default buad rate is 1200
(allowable baud rates are: 1200, 9600, 19200, 38400 and
76800).
Figure 1: Actuator Components
Communication and DO indicators
The BACnet actuator has LEDs to indicate communication
(yellow) and DO [digital output] status (green).
The RX LED will ash for data packets received by the actuator
from the MS/TP network. The TX LED will ash for data
packets sent by the actuator to the MS/TP network. Each DO
(3 to 6) has an associated LED located above its termination
point. This LED point is ON when the accociated DO is
commanded ON, otherwise it is OFF. The BACnet actuator
will attempt to communicate with other devices as soon as
it powers up. The TX LED will start ashing as it attempts to
connect and transfer data.
Setting controller address
NOTICE
For BACnet, the controller address is the same as the BACnet
MAC address.
NOTICE
Set the controller address and MS/TP network baud rate prior
to connecting the controller to the network.
• Set the controller address by setting CTLR ADDRESS
to the appropriate number, see Conguring BACnet
Parameters
• The start-up is complete
Setting the application
NOTICE
You can continue the startup procedure while calibration is
underway. However, the controller will ignore commands to
control end devices (such as the damper) until calibration of
the air velocity sensor is nished.
• Add the TEC to your job database and select one of the
following applications from Table 1
Table 1: Daikin BACnet Actuator—Electronic Output
Applications
Application Description Application Number
VAV Cooling Only 2560
VAV Cooling or Heating 2561
VAV with Electric Reheat or Baseboard Radiation 2562
VAV with Hot Water Reheat 2563
VAV Series Fan Powered with Electric Heat 2564
VAV Series Fan Powered with Hot Water Reheat 2565
VAV Parallel Fan Powered with Electric Heat 2566
VAV Parallel Fan Powered with Hot Water Reheat 2567
VAV Slave Mode 2597
After you set the application, the controller goes through a
shut-down/load sequence as it switches from slave mode
to the application selected. When the application loads, the
calibration cycle begins.
At the start of the calibration cycle, the controller
automatically sets CAL AIR to YES. CAL AIR returns to NO
when the cycle is complete.
The air velocity sensor calibration cycle begins within three
minutes of an application start-up or initialization, depending on
the controller’s address. The calibration cycle takes from two to
ve minutes to complete after this delay. The air damper closes
during the rst calibration.

sTarT-upproCedures
www.DaikinApplied.com 5 IM 1040 • VAV ACTUATOR
Enabling actuators
CAUTION
The controller’s DOs control only 24 Vac loads.
The maximum rating is 12 VA for each DO.
The points that determine actuator run times are:
• MTR 1 TIMING
• MTR 2 TIMING
• MTR 3 TIMING
Your application may not have or use all three points.
1. Use and/or to set run time(s) for actuator(s) used by your
application.
2. For damper rotation angles other than 90°, set DMP
ROT ANG to the appropriate value. The names of these
points vary.
Table 2: Damper Actuator Run Time
Damper Actuator Setting (seconds)
50Hz 60 Hz
2508021 125 90
2508021P10 125 90
Table 3: Valve Actuator Run Time
Valve Actuator Setting (seconds)
50 HZ 60 Hz
SSB81U
Floating control fail in-place 160 150
SSC81U
Floating control fail in-place 150 125
SSC81.5U
Floating control fail-safe 125 125
SQS85.53U
Floating control spring return 35 30
Specifying motor setup
CAUTION
If an Autozero Module is used, do not enable MTR3 (valve 2).
NOTICE
When MTR SETUP is changed, all enabled actuators will
calibrate. Wait until each actuator has completed its calibrating
before continuing.
MTRSETUP determines which actuators are controlled by the
application and whether they are direct or reverse acting. Set
MTRSETUP according to Table 4.
Table 4: Motor Enable/Reverse Values for MTR SETUP
(Point 58)
Enabled Enabled and Reversed
Motor 1 (damper)
Motor 2
Not used 1 (default) 3
Enabled 5 7
Enabled and Reversed 13 15
Verifying actuator setup
Command all actuators closed. Verify that they close and
remain closed. If not, adjust the setting for MTRSETUP
according to Table 4.
If any of the actuators still do not close completely, then
the actuators have been installed or set up incorrectly. See
the installation instructions or contact your local Daikin
representative.
Setting the number of heat stages or
valves
CAUTION
For installations using electric heat coils, never set min airow
settings to 0 (zero). Equipment damage can occur if electric
heat is ON without airow.
Depending on the application, HTG STG CNT or VLV CNT (if
present) refers to electric heat stages or valves used (enabled),
some point names may vary.
• Set VLV CNT to the number of valves used for water or
steam valve applications (1 or 2)
• Check the hardware to verify the number of electric heat
stages wired to the controller (1 to 3) and set HTG STG
CNT to the value for electric heat appliactions

IM 1040 • VAV ACTUATOR 6 www.DaikinApplied.com
sTarT-upproCedures
Enabling autozero module
CAUTION
If an Autozero Module is used, do not enable MTR3 (valve 2).
NOTICE
For a controller without an Autozero Module, the damper
is commanded closed to get a zero airow reading during
calibration. For a controller with an Autozero Module, the
damper is closed only for the rst calibration after controller
initialization or power up.
If an Autozero Module is used, enable it by setting CAL
MODULE to Y.
Selecting automatic calibration option
NOTICE
The air velocity sensor must be calibrated at least once every
24 hours. Make sure that the sensor has been calibrated
before balancing takes place, as this will affect the balancer’s
results.
NOTICE
Options can be combined by summing their numbers. For
example, to calibrate as in Options 1 and 2, set CAL SETUP
to 3.
Using Table 5 set CAL SETUP to the value that best meets
your job requirements.
If appropriate, change CAL TIMER from the default of 12
hours. This setting applies only if your choice for CAL SETUP
includes Option 4.
Table 5: CAL SETUP Values
CAL SETUP (Point 95) Description
0Calibration occurs ONLY when the point CAL AIR
(Point 94) is set to YES
1
Calibration occurs when the eld panel commands
a day/night mode changeover. Actual calibration is
subject to a time delay of 0, 1, 2, or 3 minutes. This
delay is determined by the point CTLR ADDRESS
(Point 1) divided by 4. The remainder is the time
delay in minutes.
Example: If CTLR ADDRESS = 11, then the
controller will wait 3 minutes (11 ÷ 4 = 2 R3) after it
receives the day/night mode changeover command
before beginning the calibration routine.
2Calibration occurs immediately after the override
switch is depressed.
4
(factory default value)
Calibration occurs on the time interval set in the
point CAL TIMER (Point 96).
For example, if CAL TIMER = 12, then the
calibration period is12 hours. Actual calibration is
subject to a time delay based on the value of CTLR
ADDRESS.
See the example in Option 1. This is the
recommended option when using a controller with
an Autozero Module.
Setting room temperature setpoints
NOTICE
If STPT DIAL is set to YES, do not set the DAY (or OCC)
setpoints; the value of RM STPT DIAL will be used for these
points.
•DAY (or OCC) cooling setpoint
•DAY (or OCC) heating setpoint
•NGT (or UOC) cooling setpoint
•NGT (or UOC) heating setpoint
If the room temperature sensor has a setpoint dial that will be
used, set STPT DIAL to YES. Otherwise, set STPT DIAL to NO.
Set the room temperature setpoints to the desired values
(some points are not present in certain cooling only
applications).
Set RM STPT MIN and RM STPT MAX for the minimum and
maximum allowable room temperature setpoints, respectively.
Valid values range from 55°F to 95°F (13°C to 35°C). Default
values are 55°F (13°C) for RM STPT MIN and 90°F (32°C) for
RM STPT MAX.
Setting override time
If using night/unoccupied override, set OVRD TIME to the
number of whole hours that an override should last. If OVRD
TIME equals 0 (default), then this feature is disabled.
Enabling Wall Switch
If a wall switch is used for day/night (Occ/Unocc) control,
enable it by setting WALL SWITCH to YES.
Setting Duct Area
If provided, enter the duct area (sq ft or sq m) into DUCT
AREA (and also into HTGDUCT AREA, where applicable) and
continue to Setting ow coefcient on page 7.
If you do not know the duct area, use Table 6:
Table 6: Duct Area Calculation
Area = Round Duct Rectangular Duct
Area in Sq. Ft.
(Dimensions in inches) (π x R2)/144 Width × Height/144
Area in Sq. M.
(Dimensions in centimeters) (π × R2)/10,000 Width × Height/10,000

sTarT-upproCedures
www.DaikinApplied.com 7 IM 1040 • VAV ACTUATOR
Setting ow coefcient
1. Set FLOW COEFF to the appropriate value found in
Table 6. This value is a starting point for the air balancer.
2. To ne tune the ow coefcient use the following formula:
new ow coefcient = (actual volume / TEC volume)
× old ow coefcient
The actual volume is the actual value obtained from the
balancer’s measurements. The TEC volume is the value
obtained from AIR VOLUME.
3. If the TEC volume is not within 5% of the actual volume,
repeat the procedure until it is within 5%.
Table 7: Box Manufacturer Flow Coefcients.
Manufacturer Sensor Tpe Value
Anemostat
2-pipe without orice 0.79
2-pipe with orice 0.59
Spider without orice 0.73
Spider with orice 0.39
Carnes 2-pipe 065
Flow cross 0.59
Carrier 0.59
E.H. Price/Siemens Industry Lab Terminal Boxes 0.78
Environmental Technologies 0.79
Krueger 0.68
Metal Aire 0.72
Nailor Industries 0.69
Titus 0.60
Trane 0.66
Setting airow setpoints
CAUTION
If using electric heat in a unit without a terminal fan, do not set
HTG FLOW MIN to 0 (zero). Equipment damage may occur at
0 (zero) CFM with electric heat ON.
NOTICE
Maximum ow(s) must be set ≥ minimum ow(s).
NOTICE
For Applications 2562, 2563, 2564, and 2566, HTG FLOW
MAX should be less than CLG FLOW MAX. Otherwise, cold
supply air may cool rather than heat the space in heating
mode. A typical setting for HTG FLOW MAX is 50% or less of
CLG FLOW MAX.
1. Set CLG FLOW MIN to the desired minimum cooling
airow setpoint.
2. Set CLG FLOW MAX to the desired maximum cooling
airow setpoint.
Applications 2561 - 2567:
1. Set HTG FLOW MIN to the desired minimum heating
airow setpoint.
2. Set HTG FLOW MAX to the desired maximum heating
airow setpoint.
Setting room temperature offset
(optional)
NOTICE
The Room Temperature Offset feature is optional.
When the room has stabilized to within 5°F, take a precision
temperature reading at the room temperature sensor, record
any difference between this reading and the value of ROOM
TEMP and set this difference value (to the nearest 0.25°F) into
RMTMP OFFSET.
Example:
If the actual room temperature is 72.0°F, and the value of
ROOM TEMP is 73.0°F, then the value entered into RMTMP
OFFSET is –1.0. In this case, the value of ROOM TEMP would
read 73.0°F, but the value of CTL TEMP would read 72.0°F.
CTL TEMP = ROOM TEMP + RMTMP OFFSET

IM 1040 • VAV ACTUATOR 8 www.DaikinApplied.com
sTarT-upproCedures
Performing the automated checkout
NOTICE
Multiple failures are added together and displayed as one
value. For example, if the RTS failed (1) and the controller
could not reach CLG FLOW MAX (16), CHK STATUS
displays 17.
The Daikin VAV Actuator has a built-in checkout procedure
that can be manually initiated at any time after the controller
has been installed. This procedure tests all of the necessary
I/O and ensures the controller has the ability to operate within
the set airow range, between CLG FLOW MIN (Point 31) and
CLG FLOW MAX (Point 32).
To perform the checkout procedure, set CHK OUT (Point 66) to
YES. When the procedure has completed, CHK OUT returns to
NO and the results are displayed in CHK STATUS (Point 70),
Table 7.
Table 8: Possible Failure Value and Description.
CHK STATUS
Values (Point 70) Description
-1 Checkout procedure has not been run since last controller
initialization.
0 No errors found.
1 RTS failed.
2Room Setpoint dial dialed [if STPT DIAL (Point 14) = YES].
4 AVS failed.
8Controller could not reach CLG FLOW MIN or below.
16 Controller could not reach CLG FLOW MAX or above.
Conguring BACnet parameters
NOTICE
WinCIS version 2.1.4 or later must be used to congure Daikin
BACnet MS/TP TEC’s.
Do not check the Metric checkbox in the Device Properties
dialogue box if the controller is communicating through the
MS/TP driver in the Field Panel. Metric can be checked only if
the controller is communicating through a router. If you need
metric and the controller is communicating through the MS/
TP driver in the Field Panel, then the Metric checkbox in the
Device Properties dialogue box must be unchecked and the
conversion must be handled in the Field Panel.
NOTICE
When the BACnet MS/TP TEC is successfully installed, the
RX and TX LED’s ash On/Off very rapidly and continuously.
Using WinCIS, do the following:
•From the Device menu, select Device Properties to
congure BACnet parameters.
•Object Name – unique to BACnet network, default = VAV
CTLR (12 character RAD50 limit).
•Object ID – unique to BACnet network, valid values = 0 to
4,194,303.
•Description – description of controller (60 character limit).
•Location – physical location of controller (60 character
limit).
•Baud Rate – options; 9600, 19200, 38400 or 76800,
default = 19200.
•MSTP Master/Slave – do one of the following:
•Check the Slave checkbox if the controller communicates
with a Field Panel using the
• MS/TP driver.
•Uncheck the Slave checkbox if the controller is
communicating through a router.
•Press the Write button — the controller accepts the
conguration values and then resets.
The startup is complete upon completion of BACnet
parameters conguration


IM 1040 (04/15) ©2015 Daikin Applied | (800) 432–1342 | www.DaikinApplied.com
Daikin Applied Training and Development
Now that you have made an investment in modern, efcient Daikin equipment, its care should be a high
priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com
and click on Training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited
Product Warranty. Consult your local Daikin Applied representative for warranty details. To nd your
local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To nd your local parts ofce, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To nd your local service ofce, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.
Products manufactured in an ISO Certied Facility.
Table of contents
Other Daikin Controllers manuals

Daikin
Daikin DCS004A71 User manual

Daikin
Daikin RoCon+ HP Series User manual

Daikin
Daikin MERCA User manual

Daikin
Daikin DPS Manual

Daikin
Daikin AIRHUB User manual

Daikin
Daikin ARC447A3 Instruction manual

Daikin
Daikin IM 735-4 Manual

Daikin
Daikin BRC7E530W User manual

Daikin
Daikin DCS601C51 User manual

Daikin
Daikin DKN-MP130-24MP User manual

Daikin
Daikin FWEC1 User manual

Daikin
Daikin BRC7C62 User manual

Daikin
Daikin iLINQ User manual

Daikin
Daikin ALTHERMA User manual

Daikin
Daikin MicroTech III User manual

Daikin
Daikin DDC User manual

Daikin
Daikin MicroTech III Manual

Daikin
Daikin DCM601B51 User manual

Daikin
Daikin QUG-Altherma Interface Instruction manual

Daikin
Daikin RoCon+ HP Series User manual