E2S GNExCP6B-PT User manual

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880
Document D154-00-251-IS Issue 7 26-08-2020 Sheet 1 of 3 www.e2s.com Fax +44 (0)208 740 4200
GNExCP6B-PT, GNExCP6D-PT &
GNExCP6E-PT
Manual Call Point – Tool reset
With Resistor Modules
For use in Flammable Gas and
Combustible Dust Atmospheres.
1) Introduction
The GNExCP6B-PT/ GNExCP6D-PT/ GNExCP6E-
PT is a tool reset button manual call point which is
certified to the European and International Gas and
Dust standards. The unit meets the requirements of
the ATEX directive 2014/34/EU and IECEx
scheme.
The call point can be used in hazardous areas
where potentially flammable gas and dust
atmospheres may be present.
All units have up to two of the following series and/
or EOL devices:
Monitoring resistors per module: -
GNExCP6B-PT - 2.0W Max
GNExCP6D-PT - 1.0W Max
GNExCP6E-PT - 1.75W Max
Monitoring diode
Monitoring Zener diode
GNExCP6B-BG units may also incorporate an LED
indicator in addition to the two series and/ or EOL
devices allowed.
The units are Group II, EPL (equipment protection
level) Gb. The equipment is certified ‘Ex db eb mb
IIC T4 Gb’ and as such may be used in Zones 1
and 2 with flammable gases and vapours with gas
groups IIA, IIB & IIC and temperature classes T1,
T2, T3 and T4.
These units are also Group III, EPL Db. The
equipment is certified:
‘Ex tb IIIC T80ºC Db’ (GNExCP6B-PT),
‘Ex tb IIIC T80ºC Db’ (GNExCP6D-PT),
‘Ex tb IIIC T75ºC Db’ (GNExCP6E-PT)
and as such may be used in Zones 21 and 22 for
combustible dusts groups IIIA, IIIB & IIIC.
2) Ratings & Markings
All units have a rating label, which carries the
following important information: -
Unit Type No.:
GNExCP6B-PT Manual Call Point
GNExCP6D-PT Manual Call Point
GNExCP6E-PT Manual Call Point
Input Voltages:
48VDC nominal 56VDC Max 0.75A Max
24VDC nominal 28VDC Max 5.0A Max Resistive
Load; 3.0A Max Inductive Load
12VDC nominal 15VDC Max 5.0A Max
6VDC nominal 9VDC Max 5.0A Max
Code:
GNExCP6B-PT
Ex db eb mb IIC T4 Gb
Ex tb IIIC T80ºC Db
IP66
–40ºC <= Ta <= +50ºC
GNExCP6D-PT
Ex db eb mb IIC T4 Gb
Ex tb IIIC T80ºC Db
IP66
–40ºC <= Ta <= +70ºC
Certificate No.:
SIRA 09ATEX3286X
IECEx SIR 09.0121X
Epsilon x: II 2GD
CE Marking
Notified body No. 2813
Year/Serial No. i.e. 20/1CP6BPT000001
Or 20/1CP6DPT000001
Or 20/1CP6EPT000001
WARNING - DO NOT OPEN WHEN AN
EXPLOSIVE ATMOSPHERE MAY BE PRESENT,
ELECTROSTATIC HAZARD – CLEAN ONLY
WITH A DAMP CLOTH
3) Type Approval Standards
The call point has an EC Type examination
certificate issued by SIRA and have been approved
to the following standards: -
EN60079-0:2018 / IEC60079-0:2017
EN60079-1:2014 / IEC60079-1:2014
EN60079-7:2015 / IEC60079-7:2017
EN60079-18:2015 / IEC60079-18:2014
EN60079-31:2014 / IEC60079-31:2013
The equipment is certified for use in ambient
temperatures in the range:
GNExCP6B-PT -40oC to +50oC
GNExCP6D-PT -40oC to +70oC
GNExCP6E-PT -40oC to +65oC
and shall not be used outside this range.
4) Installation Requirements
out by suitably trained personnel in accordance
with the applicable code of practice e.g.
IEC 60079-14/EN 60079-14
Repair of this equipment shall only be carried out
by the manufacturer or in accordance with the
applicable code of practice e.g. IEC 60079-19/EN
60079-19.
Refer to certificates SIRA 09ATEX3286X and
IECEx SIR 09.0121X for special conditions of safe
use.
The certification of this equipment relies on the
following materials used in its construction:
Enclosure: GRP - Glass Reinforced Polyester
Through enclosure mechanism: Plastic Nylon Zytel
Injection Moulded
Sealing of enclosure and mechanism: O-ring
Acrylonitrile-Butadiene Rubber
Potting Compound of resistors where used: Epoxy
Resin
If the equipment is likely to come into contact with
aggressive substances, then it is the responsibility
of the user to take suitable precautions that prevent
it from being adversely affected, thus ensuring that
the type of protection is not compromised.
“Aggressive substances” - e.g. acidic liquids, gases
or solvents that may affect polymeric materials.
“Suitable precautions” - e.g. regular checks as part
of routine inspections or establishing from the
material’s data sheet that it is resistant to specific
chemicals.
Under extreme conditions the unit may generate an
ignition-capable level of electrostatic charges. The
unit must not be installed in a location where it may
be subjected to external conditions (such as high-
pressure steam) which may cause a build-up of
electrostatic charges on non-conducting surfaces.
Cleaning of the unit must only be carried out with a
damp cloth.
5) Call Point Location and Mounting
The location of the call point should enable ease of
access for operation and testing. The unit should
be mounted using the 4 off fixing holes which will
accept up to M5 sized fixings.
INSTRUCTION
MANUAL
GNExCP6B-PT, GNExCP6D-PT & GNExCP6E-PT Tool Reset Manual Call Point
For
use in Flammable Gas and Dust Atmos
p
here
s
GNExCP6E-PT
Ex db eb mb IIC T4 Gb
Ex tb IIIC T75ºC Db
IP66
–40ºC <= Ta <= +65ºC

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880
Document D154-00-251-IS Issue 7 26-08-2020 Sheet 2 of 3 www.e2s.com Fax +44 (0)208 740 4200
View of base unit showing fixing centres (in mm).
To gain access to the mounting holes in the base
the front cover must be removed.
This is achieved by removing the 4 off M4 cap
head bolts holding on the cover.
Once the screws are removed the cover will hang
down out of the way to gain access to the Ex e
terminal block, the internal earth terminal and
mounting hole recesses.
6) Earthing
The unit has an internal earth terminal.
It is recommended that a cable crimp lug is used
on the earth wires.
The internal earth wire is placed under an earth
clamp which will stop the cable twisting. This is
secured by an M4 screw and spring washer.
Internal Earth Ex e terminal block
terminal
Note: Depending on options chosen an 8-Way DIN
Rail or 6-Way terminal block may be selected.
7) Cable connections
There are 3 off cable entries for M20x1.5 Ex e
approved cable glands or stopping plugs with a
minimum ingress protection of IP66
The unit can be wired in a number of different ways
depending on the device combination selected.
EOL (End of line) device;
resistor – ExxxR / diode – ED1 / zener – ExxxZ
Series (In line) device;
resistor – SxxxR / diode – SD1 / zener – SxxxZ /
LED
Microswitch 1 = M/S 1
Microswitch 2 = M/S 2
The unit can be wired with a maximum of 2 module
devices – refer to wiring schematic D154-06-051
Voltage
option
Max
Voltage
Min
resistor
value
allowable
in module
Type B
unit
(2.0W)
Min
resistor
value
allowable
in module
Type D
unit
(1.0W)
Min
resistor
value
allowable
in module
Type E
unit
(1.75W)
6 V dc 9 V dc 47 ohms 91 ohms 51 ohms
12V dc 15 V dc 120 ohms 240 ohms 150 ohms
24V dc 28 V dc 470 ohms 820 ohms 510 ohms
48V dc 56 V dc 1K8 ohms 3K3 ohms 2K0 ohms
When wiring to Increased Safety terminal
enclosures, you are only permitted to connect one
wire into each way on the terminal block unless a
pair of wires are crimped into a suitable ferrule.
For the six-way terminal block wire sizes allowable
are 0.5mm² to 4.0mm². For the 8-way DIN rail wire
sizes allowable are 0.5mm² to 2.5mm².
Leads connected to the terminals shall be insulated
for the appropriate voltage and this insulation shall
extend to within 1mm of the metal of the terminal
throat. They shall only be installed and wired with
cable in an ambient temperature of -10°C to +80°C
All terminal screws, used or unused, shall be
tightened down to between 0.5 Nm and 0.7 Nm
7.1) Fitted LED, Diode or Zener Diode
If a diode module is pre-fitted as either an EOL or
series device, the following current limitation
applies:
Unit Volta
g
e Max. Current
48V DC 0.75A
6, 12 & 24V DC 2.0A
If a Zener diode module is pre-fitted as either EOL
or Series device, the following current limitation
applies:
Zener
Voltage
Max. Input
Voltage
Max. Current
3.3V
56V DC
230m
A
4.7V 162mA
5.1V 149mA
5.6V 136m
A
6.2V 122mA
6.8V 112mA
10V 76mA
12V 63mA
If an LED indicator is pre-fitted (optional on
GNExCP6B Units only), the LED is protected by
the LED current-limiting resistor. See value of this
resistor in table below. This only applies to units
with LED option code ‘L’.
GNExCP6B-PTXXXXXXXXXL-XX-ExxxR-SxxxR
LED Resistor Max. Input Voltage
3K3
(
3300Ω
)
56V DC
1K5 (1500Ω) 28V DC
In any scenario, the lowest value of maximum
current should be used. For example, if the unit has
both a diode and a Zener diode, the Zener diode
would determine the maximum input current of the
unit, since its max. current is lowest.
8) Testing unit operation
The tool reset button unit can be tested without the
need to replace any element.
To test, lift the cover lift flap to reveal the tool reset
button. The button should be pressed into the body
to activate the unit and place it into the operated
condition.
The call point switch will now change over its
contacts to operate the alarm.
Once testing is complete the unit needs to be reset
from the operated condition.

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880
Document D154-00-251-IS Issue 7 26-08-2020 Sheet 3 of 3 www.e2s.com Fax +44 (0)208 740 4200
Using the special reset tool provided, rotate the tool
reset button anticlockwise by an angle of 55°, see
guide alignment marks on the button and cover,
shown below (1). The tool reset button should pop
back up to its original position.
Ensure that the tool reset button has also twisted
back clockwise by 55° to its original position see
guide marks on button and cover, shown below (2).
The unit is now reset.
1. On operated unit 2. Button should pop
twist tool reset button up and twist back to
anticlockwise 55° original position
with special key to reset
Resetting an operated unit is the same as resetting
a tested unit.
9) SIL 2 Reliability Data
Reliability and Functional safety IEC/EN61508
which has been assessed and is considered
suitable for use in low demand safety function:
• Random Hardware Failures and Systematic
Failures (route 2H)
• As an unvoted item (i.e. hardware fault tolerance
of 0) at SIL 2
The product was assessed against failure modes:
• Failure to close a contact when the call point is
struck with specified force
• Failure to open a contact when the call point is
struck with specified force
• Spurious output despite no input
Integrityinrespectoffailuretoclose SIL2
TotalFailurerate 0.133pmh
“hazardous”failurerate(revealed) 0pmh
“hazardous”failurerate(unrevealed) 0.1pmh
“safe”failurerate(revealed) 0.033pmh
“safe”failurerate(unrevealed) 0
DiagnosticCoverage 99%
Systemtype A
HardwareFaultTolerance 0
SafeFailureFraction >99%
PFD(hazardousfailure) 1.25x10‐3
ProofTestInterval Upto1year
Note: use alignment
marks circled to
indicate the tool
reset buttons
status/position
Unit currently shown
as ‘standby
condition’
This manual suits for next models
2
Other E2S Security System manuals

E2S
E2S BExCBGL2-05D-P User manual

E2S
E2S D1xC2 Series User manual

E2S
E2S D1xS1FDC024-S User manual

E2S
E2S D1xS2 Series User manual

E2S
E2S AlertAlight DL105X User manual

E2S
E2S D2xB1LD2DC024 User manual

E2S
E2S BexCS11005D24DC-RD User manual

E2S
E2S STExB2RT1 User manual

E2S
E2S GNExCP6B-PB User manual

E2S
E2S BExCTS110-05D-P User manual