2 Safety
2.1 Intended use
The glide rail system GSR XEA is used for the
sequential locking control of 2 winged doors. The glide
rail system GSR‑EMF XEA is used for the sequential
locking control and for the locking mechanism to keep
open 2 winged doors. The locking mechanism is used
in conjunction with external RMZ to keep open fire
and smoke protection closures. Fire and smoke
protection closures must meet the building regulation
requirements ‘’self‑locking’’. The electromechanical
locking device is no substitution for a door stop. The
locking device is released manually or via an external
RMZ.
2.2 Limitation of liability
The manufacturer does not assume liability for
damages in the following events:
• Nonobservance of this instruction.
• A deviating application of the intended use.
• The assignment of insufficiently skilled staff.
• Unauthorized modifications.
• Technical alterations.
• The use of spare parts which are not authorized.
2.3 Prerequisites for the
operation of catching devices
The use of the slide rail systems as catching devices
(GSR‑EMF XEA) is subject to special regulations by
reason of official admission standards. These
regulations refer in particular to the inspection, the
continuing surveillance and the maintenance. Follow
the details from the data sheet about the use of
catching devices.
Additional requirements apply for the use as fire and
smoke protection closures in conjunction with the
external RMZ and RM. A separate verification of
suitability is required for the respective fire / smoke
protection door.
3 Product description
GSRXEA
The GSR XEA comprises the following components:
• Slide rail system with sequential locking control
The GSR XEA is intended for the mounting on the
hinge side. The GSR XEA is suitable for DIN‑L and
DIN‑R doors.
GSR‑EMFXEA
The GSR‑EMF XEA comprises the following
components:
• Slide rail system with sequential locking control
• Built‑in electromechanical locking device
The GSR‑EMF XEA is intended for the mounting on
the hinge side. The GSR‑EMF XEA is suitable for
DIN‑L and DIN‑R doors. The GSR‑EMF XEA is
available in three versions:
• GSR‑EMF1:
The fixed leaf is fitted with an EMF. Both leaves
may be locked. The sequential locking control keeps
the active leaf open.
• GSR‑EMF2:
The active leaf and fixed leaf are each fitted with an
EMF.
The active leaf can either be locked independently
from the fixed leaf or both door leaves can be
locked.
• GSR‑EMF1G:
The active leaf is fitted with an EMF. The active leaf
can be locked. The fixed leaf cannot be locked.
Each door leave that is fitted with an EMF can be
locked in an opening angle of approx. 80°–130°.
Statements
Statement
(lever length)
Door width
(mm)
GSRXEA
GSR‑EMFXEA
VK (320 mm) 1220–1350
V (375 mm) 1350–2500
VL (375 mm) 2500–2800
3.1 EMF
The EMF is an electromechanical locking mechanism
with adjustable release force, which enables locking
the door without spring back. After a cut‑off of power
supply, the locking device disengages and the door will
be closed securely through the door closer.
3.2 Technical data of the EMF
Operating voltage: 24V DC
in France also 48VDC
Power consumption: EMF 1, 1G 1,4 W
EMF 2 2,8 W
in France also
EMF 1, 1G 2,2 W
EMF 2 4,4 W
Duty cycle: 100 % ED
Release torque: approx. 25 – 65 Nm at 90°
opening angle (dependent
on the set closing force on
the closer)
Door opening angle:
EMF 1
EMF 2
EMG 1G
Active leaf Fixed leaf
max. 180° max. 130°
max. 130° max. 130°
max. 130° max. 180°
The drive happens via an external RMZ.
3GSR XEA/GSR-EMF XEA 2017-10
dormakaba Mounting instruction
WN 059376 45532
Safety