ECD Brake Board User manual

Brake Board Manual
Revision Date: Jan 19, 2018
ECD System
Manual

2
E L E C T R O N I C C I R C U I T D E S I G N S P T Y . L T D .
Operation Guide
This manual covers all versions of Brake Board
hardware and software, although some features
mentioned in this manual might not be available on
earlier versions
Electronic Circuit Designs Pty. Ltd.
Factory 11/30 Perry Street • Matraville • NSW • Australia • 2036
Phone 61 2 9316 6909 • Fax 61 2 9316 6797
Email sales@ecd.com.au Web www.ecd.com.au

3
Table Of Contents
Section 1.1 Safety Regulations ...................................................................................... 4
Section 1.2 Obligations & Liability ............................................................................... 4
1.2.1 Following operating instructions................................................................................. 4
1.2.2 Obligations of operator. ................................................................................................ 4
1.2.3 Obligations of personnel. .............................................................................................. 4
1.2.4 Safety during normal operation. .................................................................................. 5
1.2.5 Hazards caused by electric power. .............................................................................. 5
2.1 Product Overview .................................................................................................... 6
2.2 Contents of the Brake Board Kit. ............................................................................. 6
2.3 Connection of ECD Brake Board ............................................................................ 6
2.3.1 24VDC ............................................................................................................................ 6
2.3.2 BKSIGNAL ................................................................................................................... 7
2.3.3 AC SUPPLY .................................................................................................................. 7
2.3.4 VAC BRAKE ................................................................................................................ 7
2.3.5 NO NC C ........................................................................................................................ 7
2.3.6 SIN 1 ............................................................................................................................... 8
2.3.7 Brake Coil and Rectifier Connections ...................................................................... 9
2.4 Setup of Brake Board ............................................................................................. 10
2.4.1 Vmax Adjustment ...................................................................................................... 10
2.4.2 V1 Adjustment ........................................................................................................... 10
2.4.3 T1 .................................................................................................................................. 11
2.4.4 T2 .................................................................................................................................. 11
2.4.5 T3 .................................................................................................................................. 11
2.4.6 T4 .................................................................................................................................. 11
2.5 LED Sequence of Operation .................................................................................. 12
3. Specifications ........................................................................................................... 13
3.1. AC SUPPLY input voltage range ............................................................................. 13
3.2.1 VAC BRAKE output current capable ratings. .................................................... 13
3.3. 24VDC brake board power supply ........................................................................... 13
3.4. REL (NO NC C) contact ratings ............................................................................... 13
4 Example Connection ................................................................................................. 14

4
Section 1.1 Safety Regulations
Installation of this equipment shall be done in accordance with all applicable local
codes
Elevator controllers and other electrical components can cause serious harm or
death if installation guides are not met. It is the responsibility of the installer of our
equipment to ensure that once installed, the equipment does not pose any threat,
danger or hazard.
Section 1.2 Obligations & Liability
1.2.1 Following operating instructions.
In order to ensure safe handling and problem free operation of this
equipment, it is absolutely essential for the relevant personal to be fully
acquainted with the relevant safety regulations.
These operating instructions contain the most important information for
operating the equipment correctly and safely.
These operating instructions, in particular the safety regulations, must be
observed by all those persons who work on the equipment.
Furthermore, all locally applicable rules and regulations relating to accident
prevention and installation must be observed.
1.2.2 Obligations of operator.
The operator undertakes to allow only those persons to work on the equipment
who
Are fully acquainted with the basic regulations relating to safety in the
workplace and accident prevention and to have been trained in handling the
equipment.
Have read the safety regulations and the warning notices contained in these
the operating instructions.
1.2.3 Obligations of personnel.
All personnel charged with working on the machine undertake prior to starting
work to
Observe the basic regulations relating to safety in the workplace and
accident prevention.
Read the operating instructions, in particular the safety regulations, and
confirm by way of their signature that they have understood them.

5
1.2.4 Safety during normal operation.
Only operate the machine when all protective equipment is fully
operational.
Prior to switching on the machine, ensure that the startup can cause no
harm to personnel.
Regularly maintain and check machine for externally identifiable damage
and check that all the safety devices are operational.
1.2.5 Hazards caused by electric power.
Work on the electric power supply may only be carried out by a qualified
electrician.
Check the electrical equipment of the machine at regular intervals.
Repair loose connections and scorched cables immediately.
Keep the control cabinet locked at all times. Access is only permitted to
authorized personnel with a key or tool.
If work has to be carried out on live parts, do this only in the presence of a
second person who can switch off the master switch in an emergency.
The machine causes electromagnetic interference sources. For this reason,
do not use any sensitive equipment in its vicinity.

6
2.1 Product Overview
The brake board is specifically designed to control elevator machine brakes across a wide
range of voltages and loads. It may also be used to control door lock cams to ensure smooth
and quiet cam operation.
The following user adjustable parameters ensures smooth and quiet brake operation and
reduction of back EMF surges;
Brake lift time and voltage
Brake cooling time and voltage. (reduced holding voltage once brake has lifted)
Brake drop time
2.2 Contents of the Brake Board Kit.
1 brake board
1 ferrite core for 24VDC supply
1 1000v 35A bridge rectifier
4 crimp lugs for rectifier
1 power diode for brake coil back EMF protection
1 system manual
2.3 Connection of ECD Brake Board
Below is a list of the connection terminals on the brake board.
24VDC Brake board power supply
BKSIGNAL Brake lift input
AC SUPPLY Brake coil supply AC voltage only. Min 80VAC. Max 240VAC.
VAC BRAKE Brake coil connection
NO NC C Loss of AC output relay
SIN1 Spare input (not used)
For diagrams of the following terminals refer to see Section 4, Fig.7 & 8.
2.3.1 24VDC
The 24VDC input is the power supply to the microprocessor and as such should be as stable as
possible.
Supplied in the kit is a ferrite core that is to be installed on the 24Vdc supply. The wires for
this supply should be twisted together then looped once through the ferrite core (see fig.1).
Note this is particularly important if the board is being supplied from a switch mode power
supply.

7
Figure 1
2.3.2 BKSIGNAL
The BKSIGNAL input is the signal from the lift controller to initiate the brake lift sequence.
This input only requires a voltage free contact.
2.3.3 AC SUPPLY
The AC SUPPLY terminal is used for the AC voltage @ 50Hz for the brake board.
This voltage is regulated by the brake board and output from terminal VAC BRAKE to control
the brake
Important Note: This voltage cannot exceed 240Vac and must be @ 50Hz
2.3.4 VAC BRAKE
The VAC BRAKE terminal is the AC output from the Brake Board to the Brake coil.
As a DC voltage is required for most brake coils, use the supplied rectifier on this output.
2.3.5 NO NC C
The NO NC C relay contacts are used to signal to the lift controller that a fault has occurred
with the brake board, inhibiting any further lift operation. See example Section 4, Fig. 6 & 7,
where the relay C & NO contacts are used for the controller PRV (prove) input.
When the brake board is functioning normally, the fault relay will be energized.
When any of the faults listed below are detected the fault relay will drop out:
Loss of AC SUPPLY. “Loss of AC!” will be displayed on the LCD. (No AC voltage at
AC SUPPLY, Fig. 2). Brake board will remain inoperative until AC SUPPLY restored.

8
Figure 2
Loss of 24VDC
Triac shorted. “Triac damaged!” will be displayed on the LCD. (Fault detected with
Triac, Fig. 3).
This fault is a fatal error and requires a 24VDC reset. Note: If a triac fault is detected
while the brake board is operating, the brake board will finish the run and set the Triac
damaged fault when BK SIGNAL turns off.
Figure 3
The relay contacts are rated as follows:
Max Voltage: 125 VAC or 60VDC
Max Current: 0.5A
Note: This relay is not rated for use in the Safety Circuit of most elevator controllers. If the
intend use of relay C and NO contacts is to open the Safety Circuit then an appropriately rated
slave relay must be used.
2.3.6 SIN 1
This terminal is currently not used and no wires should be connected.

9
2.3.7 Brake Coil and Rectifier Connections
The wiring current rating from the VAC BRAKE output to the rectifier and brake should be
sized according to the load of the brake coil.
The supplied power diode shall to be connected reverse biased at the brake coil for back EMF
suppression.
+-
BRAKE
COIL
Figure 4

10
2.4 Setup of Brake Board
The Brake Board has 6 adjustable parameters which can be adjusted to optimize the operation of
the brake:
Vmax, V1, T1, T2, T3, T4.
T2 T3 T4
V1
Vmax
T1
Note: The graph show the sequence of operation from when BK SIGNAL is triggered
Figure 5
2.4.1 Vmax Adjustment
Vmax is used to set the maximum AC voltage output (VAC BRAKE) and is expressed as a
percentage value of the input voltage (AC SUPPLY)
Vmax is a code protected user adjustable setting. To adjust this setting, first go to LCK and set
to 6789.
E.g.1. Set to 50% if AC SUPPLY is 240VAC and you require 120VAC at VAC BRAKE.
E.g.2. Set to 100% if AC SUPPLY is 240VAC and you require 240VAC at VAC BRAKE.
The Brake Board is shipped with Vmax set at a default value of 35%. The minimum allowed
setting is 10% and the maximum setting is 100%.
After any adjustments to Vmax, it is recommended that LCK be changed to any value other
than 6789, so as to prevent an accidental vmax parameter change, which may cause an over
voltage supply to the brake coil.
2.4.2 V1 Adjustment
V1 is the holding voltage for the brake coil and is adjustable to a percentage of the input
voltage at the AC SUPPLY terminal; it is also interlocked to the Vmax setting so that it cannot
be set to a higher value than Vmax. The minimum allowed setting is 10% and the maximum
setting is 100% or Vmax whichever is the lesser.
The Brake Board is shipped with V1 set at a default value of 25%.
Once the lift is running this value can be adjusted either up or down to give the desired brake
hold voltage and thus cooling effect.

11
2.4.3 T1
This setting is used to control how fast the brake coil will get to full voltage (v max).
It is adjustable in steps of 50 ms.
The minimum allowed setting is 100ms and the maximum allowed setting is 5000 ms.
Default setting is 500ms.
2.4.4 T2
This setting is used to control how long the brake coil will stay at full voltage.
It is adjustable in steps of 50 ms.
The minimum allowed setting is 100ms and the maximum allowed setting is 5000 ms.
Default setting is 1500ms.
2.4.5 T3
This setting is used to control how fast the voltage will reduce to V1 level after the T2 time
expires.
It is adjustable in steps of 50 ms.
The minimum allowed setting is 100ms and the maximum allowed setting is 5000 ms.
Default setting is 500ms.
2.4.6 T4
This setting is used to set how fast the brake voltage will reduce to 0v after the BK SIGNAL is
switched off.
It is adjustable in steps of 50 ms.
The minimum allowed setting is 0ms and the maximum allowed setting is 3000 ms.
Default setting is 500ms.

12
2.5 LED Sequence of Operation
Fitted to the Brake Board are 3 LED’s which can be used to follow the sequence of operation
of the board. The LED’s are red, green and yellow.
During standby state both the red and yellow LED’s are illuminated.
During T1 operation only the red LED is illuminated.
During T2 operation only the green LED is illuminated.
During T3 operation the red and green LED’s are illuminated.
During T4 operation no LED is illuminated.
During V1 operation all LED’s are illuminated.
T2 T3 T4
V1
Vmax
T1
GREEN
LED
RED & GREEN LED
RED
LED RED,YELLOW,GREEN LED
ALL LED'S OFF
Figure 6
The graph shows the LED sequence of operation from when BK SIGNAL is triggered
Flashing yellow LED indicates the brake board is in the following fault state;
Loss of AC SUPPLY. “Loss of AC!” will be displayed on the LCD. (No AC voltage at
AC SUPPLY). Brake board will remain inoperative until AC SUPPLY restored.
Flashing red LED and illuminated yellow LED indicates the brake board is in the following
fault state:
Triac shorted. “Triac damaged!” will be displayed on the LCD. (Fault detected with
Triac). This fault is a fatal error and requires a 24VDC reset. Note: If a triac fault is
detected while the brake board is operating, the brake board will finish the run and set
the Triac damaged fault when BK SIGNAL turns off.

13
3. Specifications
3.1. AC SUPPLY input voltage range
80VAC – 240VAC @50Hz
For AC SUPPLY input voltage less than 80VAC contact ECD for resistor upgrade.
3.2.1 VAC BRAKE output current capable ratings.
Output current ratings reduce as V Max reduces.
Eg. (with 240VAC input);
10 Amps @ 120VAC (V max = 50%)
20 Amps @ 240VAC (V max = 100%)
(with 110VAC input);
10 Amps @ 55VAC (V max = 50%)
20 Amps @ 110VAC (V max = 100%)
3.3. 24VDC brake board power supply
24 VDC
3.4. REL (NO NC C) contact ratings
0.5 @ 60VDC/125VAC
3.5. Setting Values
Default:
Vmax 35%
V1 25%
T1, T3 & T4 500ms
T2 1500ms
Minimum
Vmax 10%
V1 10%
T1 to T3 100ms
T4 0ms
Maximum
Vmax 100%
V1 100%
T1 to T3 5000ms
T4 3000ms

14
4. Connection Example:
The diagrams below show an example of how the Brake Board may be connected
GRD
T1
N240V
10V 18V
TO MAIN
LIFT C/B
POWER CIRCUIT
100-174
100-174/1
15
A
C
B
D
G
123459
67810
OF
SHEET
Date
Control System
Drawing No:
Job No:
Drawn
APP
Rev:
SIGN:
DATE:
CHANGES
Revision:
A
B
C
E
F
L1 L2 L3
WVUPE
PE
OH
OH
KEB
COMBIVERT
Brake Resistor
Temp Sw.
++
-
PB
MOTOR 3
Isolate motor cables
from other wiring
C1
Interference
suppression filter.
L1 L2 L3 PE
2
1
4
3
6
5
440 VA
110V
c
C2
5
6
3
4
1
2
1999-2006
BRAKING
RESISTOR
C/B1 16A
N
R
S
T
OH1
OH2
SIS
SHAFT
INFORMATION
SYSTEM
0v 24v
C/B3 2A
WVU
TO SHEET 2
"10" G/1
Terminals on Circuit Boards
Field Terminals
Controller Terminals
X4
"See Inst. Man.
6.3.1 for Conns."
EN
30 31 32 33 34 35 shield
5v AABBGND
__
CAUTION: Ensure any
unused conductors
within encoder cables are
terminated or islolated.
100-174
CONTROLLER
0V 24V
10V 0V
BR1
-
+
F1 4A
Therm.
FAN
1
2
COL
CURTAIN
OF LIGHT
NE PH
C/B2 2A
KEB-1BrakeBoard-1SCHVF-PULSE BOARD
25-FEB-08
VF100 KEB
L2A
RCD
10 A
OPEN LIMIT
CLOSE LIMIT
SCHINDLER
VF DOOR OP
C/B5 6A
EARTH
5
6
7
4
3
2
1
1819
CBX
CBX
BR2
+
ECD BRAKE
BOARD
0V
24V
BK SIGNAL
SUPPLY(VAC)
BRAKE(VAC)
C2
14 13
C
NC NO
TO SHEET 2
E/10
IMPORTANT.
TWIST THE 24VDC SUPPLY
WIRES TOGETHER AND LOOP
ONCE AROUND THE SUPPLIED
FERRITE CORE
11 14
12
34
1000V 25A RECTIFIER
SUPPLIED BY ECD
C/B4 6A
1
2
4
3
C
CNO
NO
DO
DC
SP4
CNO
EDP
21 22 22
21
DOB
BK
X3.18 X3.19
KEB
CRAWL
SPEED
100-174
TO DFO
SHEET 5
0V
0V
TO DFC
SHEET 5
24V
0V
PULSE
A+ (5V)
GND
PULSE BOARD
TO SHHET 3
F/4
TO ENCODER 5V
POSITIVE CHANNEL
AND ENCODER GND
C/B6A
Figure 7

15
CAR DOOR
FRONT
LANDING LOCKS LANDING LOCKS
MSD MSD
MSU
LEV
DZ MSU
DN
DIR
LIMIT
UP
DIR
LIMIT
LR DZ
LR
SAF
LR
C
BRK-N/O
M2
N Neutral
M4
L2A
C N/O M1 M3
N Neutral
J29J6 J5
16
39 40 41
44
100-174
100-174
TOP OF CAR
INSPECTION
COMMON
INSP BOX
Terminals on Circuit Boards
Field Terminals
Controller Terminals
CONTROL CIRCUIT
100-174
100-174/2
2 5
A
C
B
D
G
1 2 3 4 5 96 7 8 10
OFSHEET
Date
Control System
Drawing No:
Job No:
Drawn
APP
Rev:
SIGN:DATE:CHANGES
Revision:
A
B
C
E
F
SAFETY
GEAR
SLACK
ROPE
C
46
C
0V
+24V
X3.15
X3.16
BK
A2
X3.20
X3.21
X3.3
X3.4
X3.5
N/ON/O N/O
47
Main cont.
control.
Braking
control.
C
DF UF SP3 SP1 SP2
N/O N/OC C C
DN UP
X2.1
X2.2
X3.1
BK
+24V
21 22
TO "C2-A1"
AREA D/9
TO "X3.21"
AREA C/5
C2
31 32
X3.9
X3.10
X2.23
X2.11
X3.11
X3.12
X3.17
Decel Control
PRV
1999-2007
0V
KEB COMBIVERT
C2
A2
X2.4
X2.3
C2
43 44
N/O N/OC C
LRX
c
BRK
C2
21 22
J18
PIT
LADDER
TOP
10
GOV
OVER
SPEED
STOP
BUTTON
IN CAR
D.O.T.
LIMIT
11 11/1 13
10/1
ETS
(if applies)
11 14
PIT
LADDER
BOTTOM
GOV
TENSION
WHEEL
12
U.O.T.
LIMIT
14
11 14
15
16/1
CAR DOOR
REAR
SRTD SG
TRAP
DOOR
MAINT. BOX
STOP
OT
21
24
A1
SPD
+24V
OT
(if applies)
NB. SPD relay and OT contacts
for lifts with ETS. (above 1.0 m/s)
(if applies-see NB)
A2
(if applies)
C1
A1
A2
X3.6
0V
1.2K 1W
0V
1.2K 1W
1.2K 1W
24v
TO SHEET 1
AREA D/6
SB
TR
TO SHEET 1
AREA D/6
KEB-BRAKEBOARD-1ECI
24-JULY-07
Positioning/Relevelling VE
Rated/Max. speed VN
Insp. speed VI
Control release
Reset
Cont. Control
+24V
+24V
+24V
GND
GND
GND
Forward
Reverse
Intermediate. speed V1
CBX
A1
A2
TO SHEET 1
B/6
BRAKE BOARD
BK. Use 2P
110vac relay
DDLR UDLR
DDLR UDLR
14 14
1111
A2 A2
A1 A1
Figure 8

16
E L E C T R O N I C C I R C U I T D E S I G N S P T Y . L T D .
Operation Guide
Electronic Circuit Designs Pty. Ltd.
Factory 11/30 Perry Street • Matraville • NSW • Australia • 2036
Phone 61 2 9316 6909 • Fax 61 2 9316 6797
Email sales@ecd.com.au Web www.ecd.com.au
Table of contents
Other ECD Controllers manuals