manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Danfoss
  6. •
  7. Control Unit
  8. •
  9. Danfoss DHP-R 7UA HPC EM User manual

Danfoss DHP-R 7UA HPC EM User manual

VMILF102
DHPR&DP
INSTALLATION INSTRUCTIONS
EXPANSION MODULE, HPC EM
COOLING MODULE, HPC CM
VMILF1022 – Danfoss
VMBQI102
VMBQI102
VMILF102 Danfoss – 3
Table of contents
Installation for WCS function (warm water loading) ... 4
Installation for TWC function (tap water control)...... 6
Installation for Shunt function ....................... 8
Important information!
24 VAC 1 must not be connected together with:
󰥎
 •24VAC2
 •24VDC
 •Otherequipmentthatuses0-10Vcontrolsignal
 •SignalgroundGND
24 VAC 2 must only be used as power supply to:
󰥎
 •Externalequipmentthatrequires0-10Vcontrolsignal
 •Auxiliarymodules
The two separate 24 VAC circuits must never be connected
󰥎 to each other or to protective ground.
The total power load on 24 VAC 1 respectively 24 VAC 2 must
󰥎 notexceed50VA.
VMILF1024 – Danfoss
VMBQI102
Expansion module, HPC EM
Theoperationaldescriptionfortheexpansionmoduleisavailableinthecontrollermanual.
Installation for WCS function (warm water loading)
Application
TheexpansionmoduleinWCSoperationalmodecontrolswarmwaterloadingofthe
water heaters.
WCS operation is achieved by setting the switch according to the figure.
Required accessories for installation
Submersiblesensor,Thermokon-DanelkoAKF1004140,itemno.086U3364
One of the following modular cables:
Modularcable0.3m,itemno.086U4227
Modularcable1.1m,itemno.086U4228
Modularcable10.0m,itemno.086U4229
Connectionblock,itemno.086U5121
Other accessories
PilotvalveVVL(2-way),heatexchanger(tapwatervvx),circulationpump.
System image
Heat exchanger
Aheatexchangerisconnectedbetweentheheatpumpandthecirculationforthewaterheatersasdepictedinthesystem
image above.
Circulation pump
Acirculationpumpisconnectedneartheheatexchanger.
Pilot valve
Apilotvalveisconnectedbetweenthecirculationpumpandtheheatexchanger.
Submersible sensor
Asubmersiblesensorisconnectedonthereturnlineoftheheatexchanger,asclosetotheheatexchangeraspossible.
Heat circuit
Hot gas circuit
Cooling agent circuit
VVB VVB VVB VVB
Heatexchanger
Modular cable
Steering valve
Circulation pump
Expansion module
WCS operation
Submersible sensor
return VVX
KV
VV
VVC
DHP-R Eco
VMBQI102
VMILF102 Danfoss–5
Connecting
󰥎 Note!Themaximumloadmaynotexceed50VA.
Expansion module
Theexpansionmoduleismountedintheelectriccabinetontheintendedrail.Ifthereisnoroom,themodulecanbeinstal-
ledinanexternal,enclosedcabinetandconnectedwithalongermodularcable.
• SettheswitchesonthefrontoftheexpansionmoduletotheWCSposition

• ConnectamodularcablebetweenHPCRMExp.outandHPCEMExp.in
Connections of expansion module for WCS operation:
Temperatureinput,T1:Submersiblesensor(heatexchangerreturnline)
Temperatureinput,T2:-
Analogueoutput0-10V,AO1:Signaltopilotvalve
Relay,DO1:Signaltocirculationpump(no-potentialclosure,maximum6A)
Exp.in:ConnectionfromHPCRM
Exp.out:Connectiontopossibleadditionalmodule.
Submersible sensor

• ConnecttoT1andGND
Circulation pump

• ConnecttoDO1.1to24VAC2.1

• ConnectDO1.2tothecontactorcoil(therelaycoil)andfurtherto24VAC2.2
Pilot valve

• ConnectAO1tothesignalinputofthepilotvalve

• ConnectGNDtopilotvalveGND.IfGNDismissinginthepilotvalve,connectGNDto24VAC2.2somewhereinthe
system. It is most appropriate to jumper terminals 144 and 146 in the controller cabinet.

• ConnectthepilotvalveterminalGto24VAC2.1

• ConnectthepilotvalveterminalG0to24VAC2.2.
•
Exp.in
GGNDG0Y1
Exp.out
DO1.1
T1
T2
AO1
GND
DO1.2
HPC EM
WCS
24 VAC 2.1
24 VAC 2.1
24 VAC 2.2
24 VAC 2.2
M
alt. GG
0Y1
24 VAC 2.1
24 VAC 2.2
AO1
0-10V
Circ. pump
FromExp.out
Submersible sensor
Pilot valve
VMILF1026 – Danfoss
VMBQI102
Installation for TWC function (tap water control)
Application
In the TWC mode, the expansion module ensures that outgoing hot tap wa- ter
and heat water circulation have a sufficiently high temperature, to prevent the pre-
sence of Legionella bacteria.
TWC operation is achieved by setting the switch according to the figure.
Required accessories
2 PT1000 strap-on temperature detectors with 2 m of cable, item no.
086U3365(itemnumbercorrespondsto1transmitter)
One of the following modular cables:
Modularcable0.3m,itemno.086U4227
Modularcable1.1m,itemno.086U4228
Modularcable10.0m,itemno.086U4229
Connectionblock,itemno.086U5121
System image
Sensor, water heater
Astrap-ontemperaturedetectorisconnectedonthesupplylineleadoftheendheater,beforethemixingvalve.
Sensor, hot water return
Astrap-ontemperaturedetectoris connectedonthereturnleadofthewarmwatercirculation,beforethecirculation
pump.
Heat circuit
Hot gas circuit
Cooling agent circuit
VVB VVB VVB VVB
Modular cable
Sensor, water heater
Electriccartridge
Sensor, hot water return
Expansion module
TWC function
KV
VV
VVC
DHP-R Eco
VMBQI102
VMILF102 Danfoss–7
Connecting
󰥎 Note!Themaximumloadmaynotexceed50VA.
Expansion module
Theexpansionmoduleismountedintheelectriccabinetontheintendedrail.Ifthereisnoroom,themodulecanbeinstal-
ledinanexternal,enclosedcabinetandconnectedwithalongermodularcable.
• SettheswitchesonthefrontoftheexpansionmoduletotheTWCposition

• ConnectamodularcablebetweenHPCRMExp.outandHPCEMExp.in
Connections of expansion module for TWC operation:
Temperature input, T1: Sensor, water heater
Temperature input, T2: Transmitter, hot water return
Analogueoutput0-10V,AO1:-
Relay,DO1:Signaltoelectriccartridge,hotwater(no-potentialclosure,maximum6A)
Exp.in:ConnectionfromHPCRM
Exp.out:Connectiontopossibleadditionalmodule.
Electric cartridge

• ConnecttoDO1.1to24VAC2.1.

• ConnectDO1.2tothecontactorcoil(therelaycoil)andfurtherto24VAC2.2.
Sensor, water heater

• ConnectthesensorcabletoT1andGND.
Sensor, hot water return

• ConnectthesensorcabletoT2andGND.
Exp.in
Exp.out
DO1.1
T1
T2
AO1
GND
DO1.2
HPC EM
TWC
24 VAC 2.1 24 VAC 2.2
Start signal for
electric cartridge
water heater
Hot water return
FromExp.out
VMILF1028 – Danfoss
VMBQI102
Installation for Shunt operation
Application
Intheshuntmode,theexpansionmodulemaintainstherequiredtemperaturefora
second heat circuit.
The shunt function is achieved by setting the switch according to the figure.
Required accessories
1PT1000strap-ontemperaturedetector,itemno.086U3365
One of the following modular cables:
Modularcable0.3m,itemno.086U4227
Modularcable1.1m,itemno.086U4228
Modularcable10.0m,itemno.086U4229
Connectionblock,itemno.086U5121
Other accessories
Shunt valve, circulation pump.
System image
Sensor, shunt temperature
Astrap-ontemperaturedetectorisconnectedonthesupplylineoftheheatcircuit,afterthecirculationpump.
Heat circuit 1
Heat circuit 2
Hot gas circuit
Cooling agent circuit
VVB VVB VVB VVB
Shunt valve
Sensor, shunt temperature
Circulation pump
Modular cable
Expansion module
Shunt function
KV
VV
VVC
DHP-R Eco
VMBQI102
VMILF102 Danfoss–9
Connecting
󰥎 Note!Themaximumloadmaynotexceed50VA.
Expansion module
Theexpansionmoduleismountedintheelectriccabinetontheintendedrail.Ifthereisnoroom,themodulecanbeinstal-
ledinanexternal,enclosedcabinetandconnectedwithalongermodularcable.
• SettheswitchesonthefrontoftheexpansionmoduletotheShuntposition.

• ConnectamodularcablebetweenHPCRMExp.outandHPCEMExp.in
Connections of expansion module for shunt operation:
Temperature input, T1: Sensor, shunt temperature.
Temperatureinput,T2:-
Analogueoutput0-10V,AO1:Signaltoshuntvalve.
Relay,DO1:Signaltocirculationpump(no-potentialclosure,maximum6A).
Exp.in:ConnectionfromHPCRM.
Exp.out:Connectiontopossibleadditionalmodule.
Sensor, shunt temperature

• ConnecttoT1andGND
Circulation pump

• ConnecttoDO1.1to24VAC2.1.

• ConnectDO1.2tothecontactorcoil(therelaycoil)andfurtherto24VAC2.2.
Shunt valve

• ConnectAO1tothesignalinputofthepilotvalve.

• ConnectGNDtopilotvalveGND.IfGNDismissinginthepilotvalve,connectGNDto24VAC2.2somewhereinthe
system. It is most appropriate to jumper terminals 144 and 146 in the controller cabinet.

• ConnectthepilotvalveterminalGto24VAC2.1.

• ConnectthepilotvalveterminalG0to24VAC2.2.
Exp.in
GGNDG0Y1
Exp.out
DO1.1
T1
T2
AO1
GND
DO1.2
HPC EM
Shunt
24 VAC 2.1
24 VAC 2.1
24 VAC 2.2
24 VAC 2.2
0-10V
alt.
M
GG
0Y1
24 VAC 2.1
24 VAC 2.2
AO1
Circ. pump
FromExp.out
Shunt temperature
Shunt valve
VMILF10210 – Danfoss
VMBQI102
Inputs and outputs, HPC EM
Temperature inputs
Input Shunt TWC WCS
T1 Shunt temperature HW heater temp WCS temperature
T2 – HW return temp –
Analogue outputs
Outputs Shunt TWC WCS
AO1 Control signal – Control signal
Relay outputs
Outputs Shunt TWC WCS
DO1 Circulation pump Heater HW Circulation pump
VMBQI102
VMILF102 Danfoss – 11
Cooling module, HPC CM
The operational description for the cooling module is available in the controller manual.
Installation
Application
The cooling module controls the temperature of a cooling using a pilot valve. The cold is collected from a cooling tank,
which is cooled with active or passive cold.
Passive cold means that cooling agent fluid is circulated through the drill hole and the cooling tank, without activation
ofanyheatingpump.Onlycirculationpumpsforcoolingagentsareused.Theheatfromthecoolingtankistransported
down into the mountain. An assumption for passive cooling to work is that the cooling agent fluid is colder than the coo-
ling tank.
Active cooling means that a heat pump is activated to lower the temperature of the cooling agent, before it is transferred
into the cooling tank. If the cooling integral continues to rise, more heat pumps are started. The valve for active cooling
changes its mode and disconnects the drill hole. Therefore, the cooling agent only circulates through the cooling tank and
heat pump, so that all the produced cold can be collected.
Additionally, a dew point control function can be activated in the cooling module. This function is not necessary, but if it is
used a dew point sensor must be connected.
Surplus heat produced during active cooling can either be returned to the drill hole or cooled in a coolant cooler. If a
coolant cooler is used, a temperature sensor is connected for the cooler and the coolant module then controls the cooling
fans.
Required accessories
4PT1000contactstrap-ontemperaturedetectorwith2mofcable,itemno.086U3365(itemnumbercorrespondsto1
detector)
One of the following modular cables:
Modularcable0.3m,itemno.086U4227
Modularcable1.1m,itemno.086U4228
Modularcable10.0m,itemno.086U4229
Connectionblock,itemno.086U5121
Dewpointsensorforwallmounting,itemno.086U3396(ifthedewpointfunctionisused)
VMILF10212 – Danfoss
VMBQI102
System image
Transmitter, cooling tank
Astrap-ontemperaturedetectorisconnectedonthecoolingtankataboutathirdofthetank’sheight.
Transmitter, cooling circuit
Astrap-ontemperaturedetectorisconnectedonthesupplylineofthecoolingcircuit,afterthecirculationpump.
Transmitter, cooling tank outlet
Astrap-ontemperaturedetectorisconnectedonthereturnlineofthecoolingtank.
Transmitter, coolant cooler
Astrap-ontemperaturedetectorisconnectedonthereturnlinefromthecoolantcooler,asclosetothecooleraspos-
sible.
Heat circuit
Cooling agent circuit
Cooling circuit Cooling tank
DHP-R Eco
Modular cable
Cooling fan
Sensor, coolant cooler
Sensor, cooling tank outlet
Sensor, cooling tank
Dew point sensor
Sensor, cooling circuit
Circulation pump
Coolant cooler
Circulation pump
cooling circuit
Pilot valve
cooling circuit
Reversingvalve,coolingtank
Reversingvalve
cooling agent return
Reversingvalve
surplus heat
Cooling module
VMBQI102
VMILF102 Danfoss – 13
Connecting
󰥎 Note!Themaximumloadmaynotexceed50VA.
Cooling module
The cooling module is mounted in the electric cabinet on the intended rail. If there is no room, the module can be installed
inanexternal,enclosedcabinetandconnectedwithalongermodularcable.

• ConnectamodularcablebetweenHPCRMExp.outandHPCCMExp.in
Cooling module connections:
Temperature input, T1: Sensor, cooling tank
Temperature input, T2: Sensor, coolant cooler
Temperature input, T3: Sensor, cooling tank outlet
Temperature input, T4: Sensor, cooling circuit
Analogueinput0-10V,AI1:Signalfromdewpointsensor,roomtemperature0-50°C
Analogueinput0-10V,AI2:Signalfromdewpointsensor,relativehumidity0-100%
Analogueoutput0-10V,AO1:Signaltocoolingcircuitpilotvalve
Analogueoutput0-10V,AO2:Signaltocoolingfans
Relay24VAC,DO1:Signaltoreversingvalveagainstcoolingtank(passivecold)
Exp.in Exp.out
GGNDG0Y1
DO1
G0
G0
DO2
G0
DO3
G0
DO4
G0
DO5
G0
24VAC
T1
AO1
AI2
GND
T2
GND
T3
GND
T4
GND
AI1
GND
GND
GND
AO2
GND
HPC CM
24 VAC
0-10V
0-10V
M
24 VAC
M
24 VAC
24 VAC 24 VAC
24 VAC 2.1
24 VAC 2.2
24 VAC 2.1
24 VAC 2.2
GG
0Y1
GNDY1
24 VAC 2.1
24 VAC 2.1
24 VAC 2.2
AO1
24 VAC 2.2
24 VAC 2.1
DO1,2,4
24 VAC 2.2
Pilot valve,
cooling circuit
Pilot valve,
alternative connection
of cooling circuit
Circ. pump,
coolant cooler
Reversingvalve,
surplus heat
Reversingvalve,
cooling agent return
cooling tank
Alternative connection with
constant voltage feed for
2-point24VACreversingvalve.
Circ. pump,
coolant circuit
Dew point sensor
Cooling fans
FromExp.out
Sensor, cooling tank
Sensor, surplus cooler
Sensor, cooling tank outlet
Sensor, cooling circuit
Roomtemperature
Relativeairhumidity
VMILF10214 – Danfoss
VMBQI102
Relay24VAC,DO2:Signaltoreversingvalveagainstcoolingagentreturn(activecold)
Relay24VAC,DO3:Signaltocoolantcoolercirculationpump
Relay24VAC,DO4:Signaltoreversingvalve,surplusheat
Relay24VAC,DO5:Signaltocoolingcircuitcirculationpump
Transmitter, cooling tank

• ConnecttoT1andGND
Transmitter, coolant cooler

• ConnecttoT2andGND
Transmitter, cooling tank outlet

• ConnecttoT3andGND
Transmitter, cooling circuit

• ConnecttoT4andGND
Dew point sensor

•Connect to 24 VAC 2.1 and 24 VAC 2.2

• ConnectroomtemperaturesensortoAI1andGND

• ConnectrelativeairhumiditysensortoAI2andGND
Pilot valve, cooling circuit

• ConnectAO1tothesignalinputofthepilotvalve

• ConnectGNDtopilotvalveGND

• ConnectthepilotvalveterminalGto24VAC2.1

• ConnectthepilotvalveterminalG0to24VAC2.2
Cooling fans

• ConnectAO2tothesignalinputofthecoolingfan

• ConnectGNDtothecoolingfanGND
Voltage feed to DO output terminals

•Connect 24 VAC to 24 VAC 2.1

• ConnectG0to24VAC2.2
Reversing valve, cooling tank

• ConnectstartrelaytoDO1andG0
Reversing valve, cooling agent return

• ConnectstartrelaytoDO2andG0
Circulation pump, coolant cooler

• ConnectstartrelaytoDO3andG0
Reversing valve, surplus heat

• ConnectstartrelaytoDO4andG0
Circulation pump, cooling circuit

• ConnectstartrelaytoDO5andG0
Alternative connection of reversing valves:
Whenconstantvoltagefeedtoareversalvalve’s2-point24VACadjusterisrequired,establishdirectconnectionto24VAC
2.1and24VAC2.2.Astartrelayisnotnecessarywhenusinga2-point24VACactuator.
Connectthecontrolsignaltothecorrespondingdigitaloutputterminal,DO1,DO2orDO4.
VMBQI102
VMILF102 Danfoss–15
Inputs and outputs, HPC CM
Temperature inputs
Input Use Measurement range
T1 Temperature cooling tank -30 to 70 °C
T2 Temp coolant cooler -30 to 70 °C
T3 Temp outlet cooling tank -30 to 70 °C
T4 Temp cooling circuit 0 to 100 °C
Analogue inputs
Input Use
AI1 Room temperature 0 to 50 °C
AI2 Relative humidity 0 to 100 %
Analogue outputs
Outputs Use
AO1 Control valve cooling circuit
AO2 Cooling fans
Relay outputs
Outputs Use
DO1 Valve passive cooling (Exchange valve brine to tank) 24 VAC
DO2 Valve active cooling 24 VAC
DO3 Circulation pump surplus cooler 24 VAC
DO4 Valve surplus heat 24 VAC
DO5 Circulation pump cooling circuit 24 VAC
VMILF102

Other Danfoss Control Unit manuals

Danfoss TCBE User manual

Danfoss

Danfoss TCBE User manual

Danfoss MCO 101 User manual

Danfoss

Danfoss MCO 101 User manual

Danfoss KP 1 User manual

Danfoss

Danfoss KP 1 User manual

Danfoss PVG 100 Manual

Danfoss

Danfoss PVG 100 Manual

Danfoss MSV-F2 DN Series User manual

Danfoss

Danfoss MSV-F2 DN Series User manual

Danfoss GPS 40-150 User manual

Danfoss

Danfoss GPS 40-150 User manual

Danfoss 087H3817 User manual

Danfoss

Danfoss 087H3817 User manual

Danfoss TS 12.5 User manual

Danfoss

Danfoss TS 12.5 User manual

Danfoss PVG 32 User manual

Danfoss

Danfoss PVG 32 User manual

Danfoss JIP-WW User manual

Danfoss

Danfoss JIP-WW User manual

Danfoss VF3 DN 200 User manual

Danfoss

Danfoss VF3 DN 200 User manual

Danfoss EKF Series User manual

Danfoss

Danfoss EKF Series User manual

Danfoss EVR 2 User manual

Danfoss

Danfoss EVR 2 User manual

Danfoss AMZ 112 User manual

Danfoss

Danfoss AMZ 112 User manual

Danfoss PVG 16 PVH/Covers Manual

Danfoss

Danfoss PVG 16 PVH/Covers Manual

Danfoss AB-QM DN 125 User manual

Danfoss

Danfoss AB-QM DN 125 User manual

Danfoss PN 16 User manual

Danfoss

Danfoss PN 16 User manual

Danfoss KP 15 User manual

Danfoss

Danfoss KP 15 User manual

Danfoss BVTS User manual

Danfoss

Danfoss BVTS User manual

Danfoss TE 5 User manual

Danfoss

Danfoss TE 5 User manual

Danfoss VFS 2 User manual

Danfoss

Danfoss VFS 2 User manual

Danfoss PVG 32 User manual

Danfoss

Danfoss PVG 32 User manual

Danfoss SFV Series User manual

Danfoss

Danfoss SFV Series User manual

Danfoss GBCH Series User manual

Danfoss

Danfoss GBCH Series User manual

Popular Control Unit manuals by other brands

Leadshine Technology MA860H user manual

Leadshine Technology

Leadshine Technology MA860H user manual

Bailey Infi 90 NTAI02 Instruction

Bailey

Bailey Infi 90 NTAI02 Instruction

LOVATO ELECTRIC EXP10 30 instruction manual

LOVATO ELECTRIC

LOVATO ELECTRIC EXP10 30 instruction manual

PEHA 940 BV Installation and operating instructions

PEHA

PEHA 940 BV Installation and operating instructions

GE Tetra GECLPS5-2 installation guide

GE

GE Tetra GECLPS5-2 installation guide

CSM ECAT STGMM 6 user guide

CSM

CSM ECAT STGMM 6 user guide

Samsung RC160MHXGA user manual

Samsung

Samsung RC160MHXGA user manual

M-system R7F4HD-DC32B instruction manual

M-system

M-system R7F4HD-DC32B instruction manual

Knick Protos MS 3400-160 manual

Knick

Knick Protos MS 3400-160 manual

Ewellix SCU installation instructions

Ewellix

Ewellix SCU installation instructions

Neoway S720 manual

Neoway

Neoway S720 manual

ADTRAN E220 HFAC HDSL Installation and Maintenance

ADTRAN

ADTRAN E220 HFAC HDSL Installation and Maintenance

IDEC SmartRelay Series manual

IDEC

IDEC SmartRelay Series manual

VersaMax IC200MDD841 user manual

VersaMax

VersaMax IC200MDD841 user manual

Adeunis RF SIGFOX user guide

Adeunis RF

Adeunis RF SIGFOX user guide

Marshall Excelsior ME904-16 instruction manual

Marshall Excelsior

Marshall Excelsior ME904-16 instruction manual

Madas M14/RM N.C manual

Madas

Madas M14/RM N.C manual

Trinamic TMCL TMCM-6212 Firmware manual

Trinamic

Trinamic TMCL TMCM-6212 Firmware manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.