  9. Eastron SDM530D User manual

Eastron SDM530D User manual

Three phase din rial meter SDM530D user manual
SDM530D
THREE PHASE FOUR WIRE ENERGY METER WITH S0 PULSE OUTPUT
(SEVEN MODULE)
User manual
------------
1.1
Safety
instruction
1.2
Foreword
1.3
Performance
criteria
1.4
Specifications
1.5
Basic
errors
1.6
Dimension
&
material
1.7
Installation
1.8
Operating
1.9
CT
ratio
setting
(SDM530D
CT
only)
1.10
Technical
support
Three phase din rial meter SDM530D user manual
1.1 Safety instructions
Information for Your Own Safety
This manual does not contain all of the safety measures for operation of the equipment (module,
device), because special operating conditions, and local code requirements or regulations may
necessitate further measures. However, it does contain information which must be read for your
personal safety and to avoid material damages. This information is highlighted by a warning triangle
and is represented as follows, depending on the degree of potential danger.
Warning
This means that failure to observe the instruction can result in death, serious injury or
considerable material damage.
Caution
This means hazard of electric shock and failure to take the necessary safety
precautions will result in death, serious injury or considerable material damage.
Qualified personnel
Operation of the equipment (module, device) described in this manual may only be performed by
qualified personnel. Qualified personnel in this manual means person who are authorized to
commission, start up, ground and label devices, systems and circuits according to safety and
Regulatory standards.
Use for the intended purpose
The equipment (device, module) may only be used for the application specified in the catalogue and
the user manual, and only be connected with devices and components recommended and approved
by Eastron Electronic.
Proper handling
The prerequisites for perfect, reliable operation of the product are proper transport, proper storage,
installation and assembly, as well as proper operation and maintenance. When operating electrical
equipment, certain parts of this equipment automatically carry dangerous voltages. Improper
handling can therefore result in serious injuries or material damage.

Use
only
insulating
tools
.

Do
not
connect
while
circuit
is
live
(hot)
.

Place
the
meter
only
in
dry
surroundings
.

Do
not
mount
the
meter
in
an
explosive
area
or
expose
the
meter
to
dust,
mildew
and
insects.

Make
sure
the
used
wires
are
suitable
for
the
maximum
current
of
this
meter
.

Make
sure
the
AC
wires
are
connected
correctly
before
activating
the
current/voltage
to
the
meter.

Do
not
touch
the
meter
connecting
clamps
directly
with
your
bare
hands,
with
metal,
blank
wire
or other material as you may get an electrical shock.

Make
sure
the
protection
cover
is
placed
after
installation
.

Installation,
maintenance
and
reparation
should
only
be
done
by
qualified
personnel
.

Never
break
the
seals
and
open
the
front
cover
as
this
might
influence
the
functionality
of
the
meter, and will avoid any warranty.

Do
not
drop,
or
allow
physical
impact
to
the
meter
as
there
are
high
precision
components
inside
that may break.
Three phase din rial meter SDM530D user manual
Disclaimer
We have checked the contents of this publication and every effort has been made to ensure that the
descriptions are as accurate as possible.
However, deviations from the description cannot be completely ruled out, so that no liability can be
accepted for any errors contained in the information given. The data in this manual is checked
regularly and the necessary corrections are included in subsequent editions. We are grateful for any
improvements that you suggest.
Subject to technical modifications without notice.
Copyright
Copyright Eastron Electronic Instruments Co., Ltd. All rights Reserved.
It is prohibited to pass on or copy this document or to use or disclose its contents without our express
permission. Any duplication is a violation of the law and subject to criminal and civil penalties. All
rights reserved, particularly in the event of a patent award or utility model registration.
1.2 Foreword
the Eastron SDM530D DIN rail three phase four wire energy meter. The Eastron SDM530D energy
meter is the most advanced type electronic kWh meter available at the market. With the Eastron
product range we have introduced a large scale of energy meters on the market suitable for 110V AC
to 400V AC (50 or 60Hz).
The Eastron SDM530D has two versions, direct connection version and CT connection version. The
direct connection version SDM530D can be connected to load up to 100A. While the SDM530D CT
version shall be connected with 5A secondary output current transformer. The CT ratio can be
programmable via the buttons on the front panel.
The meter adopts big size LCD display with a highlight blue color backlit. The backlit has 3 modes
(always on, always off, on for 30seconds after each button click) programmable from the front button.
With high accuracy and long lifespan design, the SDM530D is a perfect option for any three phase
applications. 18 month quality warranty is offered, Eastron is responsible for replacement of any
failure meters, which caused by production or design mistake.
1.3 Performance criteria
Operating humidity ≤ 85%
Storage humidity ≤ 95%
Operating temperature -10°C-+50°C
Storage temperature -30°C-+70°C
International standard IEC 62053-21
Accuracy class 1
Protection against penetration of dust and water IP51
Insulating encased meter of protective class Ⅱ
Three phase din rial meter SDM530D user manual
1.4 Specifications
Meter type SDM530D
SDM530D CT
Nominal voltage (Un) 230/400V AC (3~)
Operational voltage 176/264 – 304/456V AC (3~)
Insulation capabilities
- AC voltage withstand
- Impulse voltage withstand
4KV for 1 minute
6KV – 1.2µS waveform
Basic current (Ib)
Directly connect
CT connect
10A
5A
Maximum rated current (Imax)
Directly connect
CT connect
100A
6A
Operational current range 0.4% Ib- Imax
Over current withstand 30Imax for 0.01s
Operational frequency range 50Hz ±10%
Internal power consumption ≤2W / 10VA per phase
Test output flash rate (PULSE LED)
Directly connect
CT connect
400imp/kWh
1600imp/kWh
Test pulse output rate (pins 8 & 9)
Directly connect
CT connect
400imp/kWh
1600imp/kWh
Power missing indicator (Phase A,B & C LED) the LED will burning if the phase power is missing.
Consumption indicator (PULSE & SO LED) Flashing at load running
1.5 Basic errors
With balanced loads
0.05Ib Cosφ = 1 ±1.5%
0.1Ib Cosφ = 0.5L
Cosφ = 0.8C
±1.5%
±1.5%
0.1Ib - Imax Cosφ = 1 ±1.0%
0.2Ib - Imax Cosφ = 0.5L
Cosφ = 0.8C
±1.0%
±1.0%
With single phase load
0.1Ib - Imax Cosφ = 1 ±2.0%
0.2Ib - Imax Cosφ = 0.5L ±2.0%
Three phase din rial meter SDM530D user manual
1.6 Dimension
1.7 Installation

We
recommend
that
the
connecting
wire
which
is
used
to
connect
the
meter
to
the
outside
circuit should be sized according to local codes and regulations for the capacity of the circuit
breaker or over current device used in the circuit.

An
external
switch
or
a
circuit-breaker
should
be
installed
on
the
inlet
wire,
which
will
be
used
as a disconnection device for the meter. And there it is recommended that the switch or
circuit-breaker is near the meter so that it is more convenience for the operator. The switch or
circuit-breaker should comply with the specifications of the buildings electrical design and all
local regulations.

An
external
fuse
or
thermal
cut-off
which
will
be
used
as
a
over
current
protection
device
for
the meter must be installed on the supply side wire, and it is recommended that the over
CAUTION

Turn
off
all
the
power
before
working
on
it.

Always
use
a
properly
rated
voltage
sensing
device
to
confirm
that
power
is off.
WARNING

Installation
should
be
performed
by
qualified
personnel
familiar
with
applicable codes and regulations.

Use
i
nsulating
tools
to
install
the
meter.

Fuse
or
thermal
cut-off
or
single-pole
circuit
breaker
can
’
t
be
fitted
on
the
supply line and not the neutral line.
Three phase din rial meter SDM530D user manual
current protection device is near the meter so that it is more convenience for the operator.
The over current protection device should comply with the specifications of the buildings
electrical design and all local regulations.

This
meter
can
be
installed
indoor
directly,
or
in
a
meter
box
which
is
waterproof
outdoor
,
subject to local codes and regulations.

To
prevent
tampering,
secure
the
meter
with
a
padlock
or
a
similar
device
.

The
meter
has
to
be
installed
against
a
wall
which
is
fire
resistant
.

The
meter
has
to
be
installed
in
a
good
ventilated
and
dry
place
.

The
meter
has
to
be
installed
in
a
protection
box
when
placed
in
dangerous
or
dusty
environment.

The
meter
can
be
installed
and
used
after
being
tested
and
sealed
with
a
letter
press
printing.

The
meter
can
be
installed
on
a
35mm
DIN
rail
or
direct
on
a
meter
board
with
screws
.

The
meter
should
be
installed
in
a
n
available
height
so
that
it
is
easy
to
read.

When
the
meter
is
installed
in
an
area
with
frequent
surges
due
to
e.q.
thunderstorms,
welding machines, inverters etc, protect the meter with Surge Protection Devices

After
finishing
installation,
the
meter
must
be
sealed
to
prevent
tampering.

Connection
of
the
wires
should
be
done
in
accordance
with
the
underneath
connection
diagram.
Direct connect type CT connect type
1.8 Operating
Consumption indication
On the SDM530D’S front panel, there are four LED, in which three LED are for three phase voltage and
another one for impulse. The constant of the impulse is shown on the nameplate of the meter.
Reading the meter
The SDM530D energy meter is equipped with 6+1 or 5+2 LCD display, which is used as recording
consumption and can’t be reset to zero. The number system is based on units of 10. And unit is kWh.
On the front panel, there are two rubber buttons, which are used to scroll down the meter display
information.
Pulse output
SDM530D series DIN rail energy meter is equipped with a pulse output which is fully separated from
the inside circuit. That generates pulses in proportion to the measured energy. They are test pulse
output (pins 8 & 9). Usually, the test pulse output is used as testing accuracy or reading purpose in
close quarters.
The test pulse output is a polarity dependant, passive transistor output requiring an external voltage
source for correct operation. For this external voltage source, the voltage (Ui) should be 5-27V DC,
Three phase din rial meter SDM530D user manual
and the maximum input current (Imax) should be 27mA DC. To connect the impulse output, connect
5-27V DC to connector 9 (anode), and the signal wire (S) to connector 8 (cathode). The meter pulses
is indicated on the front panel.
LEDs
There are four LEDs on the front panel, they are marked with A B C and imp/kwh.
A B C are phase voltage missing indicators , and imp/kwh is pulse output indicator.
Yellow Green Red
A-phase power Does not shine Bright Bright
B-phase power Bright Does not shine Bright
C-phase power Bright Bright Does not shine
Only AB power Does not shine Does not shine Bright
Only AC power Does not shine Bright Does not shine
ABC together on
the power
Does not shine Does not shine Does not shine
LCD display
When the meter is power on, the meter will display:
Full screen
2S
Software version 7P 1.0
5S
Impulse constant 1600imp/kWh
5S
CT ratio (CT type only)
5S
Accumulated used energy
If the CT ratio is less than 150:5, the LCD display will shows 6 integrals plus 1 decimal.
If the CT ratio is set bigger than 150:5, then the LCD will show 7 integrals.
Three phase din rial meter SDM530D user manual
Two button functions:
To set the meter LCD backlight modes, CT ratio and confirm the option.
To scroll the LCD backlit mode and choose CT ratio
Backlit Setting
SDM530D is equipped with highlight blue color backlit, which provide a clear view of reading
when the meter is installed in a dark condition.
There are three modes optional:
ONLED: the backlit always on
OFFLED: the backlit always off
OPEN30S: the backlit will turn on after each click of button
Three phase din rial meter SDM530D user manual
1.9 CT Ratio setting (SDM530D CT only)
The SDM530D CT measure the secondary energy consumption via external current transformer.
If the user wants to read the primary energy reading, he can program the CT ratio to the meter
by the front buttons. The meter has 27 pre-set and common CT ratios optional to the user.

Other manuals for SDM530D

1

This manual suits for next models

1

Other Eastron Measuring Instrument manuals

Eastron SDM530-MT User manual

Eastron

Eastron SDM530-MT User manual

Eastron SDM630-Modbus V2 User manual

Eastron

Eastron SDM630-Modbus V2 User manual

Eastron SDM120 Series User manual

Eastron

Eastron SDM120 Series User manual

Eastron SDM320-C User manual

Eastron

Eastron SDM320-C User manual

Eastron SDM120 Series User manual

Eastron

Eastron SDM120 Series User manual

Eastron SDM630-Modbus V2 User manual

Eastron

Eastron SDM630-Modbus V2 User manual

Eastron SDM630MCT-RC User manual

Eastron

Eastron SDM630MCT-RC User manual

Eastron SDM72D User manual

Eastron

Eastron SDM72D User manual

Eastron SDM530D User manual

Eastron

Eastron SDM530D User manual

Eastron SDM630MCT V2 User manual

Eastron

Eastron SDM630MCT V2 User manual

Eastron SMART X96 Series User manual

Eastron

Eastron SMART X96 Series User manual

Eastron DCM230 User manual

Eastron

Eastron DCM230 User manual

Eastron SDM530C User manual

Eastron

Eastron SDM530C User manual

Eastron SDM630MCT Series User manual

Eastron

Eastron SDM630MCT Series User manual

Eastron SDM630MCT V2 User manual

Eastron

Eastron SDM630MCT V2 User manual

Eastron SDM230-Modbus User manual

Eastron

Eastron SDM230-Modbus User manual

Eastron SDM230A User manual

Eastron

Eastron SDM230A User manual

Eastron SDM530Y User manual

Eastron

Eastron SDM530Y User manual

Eastron SDM72CT-M User manual

Eastron

Eastron SDM72CT-M User manual

Eastron SDM630-Modbus MID V2 User manual

Eastron

Eastron SDM630-Modbus MID V2 User manual

Eastron SDM230-Modbus User manual

Eastron

Eastron SDM230-Modbus User manual

Eastron SDM630MCT-MBUS V2 User manual

Eastron

Eastron SDM630MCT-MBUS V2 User manual

Eastron SDM230-Modbus User manual

Eastron

Eastron SDM230-Modbus User manual

Eastron SDM630MCT-LoRaWAN User manual

Eastron

Eastron SDM630MCT-LoRaWAN User manual

Popular Measuring Instrument manuals by other brands

Zeversolar ComBox Installation and operation instructions

Zeversolar

Zeversolar ComBox Installation and operation instructions

PSI HX-400 operating instructions

PSI

PSI HX-400 operating instructions

LOVATO ELECTRIC EXP10 16 instruction manual

LOVATO ELECTRIC

LOVATO ELECTRIC EXP10 16 instruction manual

AEMC 6526 quick start guide

AEMC

AEMC 6526 quick start guide

Proceq Original Schmidt Live quick start guide

Proceq

Proceq Original Schmidt Live quick start guide

POK Froggy 2.5 manual

POK

POK Froggy 2.5 manual

Extech Instruments 380363 user guide

Extech Instruments

Extech Instruments 380363 user guide

S+S Regeltechnik THERMASGARD TM 43 Series Operating Instructions, Mounting & Installation

S+S Regeltechnik

S+S Regeltechnik THERMASGARD TM 43 Series Operating Instructions, Mounting & Installation

HP 432A manual

HP

HP 432A manual

Powerfix Profi 94500 Operation and safety notes

Powerfix Profi

Powerfix Profi 94500 Operation and safety notes

Wolverine Airsoft REAPER GEN II owner's manual

Wolverine Airsoft

Wolverine Airsoft REAPER GEN II owner's manual

BC Group International BC Biomedical ESU-2000A user manual

BC Group International

BC Group International BC Biomedical ESU-2000A user manual

Macnaught MX06S instruction manual

Macnaught

Macnaught MX06S instruction manual

PCE Instruments PCE-CSM 1 manual

PCE Instruments

PCE Instruments PCE-CSM 1 manual

Ashcroft 2032 operating instructions

Ashcroft

Ashcroft 2032 operating instructions

Schaller humimeter FL1 user manual

Schaller

Schaller humimeter FL1 user manual

Extech Instruments TM100-NIST user guide

Extech Instruments

Extech Instruments TM100-NIST user guide

COMECO TC67U Operation manual

COMECO

COMECO TC67U Operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.