Fig. 2: Accessing the Explosion proof Enclosure
On completion of the installation, the flameproof threaded joint
should be inspected to ensure that they are clean and that they
have not been damaged during installation. Flameproof
threaded joints are not intended to be repaired. Also check that
the ‘O’ ring seal is in place. When fitting the flameproof cover
ensure the thread is engaged correctly. Fully tighten the cover
all the way, ensure no gap is visible between the cover and
base of the beacon enclosure. Tighten the M4 grub screw.
8) Power Supply Selection
It is important that a suitable power supply is used to run the
beacons. The power supply selected must have the necessary
capacity to provide the input current to all of the beacons
The following table shows the input current taken by the
various beacons:
A supply voltage variation of +/-10% outside the voltage range
is permissible.
Nominal current at nominal voltage and 1Hz flash rate
Max rated current at worst case supply voltage and flash rate.
9) Selection of Cable, Cable Glands, Blanking
Elements & Adapters
When selecting the cable size, consideration must be given to
the input current that each unit draws (see table above), the
number of beacons on the line and the length of the cable runs.
The cable size selected must have the necessary capacity to
provide the input current to all of the beacons connected to the
line.
For ambient temperatures over +40ºC the cable entry
temperature may exceed +70ºC or the cable branching point
temperature may exceed +80 ºC and therefore suitable heat
resisting cables and cable glands must be used as per table
below
STExRT1:
Min. Rating
of cables
and cable
glands
The cable entries have an M20 x 1.5 –6H entry thread. If the
installation is made using cable glands, only suitably rated and
ATEX / IECEx & UKEx certified cable glands must be used.
They must be suitable for the type of cable being used and
also meet the requirements of the current installation
standards EN 60079-14 / IEC60079-14.
Any unused cable entries must be closed with suitably rated
and ATEX / IECEx & UKEx certified blanking plugs.
If the installation is made using conduit, openings must have a
sealing fitting connected as close as practical to the wall of the
enclosure, but in no case more than the size of the conduit or
50mm, whichever is the lesser.
If a high IP (Ingress Protection) rating is required then a
suitable sealing washer must be fitted under the cable glands
or blanking plugs. A minimum ingress protection rating of IP6X
must be maintained for installations in explosive dust
atmospheres.
For combustible dust applications, the cable entry device and
blanking elements shall be in type of explosion protection and
shall have an IP 6X rating.
The STEx Beacon Range can be supplied with the following
types of adapters:
M20 to ½” NPT
M20 to ¾” NPT
M20 to M25
It is important to note that stopping plugs cannot be fitted onto
adapters, only directly onto the M20 entries.
Any other adapters used must be suitably rated and ATEX /
IECEx & UKEx certified adapters.