GNExCP6B-PB, GNExCP6C-PB &
GNExCP6D-PB
Manual Call Point – Push Button
With Resistor Modules
For use in Flammable Gas and
Combustible Dust Atmospheres.
1) Introduction
The GNExCP6B-PB/ GNExCP6C-PB/ GNExCP6D-
PB is a push button manual call point which is
certified to the European and International Gas and
Dust standards. The unit meets the requirements
of the ATEX directive 2014/34/EU and IECEx
scheme.
The call point can be used in hazardous areas
where potentially flammable gas and dust
atmospheres may be present.
2) Ratings & Markings
All units have a rating label, which carries the
following important information: -
Unit Type No.:
GNExCP6B-PB Manual Call Point
GNExCP6C-PB Manual Call Point
GNExCP6D-PB Manual Call Point
Input Voltages:
48VDC nominal 56VDC Max 0.75A Max
24VDC nominal 28VDC Max 5.0A Max Resistive
Load; 3.0A Inductive Load
12VDC nominal 15VDC Max 5.0A Max
6VDC nominal 9VDC Max 5.0A Max
Code:
GNExCP6B-PB GNExCP6C-PB
Ex db eb mb IIC T4 Gb Ex db eb mb IIC T4 Gb
Ex tb IIIC T80ºC Db Ex tb IIIC T75ºC Db
IP66 IP66
–40ºC <= Ta <= +50ºC –40ºC <= Ta <= +65ºC
GNExCP6D-PB
Ex db eb mb IIC T4 Gb
Ex tb IIIC T80ºC Db
IP66
–40ºC <= Ta <= +70ºC
Certificate No.:
SIRA 09ATEX3286X
IECEx SIR 09.0121X
Epsilon x: II 2GD
CE Marking
Notified body No. 2813
Year/Serial No. i.e. 20/1CP6BPB000001
Or 20/1CP6CPB000001
Or 20/1CP6DPB000001
WARNING - DO NOT OPEN WHEN AN
EXPLOSIVE ATMOSPHERE MAY BE PRESENT,
ELECTROSTATIC HAZARD – CLEAN ONLY
WITH A DAMP CLOTH
3) Type Approval Standards
The call point has an EC Type examination
certificate issued by SIRA and have been approved
to the following standards: -
EN60079-0:2018 / IEC60079-0:2017
EN60079-1:2014 / IEC60079-1:2014
EN60079-7:2015 / IEC60079-7:2017
EN60079-18:2015 / IEC60079-18:2014
EN60079-31:2014 / IEC60079-31:2013
The equipment is certified for use in ambient
temperatures in the range:
GNExCP6B-PB -40oC to +50oC
GNExCP6C-PB -40oC to +65oC
GNExCP6D-PB -40oC to +70oC
and shall not be used outside this range.
4) Installation Requirements
Installation of this equipment shall only be carried
out by suitably trained personnel in accordance
with the applicable code of practice e.g.
IEC 60079-14/EN 60079-14
Repair of this equipment shall only be carried out
by the manufacturer or in accordance with the
applicable code of practice e.g. IEC 60079-19/EN
60079-19.
The certification of this equipment relies on the
following materials used in its construction:
Enclosure: GRP - Glass Reinforced Polyester
Through enclosure mechanism: Plastic Nylon Zytel
Injection Moulded
Sealing of enclosure and mechanism: O-ring
Acrylonitrile-Butadiene Rubber
Potting Compound of resistors where used: Epoxy
Resin
If the equipment is likely to come into contact with
aggressive substances, then it is the responsibility
of the user to take suitable precautions that prevent
it from being adversely affected, thus ensuring that
the type of protection is not compromised.
“Aggressive substances” - e.g. acidic liquids, gases
or solvents that may affect polymeric materials.
“Suitable precautions” - e.g. regular checks as part
of routine inspections or establishing from the
material’s data sheet that it is resistant to specific
chemicals.
Leads connected to the terminals shall be insulated
for the appropriate voltage and this insulation shall
extend to within 1mm of the metal of the terminal
throat. They shall only be installed and wired with
cable in an ambient temperature of -10°C to +80°C
All terminal screws, used or unused, shall be
tightened down to between 0.5 Nm and 0.7 Nm
Refer to certificates SIRA 09ATEX3286X and
IECEx SIR 09.0121X for special conditions of safe
use.
Under extreme conditions the unit may generate an
ignition-capable level of electrostatic charges. The
unit must not be installed in a location where it may
be subjected to external conditions (such as high-
pressure steam) which may cause a build-up of
electrostatic charges on non-conducting surfaces.
Cleaning of the unit must only be carried out with a
damp cloth.
5) Call Point Location and Mounting
The location of the call point should enable ease of
access for operation and testing. The unit should
be mounted using the 4 off fixing holes which will
accept up to M4 sized fixings.
View of base unit showing fixing centres (in mm).
To gain access to the mounting holes in the base
the front cover must be removed.
This is achieved by removing the 4 off M4 cap
head bolts holding on the cover.
INSTRUCTION MANUAL
GNExCP6B-PB, GNExCP6C-PB & GNExCP6D-PB Push Button Manual Call Point
For use in Flammable Gas and Dust Atmospheres

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sale[email protected] Tel: +44 (0)208 743 8880
Document D154-00-151-IS Issue 6 03-02-2020 Sheet 2 of 5 www.e2s.com Fax +44 (0)208 740 4200
Once the screws are removed the cover will hang
down out of the way to gain access to the Ex e
terminal block, the internal earth terminal and
mounting hole recesses.
6) Earthing
The unit has an internal earth terminal.
It is recommended that a cable crimp lug is used
on the earth wires.
The internal earth wire is placed under an earth
clamp which will stop the cable twisting. This is
secured by an M4 screw and spring washer.
Internal Earth Ex e terminal block
terminal
7) Cable connections
There are 3 off cable entries for M20x1.5 Ex e
approved cable glands or stopping plugs with a
minimum ingress protection of IP66
The unit can be wired in a number of different ways
depending on the device combination selected.
GNExCP6B-PB / GNExCP6C-PB / GNExCP6D-PB
EOL (End of line) device; resistor – ExxxR / diode
– ED1 / zener – ExxxZ
Series (In line) device; resistor – SxxxR / diode –
SD1 / zener – SxxxZ / LED
Microswitch 1 = M/S 1
Microswitch 2 = M/S 2
The unit can be wired with a maximum of 2 module
devices – see wiring diagrams.
Note: - The maximum voltage stated must not be
exceeded, as the internal resistor modules are
rated as compliant with Ex mb according to the
units voltage
Please refer to wiring diagrams on sheets 4 & 5.
When wiring to Increased Safety terminal
enclosures, you are only permitted to connect one
wire into each way on the terminal block, unless a
pair of wires are crimped into a suitable ferrule.
Wire sizes allowable are 0.5sqmm to 4.0sqmm
The terminals are only permitted to be wired with
cable in an ambient temperature range of between
-10°C to 80°C. All terminal screws, used or
unused, must be fully tightened down.
Leads connected to the terminals must be
insulated for the appropriate voltage and this
insulation must extend to within 1mm of the metal
of the terminal throat.
8) Testing unit operation
The push button unit can be tested without the
need to replace any element.
To test, lift the cover lift flap to reveal the push
button. The button should be pressed into the body
to activate the unit and place it into the operated
condition.
The call point switch will now change over its
contacts to operate the alarm.
Once testing is complete the unit needs to be reset
from the operated condition.
Rotate the push button anticlockwise by an angle
of 55°, see guide alignment marks on the button
and cover, shown below (1). The push button
should pop back up to its original position.
Ensure that the push button has also twisted back
clockwise by 55° to its original position see guide
marks on button and cover, shown below (2). The
unit is now reset
1. On operated unit 2. Button should pop
twist push button up and twist back to
anticlockwise 55° original position
to reset
Resetting an operated unit is the same as resetting
a tested unit.
Note: use alignment
marks circled to
indicate the push
buttons
status/position
Unit currently shown
as ‘standby
condition’

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sale[email protected] Tel: +44 (0)208 743 8880
Document D154-00-151-IS Issue 6 03-02-2020 Sheet 3 of 5 www.e2s.com Fax +44 (0)208 740 4200
9) SIL 2 Reliability Data
Reliability and Functional safety IEC/EN61508
which has been assessed and is considered
suitable for use in low demand safety function:
• Random Hardware Failures and Systematic
Failures (route 2H)
• As an unvoted item (i.e. hardware fault tolerance
of 0) at SIL 2
The product was assessed against failure modes:
• Failure to close a contact when the call point is
struck with specified force
• Failure to open a contact when the call point is
struck with specified force
• Spurious output despite no input
Integrityinrespectof
failuretoclose
SIL2
TotalFailurerate 0.133pmh
“hazardous”failure
rate(revealed)
0pmh
“hazardous”failure
rate(unrevealed)
0.1pmh
“safe”failurerate
(revealed)
0.033pmh
“safe”failurerate
(unrevealed)
0
DiagnosticCoverage 99%
Systemtype A
HardwareFault
Tolerance
0
SafeFailureFraction >99%
PFD(hazardous
failure)
1.25x10‐3
ProofTestInterval Upto1year

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
Document D154-00-151-IS Issue 6 03-01-2020 Sheet 4 of 5 www.e2s.com Fax +44 (0)208 740 4200
Wiring Diagrams
1A - Circuit shown in Unoperated condition
Terminals +(2,3) & -(4,5) open
Terminals +(2,3) & (6) closed
Single Microswitch with EOL (End Of Line) Device
Resistor: - ExxxR
Diode: - ED1
Zener Diode: - ExxxZ
1B - Circuit shown in Operated condition
(Button pressed In)
Terminals +(2,3) & -(4,5) closed
Terminals +(2,3) & (6) open
Single Microswitch with Series Device
Resistor: - SxxxR
Diode: - SD1
Zener Diode: - SxxxZ
LED: - LED
2A - Circuit shown in Unoperated condition
Terminals +(2,3) & -(4,5) open
Terminals +(2,3) & (6) closed
2B - Circuit shown in Operated condition
(Button pressed In)
Terminals +(2,3) & -(4,5) closed
Terminals +(2,3) & (6) open
Single Microswitch with EOL & Series Device
EOL Series
Resistor: - ExxxR SxxxR
Diode: - ED1 SD1
Zener Diode: - ExxxZ SxxxZ
LED: - N/
A
LED
3A - Circuit shown in Unoperated condition
Terminals +(2,3) & -(4,5) open
Terminals +(2,3) & (6) closed
3B - Circuit shown in Operated condition
(Button pressed In)
Terminals +(2,3) & -(4,5) closed
Terminals +(2,3) & (6) open
4B - Circuit shown in Operated condition
(Button pressed In)
Terminals +(1,2) & -(4,5) M/S 1 closed
Terminals +(1,2) & (6) M/S 1 open
4A - Circuit shown in Unoperated condition
Terminals +(1,2) & -(4,5) M/S 1 open
Terminals +(1,2) & (6) M/S 1 closed
Single Microswitch with EOL & Series Device
Wiring Option 2 –W2
EOL Series
Resistor: - ExxxR SxxxR
Diode: - ED1 SD1
Zener Diode: - ExxxZ SxxxZ
LED: - N/
A
LED

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
Document D154-00-151-IS Issue 6 03-01-2020 Sheet 5 of 5 www.e2s.com Fax +44 (0)208 740 4200
5A - Circuit shown in Unoperated condition (Glass Intact)
Terminals+ (1) & -(2) M/S 1 open and +(4) & -(5) M/S 2 open
Terminals +(1) & (3) M/S 1 and +(4) & (6) M/S 2 closed
Dual Microswitch with EOL (End Of Line) Device/s
Resistor: - ExxxR
Diode: - ED1
Zener Diode: - ExxxZ
5B - Circuit shown in Operated condition (Glass Broken)
Terminals+ (1) & -(2) M/S 1 open and +(4) & -(5) M/S 2 closed
Terminals +(1) & (3) M/S 1 and +(4) & (6) M/S 2 open
Dual Microswitch with Series Device/s
Resistor: - SxxxR
Diode: - SD1
Zener Diode: - SxxxZ
LED: - LED
7B - Circuit shown in Operated condition
(Glass Broken)
Terminals +(2) & -(3) M/S 1 and +(6) & -(7) M/S 2 closed
Terminals +(2) & (4) M/S 1 and +(6) & (8) M/S 2 open
Dual Microswitch with EOL & Series Device/s
EOL Series
Resistor: - ExxxR SxxxR
Diode: - ED1 SD1
Zener Diode: - ExxxZ SxxxZ
LED: - N/A LED
8A - Circuit shown in Unoperated condition
(Glass Intact)
Terminals +(2) & -(3) M/S 1 and +(6) & -(7) M/S 2 open
Terminals +(2) & (4) M/S 1 and +(6) & (8) M/S 2 closed
8B - Circuit shown in Operated condition
(Glass Broken)
Terminals +(2) & -(3) M/S 1 and +(6) & -(7) M/S 2 closed
Terminals +(2) & (4) M/S 1 and +(6) & (8) M/S 2 open
(DIN RAILONLY) (DIN RAILONLY)
BY
R
12345678
+
-
M/S 1
+
-
EOL
RL1
M/S 1
SERIES
LED
BY
R
12345678
+
-
M/S 1
+
-
EOL
RL1
M/S 1
SERIES
LED
Single Microswitch with L.E.D,
EOL & Series Device
EOL Series
Resistor: - ExxxR SxxxR
Diode: - ED1 SD1
Zener Diode: - ExxxZ SxxxZ
LED: - N/A LED
7A - Circuit shown in Unoperated condition
(Glass Intact)
Terminals +(2,3) & -(4,5) open
Terminals +(2,3) & (6) closed
2
+
3
+
4
-
5
-
EOL
SERIES
LED
6A - Circuit shown in Unoperated condition
(Glass Intact)
Terminals +(2,3) & -(4,5) open
Terminals +(2,3) & (6) closed
6B - Circuit shown in Operated condition
(Glass Broken)
Terminals +(2,3) & -(4,5) closed
Terminals +(2,3) & (6) open
Other manuals for GNExCP6B-PB
1
This manual suits for next models
2
Table of contents
Other E2S Security System manuals

E2S
E2S D1 B2X05 Series User manual

E2S
E2S GNExCP6C-PT User manual

E2S
E2S D2xB1X05 Series User manual

E2S
E2S APPELLO A105NAX User manual

E2S
E2S STExB2LD2 User manual

E2S
E2S BExBG15D-P-SIL User manual

E2S
E2S SONFL1XDC012 User manual

E2S
E2S D2xC1 Troubleshooting guide

E2S
E2S BexCS11005D24DC-RD User manual

E2S
E2S IS-mA1M User manual