Specification
Power supply 230 ± 15% Vac, 50/60Hz
Switch action 1 x SPDT voltage free Type 1B
Switch rating
Max. 264Vac, 50/60Hz, 3(1) A
Timing accuracy ± 1 min/month
Power reserve Minimum 10 hours
Enclosure rating IP30
Max. ambient temperature 45°C
Dimensions, mm (W, H, D) 158 x 98 x 38
Design standard EN 60730-2-7
Control Pollution Situation Degree 2
Rated Impulse Voltage 2.5kV
Ball Pressure Test 75°C
1.0 Installation Guide
2.0 System Overview
Please Note:
This product should only be installed by a qualified electrician or
competent heating installer and should be in accordance with the
current edition of the IEEE wiring regulations.
1. Fix the wallplate to the wall or flush mounted box as required.
The connections are at the top and the vertical centre line of the
unit, at the position shown on the diagram below C/L (in line with
terminal ).
2. Surface cables can only enter from below the unit. If mounted on
a flush mounted box, cables can enter from the rear through the
aperture in the wallplate.
3. For mains voltage applications a link must be fitted between
terminals L and 5.
4. Whilst the unit does not require an Earth connection, a terminal is
provided on the wallplate for Earth continuity purposes.
3.0 Installation