manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Eaton
  6. •
  7. Control Unit
  8. •
  9. Eaton Durant Eclipse Series User manual

Eaton Durant Eclipse Series User manual

Other manuals for Durant Eclipse Series

3

This manual suits for next models

4

Other Eaton Control Unit manuals

Eaton PowerXL DX-NET-DEVICENET User manual

Eaton

Eaton PowerXL DX-NET-DEVICENET User manual

Eaton ELC-AN04ANNN User manual

Eaton

Eaton ELC-AN04ANNN User manual

Eaton xComfort F94 Series User manual

Eaton

Eaton xComfort F94 Series User manual

Eaton DX-NET-BACNETMSTP Manual

Eaton

Eaton DX-NET-BACNETMSTP Manual

Eaton Digitrip RMS 910 Manual

Eaton

Eaton Digitrip RMS 910 Manual

Eaton CEAG 3-PM-IO-INV Service manual

Eaton

Eaton CEAG 3-PM-IO-INV Service manual

Eaton EWFFSC15 User manual

Eaton

Eaton EWFFSC15 User manual

Eaton PXR-PCAM Manual

Eaton

Eaton PXR-PCAM Manual

Eaton ELC-MC01 User manual

Eaton

Eaton ELC-MC01 User manual

Eaton DXE-EXT-SET Manual

Eaton

Eaton DXE-EXT-SET Manual

Eaton OPTC4 LonWorks User manual

Eaton

Eaton OPTC4 LonWorks User manual

Eaton PKE-COM-RTU Manual

Eaton

Eaton PKE-COM-RTU Manual

Eaton DX-LN1 Series Manual

Eaton

Eaton DX-LN1 Series Manual

Eaton ELC-COENETM User manual

Eaton

Eaton ELC-COENETM User manual

Eaton Crouse-hinds series User manual

Eaton

Eaton Crouse-hinds series User manual

Eaton eNMC2 User manual

Eaton

Eaton eNMC2 User manual

Eaton SM65 User manual

Eaton

Eaton SM65 User manual

Eaton COOPER POWER SERIES User manual

Eaton

Eaton COOPER POWER SERIES User manual

Eaton ELC-CODNETM User manual

Eaton

Eaton ELC-CODNETM User manual

Eaton RFAPM User manual

Eaton

Eaton RFAPM User manual

Eaton NRX Digitrip 1150 Manual

Eaton

Eaton NRX Digitrip 1150 Manual

Eaton Power XL SmartWire-DT DX-NET-SWD3 Manual

Eaton

Eaton Power XL SmartWire-DT DX-NET-SWD3 Manual

Eaton Crouse-hinds series User manual

Eaton

Eaton Crouse-hinds series User manual

Eaton EOP5T07 User manual

Eaton

Eaton EOP5T07 User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Durant®
Installation and Operation
Manual Number 57750-920-02
Durant
Eclipse Series Analog Input
Flow Totalizers
Flow Ratemeters
Flow Batch Controls
Models: 5775X-42X - Totalizer w/Rate
5775X-43X - Batch Control
Table of Contents
1 Introduction
1 Description
10 Mounting
11 Wiring
20 Programming
38 Run Mode
6 Diagnostics and Error
Messages
9 Specifications
PGM
View Edit
Enter Start
Reset
Stop
PGM
BATCH
Durant
Visit our Web Site at
w w w.durant.com
1
This manual describes the installation of Durant models 5775X- 2X and 5775X-
3X. These counters are intended to be used with analog output flowmeters and
flow transmitters, therefore this manual will focus on their use in flow applications.
This manual starts with a general description of flow applications and the Eclipse.
This should provide a useful reference point for the installer. Installers are the un-
sung heroes of industry who laugh in the face of the three most-feared words in the
English language: Some Assembly Required. Installers are often given a vague
objective and some equipment; in this case pipe, valves, a flowmeter, and a counter,
with which to accomplish the mission. It is then up to the installer to use his knowl-
edge and ingenuity to make the system work.
The installation section of this manual follows the description. This provides de-
tailed information on mounting, wiring, and programming the Eclipse. The installa-
tion section uses terms that were explained in the description. Installation is nor-
mally the most complex aspect of the Eclipse, therefore the installation section is
the largest section of this manual. The bad news is that the Eclipse is very versatile,
and through wiring and programming variations, can solve a variety of applications.
The good news is that most flow applications will not require all of the wiring and
programming choices that are possible with the Eclipse. The key for the installer is
to know what must be accomplished and to know what is in the Eclipse with which
to do it.
There are three final sections in this manual. Run mode describes the operator
functions of the Eclipse. Diagnostics explains the self diagnostics and error mes-
sages that may appear on the display. The last section is specifications.
Description
Forty ( 0) model variations of the Eclipse are covered by this manual. The Eclipse is
either AC powered or DC powered. It consists of a base unit totalizer with 12 pos-
sible combinations of optional outputs, or a base unit batch control with 8 possible
combinations of optional outputs. While reading this description, it is important to
remember two things. First, all models can display flow rate. Second, the batch
control, known simply as the batcher to its fans, does all of the functions of the
totalizer. Check the part number breakdown chart on the next page to determine
what your unit is made up of. Read the description section(s) to identify how those
functions will be used in your particular application.
INTRODUCTION / DESCRIPTION
2
Base Unit
A totalizer is basically a counter that just counts. The Eclipse totalizer answers the
questions how much?, and how fast?. A typical application for a flow totalizer
would be a water meter for a building. As illustrated below, when a valve is opened
inside the building, water will flow through the pipe that feeds the building from the
water main. This flow causes the flowmeter to generate an electrical signal which is
sent to the totalizer.
Pulses In
Flowmeter Valve Flow
Reset
PGM
View Edit
Enter
PGM
Duran
t
The electrical signal varies directly with flow rate. As the rate of flow increases, the
flowmeter output voltage or current increases. The Eclipse determines flow rate by
reading the amplitude of the flowmeter signal, similar to the way speed is shown on
the speedometer of a car. The Eclipse then integrates the rate over time to deter-
mine total flow, similar to the way the odometer integrates speed over time to deter-
mine mileage.
DESCRIPTION cont.
5775X-4XX
Power Supply
0 = DC (9-30 VDC)
1 = AC (85-265 VAC)
Output Option
0 = No Option
1 = Dual Relays (Standard on Batch)
2 = Analog Output (4-20mA & 0-10V
3 = Dual Relays & Analog Output
4 = RS-485 Communications
5 = Dual Relays & RS-485
6 = Analog Output & RS-485
7 = Dual Relays, Analog Output & RS-485
A = One Relay, One Transistor
B = One Relay, One Transistor, Analog Out
C = One Relay, One Transistor, RS-485
D = One Relay, One Transistor, Analog Out & RS-485
Input / Function
0 = Pulse-Input Totalizer/Ratemeter
1 = Pulse-Input Batch Control
2 = Analog-Input Totalizer/Ratemeter
3 = Analog-Input Batch Control
Pulse input models are covered
by manual #57750-900
*
*
*
Eclipse Flow Model Numbers
3
Once installed, normally only the front panel of the Eclipse totalizer will be visible. It
will look like this:
Reset
PGM
View Edit
Enter
PGM
Durant
Four Input Keys
Six digit
LED
Display
Program Mode
Indicating
LED
The LED display dominates the front panel. The operator will view the total and rate
on this display. In totalizing applications, six digits (up to 999,999) is often not ad-
equate. The installer has three options in this case, all available through program-
ming.
1. The installer can program the Eclipse to divide the total by 10 (display up to
999,999 tens of gallons).
2. The installer can divide by 100 (display up to 999,999 hundreds of gallons).
3. The installer can display a 10 digit total in the form of the low five digits and the
high five digits on successive screens.
The display will also be used by the installer for programming purposes.
The four input keys will be used primarily by the installer for programming purposes,
but the operator can use them also for changing the display screen from total to rate,
for example. The reset key is programmable. For the base unit, the reset key can
reset the total, or do nothing for the operator.
The program mode indicating LED lets the installer know that he is in the program
mode.
The totalizer base unit has a control input board installed that allows the installer to
wire external switches to it to reset the total and to lock out the program mode from
the operator. These inputs may also perform other functions if the relay option board
is installed.
A batch control is a counter that opens a valve to allow flow to start and counts out
a certain preset volume of liquid as entered by the operator. It then shuts off the valve
after the batch has been delivered. This is a closed-loop control system. There are
DESCRIPTION cont.
4
DESCRIPTION cont.
two variations of batch control. The first, and most common is the single valve
approach represented by the diagram below.
Single Valve Batch Control
Analog Signal In
Flowmeter Valve Flow
PGM
View Edit
Enter Start Reset
Stop
PGM
BATCH
Durant
Relay 1
Out
Assume that a cosmetics manufacturer has just blended a 100,000 gallon vat of his
economy perfume, and that he wants to ship it to his customers in 55 gallon drums.
The operator enters 55 into the batch final preset by using the keys on the front
panel of the Eclipse batcher. When an empty drum is in place beneath the outlet
pipe, the operator presses the start key. This causes the batch final relay, (relay 1) to
turn ON, which in turn, opens the solenoid valve. With the valve open, perfume flows
from the vat to the drum. The flowmeter detects the flow and sends a signal to the
counter. The counter happily integrates this signal and counts up to 55. At this point,
the batcher realizes that the amount delivered to the drum is equal to the amount
entered by the operator in the batch final preset. The batch final relay turns OFF,
shutting the valve. When the operator has removed the full drum and placed another
empty drum under the outlet pipe, he again presses the start key and another batch
of 55 gallons will be delivered.
Once the batch delivery has been started, it will normally shut off automatically at the
batch final preset value. However, most users will want the ability to manually stop
the delivery as well. Assume that the operator had started his 55 gallon batch, and
then noticed that the drum had a hole in its side. The operator would then press the
front panel stop key, which would immediately turn the batch final relay OFF, shutting
the valve. Now the operator has a decision to make. Perhaps he can plug the hole
with a piece of chewing gum. In this case, he makes the repair and resumes delivery
of the batch from where he stopped by pressing the start key again. However, maybe
the operator determined that the hole could not be repaired. Then he would termi-
nate the batch by resetting the counter. The resume function, completing a batch
after it had been manually stopped, and the terminate function, ending a batch after
a manual stop, are necessary functions of a batch control.
5
The second batch application is the two valve approach that uses both internal
relays of the batcher. Each relay controls a valve, as illustrated below:
Dual Valve Batch Control
Analog Signal In
Flowmeter
Main Valve
Flow
PGM
View Edit
Enter Start
Reset
Stop
PGM
BATCH
Durant
Relay 2 Out
Dribble Valve
Relay 1 Out
The cosmetics plant made the single valve installation and soon 55 gallon drums
were being shipped out to customers everywhere. The installer stayed at the site to
observe the operation of the system and insure that it met his high standards.
Before long, the look of concern on the installers face made it clear that he was not
satisfied. Two things were troubling him. First, at the end of each batch, some extra
perfume was always delivered. The installer recognized that this was a clear case of
overrun. When the batcher delivered 55 gallons and turned OFF the valve, it took a
certain amount of time for the valve to actually close. During this time some flow
occurred. The amount of flow that occurs from the time that the batcher reaches the
batch final count until flow actually stops is called overrun.
The second observation that concerned the installer was the pounding that his
delicate plumbing took each time the valve closed. It was obvious that the shock of
going from a full flow state to a no flow state in less than one tenth of a second would
eventually cause an unauthorized exit in the system - a leak.
The installer knew that the solution for both problems was to use the dual valve
approach. This meant installing a small pipe around the valve. This pipe, the dribble
pipe, would also be equipped with a valve, known as a dribble valve. The dribble
valve is controlled by the batch final relay (relay 1), and the main valve is controlled by
relay 2, which is programmed to be the batch prewarn output. This fiendishly clever
setup operates in a simple manner. When a batch is started, both relays turn ON,
both valves open, and flow commences at a full flow rate. At a set value before the
batch final preset is reached, the prewarn relay turns OFF, closing the main valve,
and flow is reduced to the dribble rate. When the batch final preset is reached, the
batch final relay turns OFF, shutting the dribble valve and stopping the flow.
The set value before the batch final preset is the batch prewarn preset. It will
probably be set by the installer. The batcher does the arithmetic internally to deter-
DESCRIPTION cont.
6
mine at what batch count value the prewarn relay should turn OFF by subtracting the
batch prewarn preset from the batch final preset. Assume batch prewarn is set to 3.
When filling 55 gallon drums, the prewarn relay shuts off the main valve when the
batch reaches 52 gallons (55 minus 3). Should the operator decide to fill 30 gallon
drums, he simply changes the batch final preset to 30. The batcher would then shut
off the main valve when the batch reaches 27 gallons (30 minus 3). Although the
installer knows that prewarn operation is the result of careful planning, to the opera-
tor this has the appearance of magic. The batcher always knows when to shut off
the main valve, regardless of the preset batch size. If the operator concludes that the
installer has the power to create the mythical anticipating relay, it is not our duty to
confuse him with the facts.
Already some installers are thinking of other ways to use the batch control outputs.
For instance, some may wish to use the batch final relay to control a valve, and the
batch prewarn relay to operate a pump. This manual simply cannot cover all the
possibilities.
Once installed, normally only the front panel of the Eclipse batcher will be visible. It
will look like this:
PGM
View Edit
Enter Start
Reset
Stop
PGM
BATCH
Four Input Keys
Six digit
LED
Display
Program
Mode
Indicating
LED
Durant
The LED display dominates the front panel. The operator will view various counters,
presets, and the rate on this display. The installer will view and edit programming
selections on the display.
The four input keys have operator and installer functions. The operator may use
them to change display screens from count, to preset, to rate, etc. and possibly to
reset counters. The operator may also use these keys to start, stop, resume, and
terminate batch delivery.
The program mode indicating LED lets the installer know that he is in the program
mode when it is ON. This LED will flash ON and OFF for the operator when a batch
is running. Once a batch has been stopped, either manually or automatically, the
LED will remain OFF until another batch is started.
The installer is probably now thinking well, it seems that we have batch delivery
pretty well covered, but how about those totalizer functions that this thing is sup-
DESCRIPTION cont.
7
posed to do? This manual is glad you asked that question. There are actually two
other counters inside the box. One is a totalizer that counts along with the batch
counter. However, while the batch counter is reset at the beginning of each batch, the
totalizer is not reset; it continues to count up. The cosmetics manufacturer resets his
totalizer each time he blends another 100,000 gallon vat. As the batch counter deliv-
ers 55 gallon drums, the totalizer counts the total amount delivered. When the total-
izer reaches 100,000, it is time to blend another vat of perfume and reset the totalizer.
The third counter is the cycle counter. The cycle counter keeps track of how many
batches had been delivered; it counts the number of batches. The mere presence of
the cycle counter opens the door to some interesting variations of batch delivery
automation. The batch counter may be programmed to auto recycle. This is done by
programming a time in the range of 1.0 to 9.9 seconds for batch recycle time. In this
case, the operator starts the initial batch manually. Once the first batch is delivered,
the batcher stops for the duration of the auto recycle time and then automatically
starts another batch. This may continue until the operator manually stops the pro-
cess with the cycle counter showing the number of batches run. However, the cycle
counter has a setpoint, called cycle preset, which will stop the process automati-
cally after that number of batches has been delivered. This type of operation is
known as cycle autostop. If a batch autorecycle time of 0.0 is programmed, the
batcher stops after each batch has been delivered, and each batch must be manu-
ally started by the operator.
Two other things can happen when the cycle counter reaches the cycle preset, cycle
reset and cycle output. The cycle counter will automatically reset to zero if it is pro-
grammed to reset at cycle setpoint. This feature would normally be employed in
combination with the use of an output at cycle setpoint. If both relays are already
used to deliver the batch, or if relay 2 is used for another function, this will not be
possible. Refer to the relay output option description on page 32. If relay 2 is avail-
able to be used as a cycle output, the cycle counter can cause any combination of the
following events at the cycle preset value:
1. Cycle autostop or no autostop.
2. Cycle counter reset or continue to count up.
3. Cycle output or no output.
When all is said and done, most users will simply use the cycle counter to count
batches and nothing else. However, the installer will certainly appreciate knowing
the possibilities.
There are a few final points to be made about the batchers base unit. First, it also
provides an alarm output at a preset rate, if relay 2 is not used for another function.
Second, the relay output board, an option for the Eclipse totalizer, is always included
in the batcher. The outputs are described in the relay output option description on
page 8. Third, a control input board is installed in the unit. The board has three
DESCRIPTION cont.
8
inputs that may be programmed to do a number of functions such as counter(s)
reset, unlatch outputs, program mode lockout, and the batch control start and stop
functions.
Relay Output Option Board
Two types of output boards are available for the Eclipse. One is a dual relay as
indicated by the last digit of the part number being a 1, 3, 5, or 7. The other is a single
relay/single transistor as indicated by the last digit of the part number being an A, B,
C, or D. In either case, output 1 is a relay. One of the output option boards is standard
in the batch control unit. Output 1 is dedicated as the batch final output in the batcher.
Output 2 can be programmed to one of the totalizer output functions described
below, or to the batch prewarn or cycle setpoint function. The batch prewarn output is
described on page 5. As a cycle setpoint output, it will turn ON when the cycle count
reaches the cycle preset value, and turn OFF either after a programmable time in the
range of 0.01 to 99.99 seconds elapses, or after an unlatch 2 input occurs. The
unlatch input can be either a control input or a front panel key programmed to unlatch
2.
If the output board is installed in a totalizer base unit, either output can be pro-
grammed to perform one of the following totalizer output functions:
1. Totalizer setpoint. This option is not available if the totalizer is programmed to
10 digit total. Turns ON when the totalizer counts to a number greater than or
equal to the totalizer preset value. Turns OFF either after a programmable
time in the range of 0.01 to 99.99 seconds elapses, or after an unlatch input
occurs. If the output is programmed to latch (no timeout), the output will be
checked at each input sample until an unlatch input occurs, even after power
has been cycled OFF and then ON to the unit.
2. Rate low setpoint. Turns ON when the rate is less than or equal to the rate low
setpoint. However, from a start condition (power up for the totalizer; batch start
for the batcher), the rate reading must first become greater than or equal to
the rate low setpoint value before this alarm feature is enabled. Turns OFF
after a programmed timeout in the range of 0.01 to 99.99 seconds, or when
an unlatch input occurs, or when the rate becomes greater than the setpoint
(follows mode). This output is updated each time the rate display updates.
3. Rate high setpoint. Turns ON when the rate is greater than or equal to the rate
high setpoint. Turns OFF after a programmed timeout, or when an unlatch
input occurs, or when the rate becomes less than the setpoint (follows mode).
. Rate low-high setpoint. Turns ON when the rate is less than or equal to the
rate low setpoint, OR is greater than or equal to the rate high setpoint. If the
rate low setpoint is greater than the rate high setpoint, the output will be ON
when the rate is greater than the rate high setpoint AND less than the rate low
setpoint. Follows mode only.
DESCRIPTION cont.
9
5. Totalizer pulse output. Puts out a timed pulse for each totalizer count. This
signal is intended to go to a remote totalizer. The pulse width ON time is
selectable to be either 500 +/- 8 msec, 2 msec, or 50 msec. The minimum
OFF time is the same as the ON time. Regardless of the totalizer display
mode selected for the Eclipse (i.e. divide by 1, 10, or 100), the totalizer pulse
output operates in the divide by 1 mode. The totalizer pulse output has a
9,999 count buffer. Because of the nature of this output, it is recommended
that a transistor output be used for this function.
Analog Output Option Board
Sometimes known as analog retransmission, the installer can assign the output to
follow displayed rate, or total, or batch count. Both -20 mA and 0-10V outputs are
given; however they are not independently programmable. The installer programs
not only the assignment, but the offset and full scale values. Both outputs follow the
assigned count or rate and go from minimum value ( mA and 0V) to maximum
value (20 mA and 10V) as the displayed count or rate goes from offset value to full
scale value. Both outputs are electrically isolated from all other circuitry inside the
Eclipse.
S 485 Serial Communications Option Board
This option board allows a host device, such as a computer, to download and read
programming selections, and to perform most of the run mode operator functions
such as read count and rate, enter setpoints, reset counters, and start and stop
batch delivery.
This manual does not contain information on the serial command protocol or the
serial command list. That information is contained in the 57750 serial specification
and obtainable by contacting the Durant Literature Department at 800-5 0-92 2
(US and Canada), or 920-261- 070, or by FAX at 920-261-9097.
DESCRIPTION cont.