Delta HEX180PB User manual

Specification and Manual
Customer :
Description : Heat Exchanger 190 W/K
Customer Part No. : Rev.:
Delta Model No. : HEX180PB Rev : 00
Sample Date Code:
Sample Issue Date : Mar.21.2018
Delta Electronics, Inc.
252, Shang Ying Road, Kuei San District TEL : 886-(0)3-3591968
Taoyuan City 33341, Taiwan, R. O. C. FAX : 886-(0)3-3591991
Please send one copy of this specification back after you
signed approval for production pre-arrangement
Approved by :
Date :

Table of content
Packing & Shipping.........................................................................................................................III
Safety Notes.....................................................................................................................................III
1. Product Instruction....................................................................................................................1
1-1. General Description..........................................................................................................1
1-2. Main Feature & Model Number.......................................................................................1
1-3. Dimension...........................................................................................................................2
1-4. Mounting Panel Cutout.....................................................................................................2
1-5. Configuration & Maintenance..........................................................................................3
1-6. Thermal and Airflow..........................................................................................................4
2. Electrical Specification..............................................................................................................4
2-1. Indicator & Connector.......................................................................................................4
2-1-1 Power Supply & Alarm Connector........................................................................4
2-1-2 Panel Operation......................................................................................................5
2-2. Fan Control Curve.............................................................................................................5
3. Environmental Condition..........................................................................................................6
3-1. Operating Temperature ....................................................................................................6
3-2. Storage Temperature........................................................................................................6
3-3. Operation Humidity...........................................................................................................6
3-4. Ingress Protection Rating.................................................................................................6
3-5. MTBF...................................................................................................................................6
4. Reliability Table..........................................................................................................................6
5. Safety Certification....................................................................................................................6
6. Accessor.....................................................................................................................................7
7. Installation Notice......................................................................................................................7
8. Warranty .....................................................................................................................................8
9. Reclaim.......................................................................................................................................9

Description
This document is an installation and the characteristics of Delta HEX180PB. Before installing the
unit, please read this manual thoroughly, and following the instructions contained in it. The document is
the exclusive property of Delta Electronics, Inc. it should not be distributed, reproduced, or any other
format without prior permission of Delta. Specifications are subject to change without notice.
Packing & Shipping
HEX is a precision instrument, it should be handled or transported with care, do not stand on the box,
or place heavy objects on it. Please pay attention to the following icons on the package.
Safety Notes
Please read the safety notes carefully before installing HEX unit and be sure to install it correctly.
After completing the installation, make sure that the unit operates properly during the start-up operation.
Meaning of WARNING and CAUTION notices:
Warning:
Failure to follow these instructions properly may result in personal injure or loss life.
Caution:
Failure to observe these instructions properly may result in property damage or personal injury,
which may be serious depending on the circumstance.
Warming:
1. Installation work and electrical wiring must be done by qualified person(s) in accordance with all
applicable codes, standards and national wiring regulations.
2. Use this unit only in the manner intended by the manufacturer. If you have questions, please contact the
manufacturer.
Install the HEX in accordance with the instructions in this installation manual. Improper installation may result
in water leakage, electric shocks or fire.

Make sure that all wiring is secured, the specified wires are used, and there is no strain on the terminal
connections or wires.
3. If refrigerant gas leaks during installation, ventilate the area immediately. Do not directly touch refrigerant
that has leaked from refrigerant pipes or other areas, as there is a danger of frostbite.
4. Before serving or cleaning unit, switch power off and disconnect power supply.
5. When cutting or drilling into wall or ceiling, do not damage electrical wiring or hidden utilities.
6. Be sure to use only the specified accessories and parts for installation work.
7. This appliance is intended to be used by expert or trained users in shops, in light industry and on farms,
or for commercial use by lay persons”.
Caution :
1. Install the HEX on a wall/ door strong enough to withstand the weight of the unit.
2. Do not allow a child to mount on the outdoor unit or avoid placing any object on it.
3. Do not block air inlets or exits.
4. Do not install the HEX at any place where there is a danger or flammable gas leakage.
5. To avoid injury, do not touch the air inlet or aluminum fins of unit.
6. Watch your steps at the time of fin cleaning or HEX inspection.
7. Do not topple the HEX while moving or storage.
8. The appliance is not to be used by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or
instruction.
9. Children being supervised not to play with the appliance.

Specification for Approval
Customer :
Description : Heat Exchanger
Customer P/N : Rev. :
Delta model no. : HEX180PB Rev. : 00
Sample revision. : Date Code :
Sample issue date : Quantity :
INTERNAL EXTERNAL

Page 1
1. Product Instruction
1-1. General Description
The Heat Exchanger (HEX) is designed for direct air to air heat exchange to remove the heat from
the cabinet, and there is designed for IP55 sealed outdoor telecom cabinet to provide stable and optimum
internal conditions for equipment and avoid hotspot inside the cabinet. It is easy to be installed in the
cabinet with the nuts.
The internal and the external air circulation loops of the HEX are separated to prevent the
introduction of dust, humidity and dirt. The fan on the external air loop conforms to IP55 protection rating.
1-2. Main Feature & Model Number
Dimensions, Weight & Mounting method
Dimension (H x W x D) (without flange)
mm
780 x 480 x 247
Application
N / A
Outdoor
Weight
Kg
25.0
Mounting Method
N / A
Door / Side
Color (optional)
N / A
RAL7035
Environmental Protection & Performance
Operating Temperature Range
°C
-20 to +65
Refrigerant type and quantity
N / A
R134a / 350±10g
Protection for Dust ,Wind and Water (External)
N / A
IEC60529 IP55
Sound pressure level noise (1.5m)
dB-A
72
Operating Status
N/A
LED Indicator
Cooling Capacity & Operational Data
Rated Cooling Capacity
W / K
190
Operation Cooling Current
A
6.0
Rated Internal Airflow
CMH
935
Rated External Airflow
CMH
935
Power & Range
Input Voltage
VDC
48
Operation Voltage range
VDC
40 - 60
Max. Operating DC Current
A
7.2
Alarm
N / A
Dry Contact Output
Key Components
Controller
N / A
Built-in Smart Controller
Fans
N / A
Delta High Efficiency Blowers
*Note 1 : The cooling capacity (W/K or W/°C) is defined as Q / (TI-TA)
Q : Heat dissipation (W) from inside of cabinet
TI : Return temperature of internal air circuit (K OR °C)
TA : Ambient temperature of external air circuit (K OR °C)

Page 2
1-3. Dimension
(1) Material : steel sheet SGCC t=1.0mm.
(2) Finish : Powder coating 75 μm(MIN.), Color RAL 7035.
(3) Dimensional Tolerance : ± 1.0mm [0.04”]
1-4. Mounting Panel Cutout

Page 3
1-5. Configuration & Maintenance
Make sure the HEX surface sealed with mounting flange to avoid water
penetrates into shelter through mounting interface. It is suggested to use gaskets
sticking on the mounting flange and seal the gap between flange and cabinet with
silicone gel during installation. There should be NO any gap surround gaskets to
avoid water penetrates into enclosure.
In order to assure the HEX running at optimal condition, the condenser should
be cleaned once annually at least; user can clean the condenser with flow water
directly. The external side fan blade can also be cleaned with normal pressure water
if there is dust accumulation. Please do not use strong water jet to impact the
center of fan and the surface of condenser.
The bottom hole of the heat exchangers is used for drainage, please clear
drain holes when the maintenance. Please also notice that following:
1. Check wires are connected correctly, and the insulation is not cracking or
broken.
2. Do not wipe the product with organic solvent, volatile substances like toluene or
gasoline, it will destroy the powder-coated surface.
3. Turn off the power before maintaining.
4. Please turn off power and remove dry contact connector while non-operating for
a long time.
5. If any abnormal acoustic noise from HEX happened, please turn off the product
and contact with customer services.
NO.
Q'TY
DESCRIPTION
1
1
Case Chassis
2
1
Internal Case Cover
3
2
Internal Fans
4
1
Heat Exchanger
(Evap/Cond)
5
1
External Case Cover
6
2
External Fans
7
1
Controller

Page 4
6. The refrigerant is environmental friendly product of R134a. Little refrigerant
leakage (< 5 g/ year) is allowed for application. If refrigerant leakage seriously,
please turn off the power and wait for at least 2 hours to make sure the
refrigerant fully exhaust. Please also contact the services to replace spare
parts.
1-6. Thermal and Airflow
The internal and external air flow circulation is shown as the figure. Through
separated mechanism design, internal and external air flow won’t be mixed since
the waste heat can be dissipated from the cabinet to the ambience. Internal
temperature sensor is placed at return air stream to provide reliable temperature
measurement and safety of operation.
The waste heat generated from the internal equipment will be absorbed by the
refrigerant through the evaporator and dissipate to the ambience by the condenser
of external side.
2. Electrical Specification
2-1. Indicator & Connector
2-1-1 Power Supply & Alarm Connector
PIN FUNCTION
1 -48V
20V
3 NORMAL OPEN
4 COMM
5 NORMAL CLOSE
6 RS485 - A PORT
7 RS485 - B PORT

Page 5
Dry contact : (contact max. rating : 60VDC/400mA)
User can select dry contact definition both normal open (N.O. Pin3,4)
or normal close (N.C.Pin5,4) for alarm output
Normal open
Normal close
Connection
Pin 3 & Pin 4
Pin 5 & Pin 4
Control board, NTC and fan are in
normal status
OPEN
CLOSE
Power-off or control board is disabled
CLOSE
OPEN
NTC resistance is over range such as
“open circuit”or “short circuit”or Over Temp
CLOSE
OPEN
Fan speed is lower than 50% of
definition or fan locked
CLOSE
OPEN
2-1-2 Panel Operation
Fan
NTC sensor
Normal
GREEN
GREEN
Abnormal or failed
RED
Blinking RED
2-2. Fan Control Curve

Page 6
3. Environmental Condition
3-1. Operating Temperature
-20 °C ~ +65 °C (-4 °F ~ 149 °F)
3-2. Storage Temperature
-40 °C ~ +70 °C (-40 °F ~ 158 °F)
3-3. Operation Humidity
External air loop: 0 ~ 100 % RH
Internal air loop: 0 ~ 90 % RH, non-condensing
3-4. Ingress Protection Rating
IP55 (IEC60529) on external side
GR487 on external side
3-5. MTBF
The L10 Fan life expected to be at least 100,000 hours continuous
operation at 35°C with 15~ 65%RH.@ label rated voltage
4. Reliability Table
Test item
Condition
High temperature
IEC 60068-2-2
Low temperature
IEC 60068-2-1
High temp. / High humidity
IEC 60068-2-3
Temperature cycle
IEC 60068-2-14 test Nb
Vibration
ETSI 300 019-1-4 CLASS 4.1
Ingress protection (external side)
IEC 60529 IP55
Salt fog test (external side)
GR487 , 720hrs
Package bump
IEC 60068-2-29
5. Safety Certification
Below safety certificate will be applied when model is available

Page 7
6. Accessor
Connector : DINKLE 2ESDVM-07P
7. Installation Notice
Check the surrounding obstacles to make sure the product get enough space for air circulate.
Pin
Description
Cable wire size
1
-48V
16 AWG
2
0V
16 AWG
3
Normal open
24 AWG
4
Common
24 AWG
5
Normal close
24 AWG
6
RS485 A port
24 AWG
7
Rs485 B port
24 AWG

Page 8
8. Warranty
Delta Electronics, Inc. Warranty for Cabinet Thermal Solutions Products
Delta Electronics, Inc warrants that all Heat Exchangers, Air Conditioners, Heaters, Thermoelectric
Coolers and related products and accessories within its Cabinet Thermal Solutions product family and
manufactured by Delta Electronics, Inc., herein referred to as (“products”), will be free from defects in
material and workmanship for a period of one (1) year from the date of shipment by Delta Electronics,
Inc. This warranty covers repair or replacement of product at the sole discretion of Delta Electronics,
Inc. and is subject to the following Conditions and Exclusions:
A. Conditions.
All products must be installed and operated according to Delta product Specification(s) and
product Instruction/User Manual(s):
Maximum voltage variation is no greater than normal operation and instruction in Delta product
Specification(s) and product Instruction/User Manual(s), with avoidance to power line
disturbances of any kind.
Application is not to exceed minimum and maximum stated operation temperatures and
humidity range as indicated in the Delta product Specification(s) and product Instruction/User
Manual(s).
Filters (if applicable) must be cleaned regularly.
Products and any parts thereof must not be modified, unless prior written authorization is
received from Delta Electronics, Inc.
All products must be installed and grounded in accordance with all relevant electrical and
safety codes, as well as the National Electric Code and OSHA rules and regulations.
All products must be installed in a stationery application, free of vibration and shock.
A violation of any one of these conditions shall render the warranty hereunder void and of no
effect.
B. Exclusions.
This warranty does not cover the following:
Applications where products are being misapplied. This includes inappropriate selection of
products for the environment and conditions in which it is to be used.
Damages caused by shipping carrier or any other accident after products have left Delta
Electronics, Inc. manufacturing facility. Shipping claims are the responsibility of the customer
and are to be completed in a timely manner.
Reimbursement of labor for installation or removal of any warrantied products, or for parts and
labor resulting from repairs performed by any other source besides Delta Electronics, Inc.

Page 9
This is the complete warranty and is in lieu of any other warranty expressed or implied, including
but not limited to any implied warranty of merchantability or fitness for a particular purpose. Delta
Electronics, Inc. will in no way be liable for incidental or consequential damage whatsoever or for
any other claims by the customer for damages in connection with Delta Electronics Inc. products,
even if advised in advance of the possibility of such damage.
Return Procedure
All returns require a Return Material Authorization number (RMA #), regardless of reason for return,
whether it be for warranty or out of warranty repair. Returns without an RMA # will be refused by
Delta Electronics, Inc. Approval for return requests are at the sole discretion of Delta Electronics, Inc.
Buyer should provide the following information at the time of RMA request:
1. Complete Model Number, Serial Number and description of damaged unit requested to be returned.
2. Original Buyer Purchase Order number and date product was received by Buyer.
3. Quantity to be returned and a brief description of failure for each unit, if different.
All returns to Delta Electronics, Inc must be securely packed, using original cartons if possible. All
returns must have the RMA number visible on the outside of the carton. Delta Electronics, Inc. is not
responsible for material damaged in transit.
Shipping cost for all non-warranty repairs is the responsibility of the sender and must be shipped
prepaid. Shipping costs for all warranty related repairs will be covered by Delta Electronics, Inc.
provided the products are returned using a Delta Electronics, Inc approved carrier. If after diagnosis,
products determined by Delta Electronics, Inc. are not covered under warranty, Buyer will be
responsible for all shipping charges and will be billed accordingly.
LIMITATION OF LIABILITY
DELTA ELECTRONICS, INC. WILL NOT BE LIABLE UNDER ANY CIRCUMSTANCES FOR ANY
INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES, INCLUDING WITHOUT LIMITATION ANY
LOST PROFITS OR LABOR COSTS, ARISING FROM THE SALE, USE OR INSTALLATION OF THE
GOODS, FROM THE PRODUCTS BEING INCORPORATED INTO OR BECOMING A COMPONENT OF
ANOTHER PRODUCT, FROM ANY BREACH OF THIS AGREEMENT OR FROM ANY OTHER CAUSE
WHATSOEVER, WHETHER BASED ON WARRANTY (EXPRESSED OR IMPLIED) OR OTHERWISE
BASED ON CONTRACT, OR ON TORT OR OTHER THEORY OF LIABILITY, AND REGARDLESS OF
ANY ADVICE OR REPRESENTATIONS THAT MAY HAVE BEEN RENDERED BY DELTA
ELECTRONICS, INC. CONCERNING THE SALE, USE OR INSTALLATION OF THE PRODUCTS.
9. Reclaim
At the end of the unit working life, the produce must not be disposed of as urban waste. It must be
taken to a special local authority differentiated waste collection center or to a dealer providing this service.
Table of contents
Other Delta Industrial Equipment manuals

Delta
Delta WHITEWATER DF Series User manual

Delta
Delta HEX200PC User manual

Delta
Delta J1900 Series User manual

Delta
Delta HEX150PB Series User manual

Delta
Delta 32-325 User manual

Delta
Delta DVP02LC-SL User manual

Delta
Delta HEX080PD Series User manual

Delta
Delta Dometic CDF 11 User manual

Delta
Delta DTM Series User manual

Delta
Delta HEX260PA-A User manual

Delta
Delta TP02G-AS1 User manual

Delta
Delta HEX110QA User manual

Delta
Delta HEX070PB User manual

Delta
Delta HEX050QA User manual

Delta
Delta ASRTU-EC16AP1TA User manual

Delta
Delta 46-461 User manual

Delta
Delta HEX200PB User manual

Delta
Delta HEX050PA User manual

Delta
Delta HEX080QA Series User manual

Delta
Delta LE-412523 User manual