manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Ecoflam
  6. •
  7. Burner
  8. •
  9. Ecoflam Multicalor 300.1 User manual

Ecoflam Multicalor 300.1 User manual

techniques for energy saving
GASTEC
GAS / LIGHT-OIL DUAL BURNERS
LB1203
24.10.2003
Multicalor 300.1
Multicalor 400.1
Light oil / Natural gas 40÷300 mbar
MODEL
pag.2
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
TECHNICAL FEATURES : Multicalor 300.1 Multicalor 400.1
Max. thermal output kcal/h 2.586.000 3.362.000
kW 3.000 3.900
Min. thermal output kcal/h 543.100 754.300
kW 630 875
Max flow rate Nm3/h 301 392
Min flow rate Nm3//h 63 170
Natural gas supply pressure mbar 40÷300 40÷300
Max. light oil flow rate kg/h 253 329
Min. light oil flow rate kg/h 68 143
Voltage, 3phase + neutral, at 50 Hz V 230/400 230/400
Motor kW 5,5 7,5
Motor’s RPM N° 2800 2800
Fuels: Nat. Gas LHV = 35,9 Mj/Nm3 = 8.570 kcal/Nm3; Light Oil LHV = 10.200 kcal/kg max. 1,5° at 20 °C
mbar
1500 2000 2500 3000 3500 4000
10
12
14
16
1000
-2 kW
0
2
4
6
8
500
Multicalor
300.1 Multicalor
400.1
Multicalor
300.1 Multicalor
400.1
WORKING FIELDS
OVERALL DIMENSIONS
SUNTEC
SUNTEC
SUNTEC
I
M
L
ED - D1
F
G
C
B
A
H
0
12
0- STOP
1- GASOLIO
2- GAS
0
AUTO
MODEL A B C D D1 E F G H I L M
MULTICALOR 300.1 1351 453 898 328 528 755 290 466 280 315 315 M16
MULTICALOR 400.1 1351 453 898 363 563 755 320 466 280 315 315 M16
D = short head D1 = long head
Burner output
Backpressure in combustion chamber
pag.3
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
GAS TRAIN ASSEMBLY
1 . Main gas pipe
2 . Cut-off valve
3 . Antivibrating coupling
4 . gas rfilter
5 . Gas governor
6 . Safety gas valve
7 . Leakage control device
8 . Working gas valve
9 . Min. gas pressure switch
MODULAIR P 3000
MODULAIR P 4000
6
5312 478
9
To be supplied
by the installer
12 3 4 5
67
89
To be supplied by the installer 1 - main gas pipe
2 - ball valve
3 - antivibration coupling
4 - gas filter
5 - working gas valve
6 - actuator
7 - actuator
8 - leakage control
9 - gas pressure switch
12 34
56
78
5 - gas pressure switch
6 - safety gas valve
7 - leakage control
8 - working gas valve
1 - main gas pipe
2 - ball valve
3 - antivibration coupling
4 - governor
ELECTRICAL CONNECTIONS
All burner motors are tested at 400 V 3phase at 50 Hz, whilst auxiliaries are tested at 230V 1phase at 50 Hz.
Should it be necessary to power the burners at 230V/50Hz 3phase without neutral, carry out the necessary modifications accor-
ding to the burner’s wiring diagram, and check that the thermal relay is within the absorption field of the motor.
CONNECTION TO GAS PIPE
Once the burner has been connected to the gas supply, check that this last is perfectly sealed. Also verify that the chimney is not
clogged. Open the on-off valve and carefully bleed the piping through the pressure port, then check the pressure value through
a suitable pressure gauge. Turn on the system and adjust the thermostats to the needed temperature. When the thermostats
close, the leakage control device runs a valves leakage test, then enables the burner to start the ignition cycle.
OPERATION OF BURNER WITH GAS MULTICALOR 300.1-400.1
Before starting the burner, make sure it is mounted correctly. Then check connections are correct according to the diagram and
piping is appropriate to the system. Before connecting the burner to the electricity supply, make sure voltage corresponds to
burner plate data. The connection diagram and start-up cycle are shown separately. For wiring from control box to burner, see
the enclosed connection diagram. Pay particular attention to neutral and phase connections : never exchange them!. Vent air
and impurities of gas pipe. Check gas pressure conforms to the limits stated on the burner plate when connecting a master
gauge to the test port provided on the burner. Blower motor starts and pre-purging begins. Since pre-purging has to be carried
out with the max. air delivery, the burner control circuit turns the air damper to the max. delivery
position by the air servocontrol in approximately 30 seconds time. When the servocontrol is fully
open, a signal to the electronic control unit starts the 66 seconds pre-purge cycle. At the end of the
prepurging time, the air servocontrol gets to the Low Flame position so that burner ignition is ensu-
red at min. output. Simultaneously the ignition transformer receives voltage and after 3 seconds (pre-
ignition) opens the gas valve. Fuel flows to the combustion head and ignites, being governed by the
gas firing butterfly valve. Two seconds after gas valves have opened, the ignition transformer is excluded from the circuit. In
0
12
0 - STOP
1 - GASOLIO
2 - GAS
LIGHT-OIL
The control box starts the burner
fan, to carry out the prepurging of
the combustion chamber, and
cheks the vent air pressure through
the air pressure switch. At the end
of prepurging, the ignition tran-
sformer cuts-in and generates a
spark between the electrodes. At
the same time the two gas valves
open (Vs safety valve and Vl working valve). The total safety, in case of missed ignition or casual burner's flame-out,
is granted by a ionisation probe which cuts-in and sets the burner shutdown within the safety time. In case of gas
lack or a major pressure drop, the minimum air pressure switch shuts down the burner.
LANDIS & STAEFA, Model LFL1.622 OPERATING CYCLE
+
–
C
AIR EXCESS (%)
AIR FACTOR
THERMAL POWER (kW)
10 10 20 30 40 50 60
70
80
90
100 200 300 400
500
600
700
800
900
1000
1,1
1,15
1,2 1,2 1,2
1,25
1,3
15
20
25
30
2000 3000
5000
4000
6000
Natural Gas
CO29,6%
CO <100 ppm
Ref. Description
t1 Duration Waiting time for confirmation
t2 of air pressure
t3 Preventilation time
t4 Safety time
t5 Pressurizing time
Time for enabling operation of the
main gas valve on minimum capacity
t6 Time for enabling operation of the
main gas valve on maximum capacity
Duration
8”
66”
2”
4”
10”
10”
Rivelazione
di fiamma
Spia di blocco
Valvola gas
Serranda aria
Serranda gas
Trasformatore
di accensione
Pressostato aria
Motore ventilatore
Pressostato gas
0
min
100%
t1 t2
t4
t3
t6t5
Ciclo di funzionamento normale Ciclo di funzionamento
in mancanza di fiamma all'accensione
t1 t2
t4
t3
Consenso
min./max. potenza
Gas manostat
Fan motor
Air Switch
Ignition transformer
Gas valve
Min/max capacity
enabling device
Air damper
Gas damper
Flame detector
Cut-out pilot lamp
Normal operating cycle Operating cycle in the event of
ignition failureNormal operating cycle
ADJUSTING THE PRESSURE REGULATOR
The pressure regulator, complete with its incorporated filter, must be installed to avoid contaminants
reaching the gas valve. It is important to ensure certain conditions: The pressure of the gas must not
exceed the established maximum pressure. To increase the pressure of the gas supply, tighten screw
C; to reduce the pressure, loosen screw C. After making any adjustments, put the cap back in place.
CALCULATING THE BURNER CAPACITY
To calculate the burner's capacity in kW, proceed as follows: Check the gas flow rate (in liters)
on the counter and the time of the reading in seconds.
Proceed with the calculation using the following formula: x f = kW
e
sec
e=Litres gas
sec = Time in second
G20 = 34,02
G30 = 116
G31 = 88
f
pag.4
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
ADJUSTING THE COMBUSTION PROCESS
IMPORTANT: to obtain the right adjustment of the combustion and thermal capacity it is important to analyze the reducts of
combustion with the aid of suitable instruments. The combustion and thermal capacity adjustment is done simultaneously,
together with the analysis of the products of combustion, making sure that the measured values are suitable and that they com-
ply with current safety standards. On this matter, please refer to the table and figure below.
THESE OPERATIONS MUST BE DONE BY PROFESSIONALLY-QUALIFIED TECHNICIANS.
NOTE: ALL SAFETY DEVICES (AIR PRESSURE SWITCH, MINIMUM GAS PRESSURE SWITCH, GAS SOLENOID
VALVES AND GAS GOVERNOR) SHALL BE DULY SEALED AFTER CALIBRATION AND BURNER START UP BY
ECOFLAM’S TECHNICIANS.
case of no ignition the burner goes to lock-out within two seconds. Now the burner is operating at the min. firing rate (about
30% of the max. firing rate). The air servocontrol runs at the Low Flame position and in case the temperature control has to be
set at the max. output it goes to a fully open position of air damper and butterfly valve. During the burner-off periods the air
dumper closes up fully.
pag.5
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
ADJUSTMENT OF GAS SOLENOID VALVES
The ignition flow rate is carefully adjusted. during test phase to 1/3 of the maximum flow rate (according to specifications).
Operations for eventual further adjustment must be carried out by skilled personnel authorized by ECOFLAM.
DUNGS MVDLE
To adjustment gas output, loo-
sen the screw R and turn the
knob P as required. To reduce
output, turn knob clockwise,
to increase it turn knob coun-
terclockwise. Tighten the
screw R. For fast opening adju-
stment, remove the cap T and
insert it in the pin Q with its
groove up. To reduce firing
output screw it up, to increase,
unscrew it.
DUNGS MVD
To adjustment gas output, take
out the cap L and loose the nut
F.Adjust the screw E with a
screwdriver. To reduce output
turn counter clockwise, to increa-
se it turn clockwise.
Tighten the nut F.
+
-
B
The pressure regulator is inside to gas solenoid
valve (actuator SKP20). For adjustment the pres-
sure proceed as follows:
Take out the cap (A) and turn the screw (B) with
a screwdriver. To increase pressure, turn screw-
driver clockwise, to reduce it turn screwdriver
counterclockwise. Take in the cap (A).
ADJUSTMENT THE PRESSURE OF GAS SOLENOID VALVE (Landis SKP20)
DUNGS SV-DLE
To adjustment gas output, loosen the screw R and turn the knob P as required. To reduce output, turn knob clockwise,
to increase it turn knob counterclockwise. Tighten the screw R. For fast opening adjustment, remove the cap T and
insert it in the pin Q with its groove up. To reduce firing output screw it up, to increase, unscrew it.
R
QT
P
pag.6
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
ADJUSTMENT OF GAS MINIMUM PRESSURE SWITCH
Unscrew off and remove cover M. - Set regulator N to a value equal to 60% of gas nominal feed
pressure (i.e. for nat. gas nom. pressure = 20 mbar, set regulator to a value of 12 mbar; for
L.P.G. nom. pressure of G30/G31- 30/37 mbar, set regulator to a value of 18 mbar).Screw
up cover M
ADJUSTMENT OF THE AIR PRESSURE SWITCH
Unscrew screws A and B and remove cover C.- Set the pressure switch to the minimum by
turning regulator D to position 1.
- Start the burner and keep in low flame running, while checking that combustion is cor-
rect. Through a small cardboard, progressively obstruct the air intake until to obtain a
CO2 increase of 0,5÷0,8% or else, if a pressure gauge is available, connected to pressure
port E, until reaching a pressure drop of 1 mbar (10 mm of W.G.). - Slowly increase the
adjustment value of the air pressure switch until to have the burner lockout. Remove the
obstruction from the air intake, screw on the cover C and start the burner by pressing the
control box rearm button.
Note: The pressure measured at pressure port E must be within the limits of the pressure
switch working range. If not, loose the locking nut of screw F and gradually turn the same: clockwise
to reduce the pressure; counterclockwise to increase. At the end tighten the locking nut.
2,5
5
10
15
50
25
35
30
40
45
20
0,4
0,6
0,9
3,0
1,5
2,1
1,8
2,4
2,7
1,2
I
L
MN
A
B
CD
E
F
GH
gas pressure
switch
air pressure switch
LEAKAGE CONTROL DEVICE DUNGS VPS 504-VDK 200
When the thermostats are closed, the gas leakage control device checks the valve seals by pressurizing the circuit between the
two gas valves. When test pressure is reached the device remains in stand-by for about 25 seconds. At the end of the test the yel-
low pilot light on the control device lights up and the burner is enabled to carry out the start-up cycle. If the seal on one of the
valves is faulty and this causes a drop in test pressure, the device puts the system into the safety condition and the red pilot right
on the device lights up. The flame control device starts the burner fan to carry out prewashing of the
combustion chamber,checking fan air pressure via the air pressure switch. After preventilation the igni-
tion transformer starts operating, generating a spark between the electrodes and simultaneously the gas
valves open (safety gas valve VS and first stage operating valve VL). If the flame does not ignite or goes
out, total safety is ensured by an ionization detection probe. The safety time limit in the event of no
flame is less than 2 seconds at start-up and less than 1 during operation. In the event of no gas being
supplied or of a considerable drop in pressure the minimum gas pressure switch interrupts burner operation. About 20/30
seconds after ignition the flame control device commands operation of the second stage via the gas valve and air servocontrol,
thus taking the burner to maximum power.
VLVS
DISPOSITIVO
CONTROLLO
TENUTA
LANDIS & STAEFA SQM 50.381A2 AIR DAMPER MOTOR
Remove cover to gain access to the adjusting cams.The cams are to be adjusted through the suitable key provided
for. Description:
I-High flame operating opening position adjusting cam (Light-Oil /Gas)
II -Ignition flame opening position adjusting cam (Gas).
III -Low flame operating opening position adjusting cam (Gas)
IV -Low flame operating opening position adjusting cam ( Light-Oil)
V-2nd flame solenoid valve opening On/Off cam (Light-Oil)
VI -Not used cam
VII -Not used cam
VIII -Not used cam
Multicalor 300.1
Cam VIII
is never used
LEAKAGE
CONTROL
DEVICE
I - High flame operating opening position adjusting air cam
II - Ignition flame opening position adjusting air cam (Gas/Light-Oil)
III - Low flame operating opening position adjusting cam (Gas)
IV - Low flame operating opening position adjusting cam (Light-Oil)
(always 3° lesser than Low flame adjusting V cam)
V - Low flame operating opening position adjusting air cam (Light-Oil)
VI - Low flame solenoid valve opening On/Off cam (Light-Oil)
VII - High flame solenoid valve opening On/Off cam (Light-Oil)
VIII -Not used cam
Multicalor 400.1
pag.7
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
AIR ADJUSTMENT
+
--
Part. 1
Part. 2
Part. 3
-
+
-
COMMUTATORE
0
AUTO
0 =
bloccaggio degli apparati per il
funzionamento in una posizione intermadia
=
funzionamento alla massima potenza
=
funzionamento alla minima potenza
AUTO =
funzionamento automatico
operating elements locked in an intermediate
position
operation on maximum capacity
operation on minimum capacity
automatic operation
SELECTOR
ADJUSTING THE MINIMUM CAPACITY OF THE BURNER – AIR and GAS
Position the selector placed on the control panel on position 2 and proceed as follows:
Adjust the minimum gas flow rate using a suitable wrench, turn the butterfly valve until you reach the correct gas
flow, as established by analyzing the combustion process.
ADJUSTING THE MAXIMUM CAPACITY OF THE GAS
Position the selector, situated on the control panel, on position 1 and proceed as follows:
Adjusting the maximum gas flow rate (see figure on solenoid valve adjustments) or adjust the gas pressure in the
governor.
ADJUSTING THE MAXIMUM AIR FLOW RATE
Adjusting the maximum air flow rate (see figure, detail 2). Loosen the nut holding the air damper transmission rod;
The correct air flow as established by analyzing the combustion process.
ADJUSTING THE INTERMEDIATE BURNER CAPACITY
Using the selector, start the servomotor (closing or opening) and position on 0 to stop the stroke; the adjustment is
made as outlined below. Repeat the operation for the other cam points.
Adjustment the intermediate gas flow rates (see figure, detail 3): - using a suitable Allen wrench, change the position
of the cam guide blade; if you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.
22 23
LANDIS
LFL 1.622
Fotocellula
min 70 µA
Mi
croamperometro
fondo scala 1000 µA
FLAME DETECTION SYSTEM CHECK
PHOTORESISTOR
Microamperometer
full scale 1000 µA
pag.8
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
REMOVING THE BLAST TUBE REMOVING THE FIRING HEAD
FIRING HEAD SETTING
+
-
pag.9
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
HYDRAULIC CIRCUIT
VS
V2
V1
4
5
V3
VS
V2
V1
4
5
1
1
23
1- HOSE
2- OIL FILTER
3- OIL COCK
4- SUCTION
5- RETURN
OPERATION OF BURNER WITH LIGHT-OIL FUEL MULTICALOR 300.1-400.1
Once installed the burner, check the following items:
- The burner power feeding and the main line protection fuses
- The correct length of pipes and that the same are sealed.
- The type of fuel, which must be suitable for burner.
- The connection of boiler’s thermostats and all the safeties.
- The motor rotation direction.
- The correct calibration of the motor’s thermal protection.
When all the above mentioned conditions are checked and accomplished, it is possible to go on with burner’s tests. Power the
burner. The control box feeds the ignition transformer and the burner’s motor at the same time, which will run a prepurging of
the combustion chamber. At the end of prepurging, the control box powers up the ignition transformer and opens the light-oil
valve, so the burner start . the servomotor will set up to the light-oil ignition position, whilst the control box powers up the
ignition transformer and the “Safety” and “Low flame” solenoid valves. After a safety interval of 2 seconds and a correct igni-
tion, the control box turns off the ignition transformer and, 10 seconds later, sets the motorised air damper to its maximum
opening and opens the 2nd stage solenoid valve (Multicalor 300.1) and 3rd stage solenoid valve (Multicalor 400.1). In case of
faulty ignition,the control box will shut down the burner in 2 sec.
In order to obtain a correct combustion, it shall be necessary to adjust the Low and High flame by following the instructions of
the Air servomotor and firing head adjustment.
During such a phase, it will be possible to manually switch between HIGH and LOW flame and viceversa, through the
High/Low flame switch. At the end of the adjusting phase, leave the switch in position “AUTO”. The fuel pump feeding pres-
sure, must remain around 12 bar.
0
12
0 - STOP
1 - GASOLIO
2 - GAS
Multicalor 300.1
Multicalor 400.1
LIGHT-OIL
pag.10
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
VERIFY:
- That piping system is perfectly sealed;
- That the use of hoses is avoided whenever is possible (use copper pipes preferably);
- That depression is not greater than 0,45 bar, to avoid pump’s cavitation;
- That check valve is suitably designed for the duty;
The pump pressure is set at a value of 12 bar during the testing of burners. Before starting the burner, bleed the air in the pump
through the gauge port. Fill the piping with light-oil to facilitate the pump priming. Start the burner and check the pump fee-
ding pressure. In case the pump priming does not take place during the first prepurging, with a consequent, subsequent lock-
out of the burner, rearm the burner’s lock-out to restart, by pushing the button on the control box. If, after a successful pump
priming, the burner locks-out after the prepurging, due to a fuel pressure drop in the pump, rearm the burner’s lock-out to
restart the burner. Do never allow the pump working without oil for more than three minutes. Note: before starting the burner,
check that the return pipe is open. An eventual obstruction could damage the pump sealing device.
PRIMING AND ADJUSTMENT OF OIL PUMP
1
2
5
6
3
4
1- INLET
2- RETURN
3- BLEED AND PRESSURE GAUGE PORT
4- VACUUM GAUGE PORT
5- PRESSURE ADJUSTMENT
6- TO NOZZLE
SUNTEC TA3C40105
6
53
2
SUNTEC
14
SUNTEC J7CCC10014P
NOZZLE PUMP PRESSURE (bar)
GPH 10 11 12 13 14 15 16
2,50 9,50 9,97 10,41 10,83 11,24 11,64 12,02
3,00 11,40 11,96 12,49 13,00 13,49 13,96 14,42
3,50 13,30 13,95 14,57 15,17 15,74 16,29 16,83
4,00 15,20 15,94 16,65 17,33 17,99 18,62 19,23
4,50 17,10 17,94 18,73 19,50 20,24 20,95 21,63
5,00 19,00 19,93 20,82 21,67 22,48 23,27 24,04
5,50 20,90 21,92 22,90 23,83 24,73 25,60 26,44
6,00 22,80 23,92 24,98 26,00 26,98 27,93 28,84
6,50 23,70 25,91 27,06 28,17 29,23 30,26 31,25
7,00 26,60 27,90 29,14 30,33 31,48 32,58 33,65
7,50 28,50 29,90 31,22 32,50 33,73 34,91 36,05
8,30 31,54 33,08 34,55 35,97 37,32 38,63 39,90
9,50 36,10 37,87 39,55 41,17 42,72 44,22 45,67
10,50 40,06 41,73 43,74 45,41 47,20 48,90 50,50
12,00 45,60 47,80 50,00 52,00 54,00 55,90 57,70
13,80 52,40 55,00 57,50 59,80 62,10 64,20 66,30
15,30 58,10 61,00 63,70 66,30 68,80 71,10 73,60
17,50 66,50 69,80 72,90 75,80 78,70 81,50 84,10
19,50 74,10 77,70 81,20 84,50 87,70 90,80 93,70
21,50 81,70 85,70 89,50 93,20 96,70 100,10 103,40
24,00 91,20 95,70 99,90 104,00 107,90 111,70 115,40
28,00 106,40 111,60 116,60 121,30 125,90 130,30 134,60
30,00 114,00 119,60 124,90 130,00 134,90 139,60 144,20
GPH OUTPUT kg/h
NOZZLE FLOW RATE (DELAVAN B - MONARCH PLP)
pag.11
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
3 ÷ 4 mm
5 ÷ 6 mm
3 ÷ 4 mm
5÷6 mm
POSITION OF IGNITION ELECTRODES
NOZZLE CLEANING AND REPLACEMENT
Use only the suitable box wrench provided for this operation to remove the nozzle, taking care to not
damage the electrodes. Fit the new nozzle with the same care.
Note: Always check the position of electrodes after having replaced the nozzle (see illustration). A wrong
position could cause ignition troubles.
A - pulsante di sblocco
B - operating lamps (orange=light-oil; green= gas)
C - Selector switch:
O = Loking of devoices for operating at intermediate outputs
= Operation at max. output
= Operation at min. output
AUTO= Automatic operation
D - ON/OFF switch
E - Fuse holder
F - Selector:
0 = STOP
1 = Light-oil operation
2 = Gas operation
A
B
C
D
E
0
12
0 - STOP
1 - GASOLIO
2 - GAS
0
AUTO
F
DESCRIPTION OF CONTROL PANEL
Multicalor 300.1
Multicalor 400.1
pag.12
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
MAINTENANCE
YEARLY CHECKS
The burner’s periodical check (firing head, electrodes etc.) must be carried out by authorised personnel one or two times per
year, depending on the utilisation. Before going on with the maintenance controls of the burner, it should be advisable to check
its general conditions, according to the following steps:
Unplug the burner; close the fuel cock; shut down the gas supply; remove burner’s cover and clean the fan and air intake; clean
the firing head and check the electrode’s position; reassemble all the parts; check the connection’s sealing; check the chimney;
start the burner and check the combustion flue (CO2 = 9.5 ÷ 9.8; O = lower than 75 ppm).
BEFORE EVERY INTERVENTION CHECK:
The electric system is duly powered and the burner is plugged in.
The gas pressure must be the suitable one and the gas cock open.
The control devices must be properly connected.
When all the above conditions are met, start the burner by pressing the lockout enable pushbutton.
Check the burner’s cycle.
THE BURNER DOES NOT START:
Check the ON/OFF switch, the thermostats, the motor and the gas pressure.
The master switch is in position “0”. Fuses are blown out.
The control box is faulty.
THE BURNER RUNS THE PREPURGING AND SWITCHES TO LOCKOUT AT THE END OF CYCLE:
Check the fan and the air pressure.
Check the air pressure switch.
Control box faulty. Ignition transformer faulty.
Check the ignition cable. Electrodes are dirty or in wrong position.
Nozzles are clogged or worn. Filters are clogged. Light-oil pressure is too low.
Combustion air’s flow rate too high related to nozzle output.
THE BURNER RUNS THE PREPURGING BUT DOES NOT IGNITE:
Check the position of the electrodes; check the ignition cable;
Check the ignition transformer;
Check the control box.
THE BURNERS IGNITES BUT SWITCHES TO LOCKOUT AFTER THE SAFETY TIME:
Check phase and neutral for a correct connection.
Check gas solenoid valve.
Check the position of ionisation probe and its connection.
Check the control box.
Check nozzles (clogged or worn).
The photoresistor does not detect the flame.
The filters are clogged. Light-oil pressure too low.
Combustion air’s flow rate too high related to nozzle output.
THE BURNERS IGNITES BUT SWITCHES TO LOCKOUT AFTER FEW MOMENTS:
Check gas governor and gas filter.
Check gas pressure through a manometer.
Check ionization value (min. 70 µA).
THE BURNER DOES NOT SWITCHES TO HIGH (OR 3RD) FLAME:
Manual selector switch in wrong position.
Faulty control box. High (3rd) flame solenoid valve’s coils faulty. High (3rd) flame’s nozzle clogged.
Air damper’s jacket faulty or wrongly adjusted.
pag.13
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
Multicalor 300.1 - 400.1
7
8
36
11
38
14
4
6
5
3
910
41
26
31
29
30
27
34
32
33
35
28
42
43
37
21
13 12
25 24
22
23
19
20
17
16
15
18
25 24
1
46
45
44
40 239
47
46
49
56
57
53
54
48 52
51
50
55
58
245
44
39
DUNGS DMV-DLE
LANDIS VGD
SKP10
SKP20
44
pag.14
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
Multicalor 300.1 Multicalor 400.1
N° DESCRIPTION Natural gas 50 mbar code code
1-AIR PRESSURE SWITCH DUNGS LGW10 A2P Q120 Q120
2-GAS PRESSURE SWITCH MIN. DUNGS GW 50 A4 Q107 -
DUNGS GW 50 A5 - Q107/3
3-AIR INTAKE SET GRPA100 GRPA100
4 - COVER BFC09254/038
5-GLASS BFC02004 BFC02004
6-PEED WINDOM FRAME BFC02006 BFC02006
7-MOTOR 5,5 k W M128/017 -
7,5 k W - M129/017
8-FAN 320 x 150 BFV10304/001 BFV10304/001
9-AIR CONVEYOR BFC08256/001 BFC08256/001
10 - AIR INTAKE GRCA320 GRCA320
11 - AIR INTAKE PIPE BFS02208/201 BFS02208/201
12 - CONTROL BOX BASE LANDIS A401 A401
13 - CONTROL BOX LANDIS LFL1.622 A113 A113
14 - IGNITION TRANSFORMER BRAHMA T8 T101 T101
15 - REMOTE CONTROL SWITCH BF40.00 R616 R616
16 - REMOTE CONTROL SWITCH (PUMP) MC9.10 R603/1 R603/1
17 - MOTOR THERMAL RELAY Lovato RF25 14-23A - R513/1
18 - MOTOR THERMAL RELAY (PUMP) Lovato RF9 1,4-2,3 A R510 R510
19 - MAIN SWITCH cod.40100I1509 R1020 R1020
20 - GAS/LIGHT-OIL SELECTOR R1020/5 R1020/5
21 - SELECTOR R1020/5
22 - LAMP Elettrospring EL/N-SC4 E1510 E1510
23 - FUSE SUPPORT FUSIT FH-B528 E802/2 E802/2
24 - RELÉ BASE Finder 5532 R905 R905
Finder 5534 R906 R906
25 - RELÉ Finder 5532 R711 R711
Finder 5534 R712 R712
26 - UV CELL LANDIS QRA 2 A205 A205
27 - IGNITION CABLE SHORT HEAD BFE01403/2
LONG HEAD
28 - IGNITION ELECTRODES SET E625 E625
29 - PIPE SHORT HEAD
LONG HEAD
30 - ROD SHORT HEAD
LONG HEAD
31 - FIRING HEAD
32 - FRONT DISC
33 - NOZZLE HOLDER
34 - INNER ASSEMBLY SHORT HEAD
LONG HEAD
35 - BLAST TUBE SHORT HEAD BFB07023/103 BFB07026/103
LONG HEAD BFB07023/203 BFB07026/203
36 - GASKET ISOMART BFG04051/1 BFG04051/1
37 - ANTIJAMMING FILTER S132/4 S132/4
38 - AIR DAMPER MOTOR LANDIS SQM50.381A2 M212/9 M212/9
39 - LEAKAGE CONTROL VPS 504 S02 V185 V185
40 - GAS FILTER FSDR50/CE S505/2 -
FSDR65/CE - S513/6
41 - SILENCER GRSIL04/01 GRSIL04/01
42 - WIELAND PLUG 7 pin E225 -
6 pin - E226
43 - WIELAND SOCKET 7 pin E225/1 -
6 pin - E226/1
44 - GAS VALVE DUNGS MVD 215 V117 -
DUNGS SV 520 - V1994/6
LANDIS VGD40.080 - V190/01
45 - COIL DUNGS MVD 215 -
DUNGS SV 520 -
Landis SKP 10.110B27 - V190/91
Landis SKP 20.110B27 - V190/8
46 - GAS VALVE DUNGS MVDLE 215 V118 -
DUNGS SV-DLE 520 - V1994/61
pag.15
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
47 - COIL DUNGS MVDLE 215
DUNGS SV-DLE 520 -
48 - OIL PUMP SUNTEC J7CCC10014P P103/1 -
SUNTEC TA2C40105 - P148
49 - COUPLING MP501/4 MP503
50 - PUMP MOTOR 740 W M147 M147
51 - OIL VALVE Parker SCEM VE 140 V175/1 V175/1
52 - COIL Parker SCEM VE 140
53 - OIL VALVE DELTA 1/8 F.F.F84 V420 V420
54 - COIL DELTA 1/8 F.F.F84
55 - OIL FILTER 1 X1 7010 1 S103 -
1 X1 03 - S107/5
56 - GAS VALVE BRAHMA E6GSRP V109 -
BRAHMA EG12SR - V142/1
57 - COIL BRAHMA V209 V209
58 - FAN SCOOP - BFC08059/001
Multicalor 300.1 Multicalor 400.1
N° DESCRIPTION Natural gas 50 mbar code code
pag.16
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
Multicalor 300.1 Multicalor 400.1
N° DESCRIPTION Natural gas 300 mbar code code
1-AIR PRESSURE SWITCH DUNGS LGW10 A2P Q120 Q120
2-GAS PRESSURE SWITCH MIN. DUNGS GW 50 A4 Q107 -
DUNGS GW 50 A5 - Q107/3
3-AIR INTAKE SET GRPA100 GRPA100
4 - COVER BFC09254/038
5-GLASS BFC02004 BFC02004
6-PEED WINDOM FRAME BFC02006 BFC02006
7-MOTOR 5,5 k W M128/017 -
7,5 k W - M129/017
8-FAN 320 x 150 BFV10304/001 BFV10304/001
9-AIR CONVEYOR BFC08256/001 BFC08256/001
10 - AIR INTAKE GRCA320 GRCA320
11 - AIR INTAKE PIPE BFS02208/201 BFS02208/201
12 - CONTROL BOX BASE LANDIS A401 A401
13 - CONTROL BOX LANDIS LFL1.622 A113 A113
14 - IGNITION TRANSFORMER BRAHMA T8 T101 T101
15 - REMOTE CONTROL SWITCH BF40.00 R616 R616
16 - REMOTE CONTROL SWITCH (PUMP) MC9.10 R603/1 R603/1
17 - MOTOR THERMAL RELAY Lovato RF25 14-23A - R513/1
18 - MOTOR THERMAL RELAY (PUMP) Lovato RF9 1,4-2,3 A R510 R510
19 - MAIN SWITCH cod.40100I1509 R1020 R1020
20 - GAS/LIGHT-OIL SELECTOR R1020/5 R1020/5
21 - SELECTOR R1020/5
22 - LAMP Elettrospring EL/N-SC4 E1510 E1510
23 - FUSE SUPPORT FUSIT FH-B528 E802/2 E802/2
24 - RELÉ BASE Finder 5532 R905 R905
Finder 5534 R906 R906
25 - RELÉ Finder 5532 R711 R711
Finder 5534 R712 R712
26 - UV CELL LANDIS QRA 2 A205 A205
27 - IGNITION CABLE SHORT HEAD BFE01403/2
LONG HEAD
28 - IGNITION ELECTRODES SET E625 E625
29 - PIPE SHORT HEAD
LONG HEAD
30 - ROD SHORT HEAD
LONG HEAD
31 - FIRING HEAD
32 - FRONT DISC
33 - NOZZLE HOLDER
34 - INNER ASSEMBLY SHORT HEAD
LONG HEAD
35 - BLAST TUBE SHORT HEAD BFB07023/103 BFB07026/103
LONG HEAD BFB07023/203 BFB07026/203
36 - GASKET ISOMART BFG04051/1
37 - ANTIJAMMING FILTER S132/4 S132/4
38 - AIR DAMPER MOTOR LANDIS SQM50.381A2 M212/9 M212/9
39 - LEAKAGE CONTROL VPS 504 S02 V185
40 - GAS FILTER FSDR50/CE S505/2 -
FSDR65/CE - S513/6
41 - SILENCER GRSIL04/01 GRSIL04/01
42 - WIELAND PLUG 7 pin E225 -
6 pin - E226
43 - WIELAND SOCKET 7 pin E225/1 -
6 pin - E226/1
44 - GAS VALVE DUNGS MVD 215 V117 -
DUNGS SV 520 - V1994/6
45 - COIL DUNGS MVD 215 -
DUNGS SV 520 -
46 - GAS VALVE DUNGS MVDLE 215 V118 -
DUNGS SV-DLE 520 - V1994/61
47 - COIL DUNGS MVDLE 215
DUNGS SV-DLE 520 -
48 - OIL PUMP SUNTEC J7CCC10014P P103/1 -
pag.17
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
SUNTEC TA2C40105 - P148
49 - COUPLING MP501/4 MP501/4
50 - PUMP MOTOR 740 W M147 M147
51 - OIL VALVE Parker SCEM VE 140 V175/1 V175/1
52 - COIL Parker SCEM VE 140
53 - OIL VALVE DELTA 1/8 F.F.F84 V420 V420
54 - COIL DELTA 1/8 F.F.F84
55 - OIL FILTER 1 X1 7010 1 S103 -
1 X1 03 - S107/5
56 - GAS VALVE BRAHMA E6GSRP V109 -
BRAHMA EG12SR - V142/1
57 - COIL BRAHMA V209 V209
58 - FAN SCOOP - BFC08059/001
Multicalor 300.1 Multicalor 400.1
N° DESCRIPTION Natural gas 300 mbar code code
pag.18
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
TP
3
M
3
M
LINE
LOAD
TP
TP
-
+
N
NL1
L1
S3T2T1 B4
S3T2T1 B4
S.p.A.
00 01 02 03 04 05 06 07 08 09
A
00 01 02 03 04 05 06 07 08 09
B
C
D
E
A
B
C
D
E
IND.MODIFICA
SOST.DA
SOST.IL
IND.MOD.
PROPRIETA' RISERVATA DELLA DITTA ECOFLAM S.p.A.
DATA-FIRMA
DATA
FIRMA
CONTROLLATO
DESCRIZIONE MODIFICA
DISEGNATO
DATA
FIRMA
COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE.A TERMINE DI LEGGE E' VIETATO RIPRODURRE O
CONTROLLO DI TENUTAAPPARECCHIATURA
UFF.TECNICO-SETTORE ELETTRICO
DENOMINAZIONE
SIST. RIVELAZ. CODICE
MOTORIDUTTORE
1821
LANDIS LFL 1.622
1043 65 87 9 141211 13 1615 17 32222019 21 2423 31
PAGINA DI
BEM43.103
MULTICALOR 300 2 FIAMME
LANDIS SQM 50.381A2
LANDIS LFL 1.622 DUNGS VPS 504 UV
30-10-2002
BEM43086
30-10-2002
50 Hz 380V
6SR 5T N 1097 8 11
HLB STAB
P
T
STC
P
T
STS
MP
UVW
FMP
MV
UVW
FMV
KMP
RSTNO
KMV
RSTNO
FU
SAL
Z
FMP
95
96
SAMA
12 30
FMV
95
96
SPA
SPGmin
HLG HLg
YVg1 YVg2YVgS
pos 1: ALTA FIAMMA/HIGH FLAME/2meALLURE/ALTA LLAMA
pos 3: AUTOMATICO/AUTOMATIC/AUTOMATIQUE/AUTOMATICO
INTERRRUPTEUR 2me-1re ALLURE
pos 2: BASSA FIAMMA/LOW FLAME/1re ALLURE/BAJA LLAMA
CONMUTADOR ALTA-BAJA LLAMA
SWITCH HIGH-LOW FLAME
COMMUTATORE ALTA-BASSA FIAMMA
T
PE
S
R
SAMA
12 3
0
24
TV
UV
KA1
12N 11 1 21 222 313 1423 4
KA2
16515 25 266 17 277
LANDIS SQM 50.381A2
M
1
1/2
pos 2:GAS
pos 1:GASOLIO
KA3
YVG1 YVGS
SAgG
12 30
N
DUNGS VPS 504
T7T8 B5T6
BROWN
BLUE
YELLOW-GREEN
L1
BLACK
YVGP
PER COLLEGAMENTO IN 220V TRIFASE
BORNE N DE LA CAJA DE BORNES
PARA CONEXION EN 220V TRIFASICA
MODIFICAR LAS CONEXIONES DEL MOTOR
Y ALEJAR EL CABLE DEL BORNE N AL
A LA BORNE N DE LA BOITE A BORNES
POUR CONNEXION EN 220V TRIPHASE
MODIFIER LES CONNEXIONS DU MOTEUR
ET DE PLACER LE CABLE DE LA BORNES
TO TERMINALT OF THE TERMINAL STRIP
FOR 220V THREE PHASE CONNECTION
CHANGE THE CONNECTIONS OF THE MOTOR
AND MOVE THE WIRE OF TERMINAL N
CAMBIARE I COLLEGAMENTI DEL MOTORE
E SPOSTARE IL FILO DAL MORSETTO N
AL MORSETTO T DELLA MORSETTIERA
Q
N
FMV
97
98
HLBT
pag.19
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
PAGINA DI
Q INTERRUTTORE GENERALE CON FUSIBILE
Z FILTRO ANTIDISTURBO
FU FUSIBILE
MP MOTORE POMPA
MV MOTORE VENTILATORE
TV TRASFORMATORE
UV FOTOCELLULA
FMP RELE' TERMICO MOTORE POMPA
FMV RELE' TERMICO MOTORE VENTILATORE
HLB LAMPADA DI BLOCCO
HLG LAMPADA GAS
HLg LAMPADA GASOLIO
KA1 RELE'
KA2 RELE'
KA3 RELE'
GAS LAMP
LAMPE DE GAZ
ESPIA GAS
OIL LAMP
TEMOIN MAZOUT
ESPIA GASOLEO
MOTOR PUMP THERMAL RELAY
RELAIS THERMIQUE MOTEUR POMPE
RELE' TERMICO MOTOR BOMBA
MOTOR THERMAL RELAY (FAN MOTOR)
RELAIS THERMIQUE MOTEUR VENTILATEUR
RELE' TERMICO MOTOR VENTILADOR
LOCK-OUT LAMP
LAMPE DE SECURITE
ESPIA DE BLOQUEO
IGNITION TRANSFORMER
TRANSFORMATEUR D'ALLUMAGE
TRANSFORMADOR
UV CELL
CELLULE UV
FOTOCELULA
MOTOR FAN
MUTEUR VENTILATEUR
MOTOR VENTILADOR
MAIN SWITCH WITH FUSE
INTERRUPTEUR GENERAL AVEC FUSIBLE
INTERRUPTOR GENERAL CON FUSIBLE
FUSE
FUSIBLE
FUSIBLE
OIL PUMP MOTOR
MOTEUR POMPE
MOTOR BOMBA
ANTJAMMING FILTER
FILTRE ANTIPARASITES
FILTRO DE PROTECION ANTIDISTURBIO
RELAY
RELAIS
RELE'
RELAY
RELAIS
RELE'
RELAY
RELAIS
RELE'
STAB TERMOSTATO DI ALTA-BASSA FIAMMA
ELECTROVANNE MAZOUT DE SECURITE
ELECTROVALVULA DE GASOLEO DE SEGURIDAD
ELETTROVALVOLA GASOLIO DI PRIMA FIAMMA
ELETTROVALVOLA GASOLIO DI SECONDA FIAMMA
SECOND STAGE OIL SOLENOID VALVE
ELECTROVANNE MAZOUT GRANDE ALLURE
ELECTROVALVULA DE GASOLEO 2^ LLAMA
ELETTROVALVOLA GAS PILOTA
PILOT FLAME SOLENOID GAS VALVE
ELECTROVANNE GAZ PILOTE
ELECTROVALVULA GAS PILOTO
EXTRA SAFETY GAS SOLENOID VALVE
ELECTROVANNE GAZ DE SECURITE
ELECTROVALVULA GAS DE SEGURIDAD
ELETTROVALVOLA GAS DI SICUREZZA
EXTRA SAFETY OIL SOLENOID VALVE
ELETTROVALVOLA GASOLIO DI SICUREZZAYVgS
YVGS
YVGP
HIGH-LOW FLAME THERMOSTAT
THERMOSTAT GRANDE-PETIRE ALLURE
TERMOSTATO DE ALTA-BAJA LLAMA
ELETTROVALVOLA GAS DI PRIMA FIAMMA
FIRST STAGE GAS SOLENOID VALVE
ELECTROVANNE GAZ PETITE ALLURE
ELECTROVALVULA GAS DE 1^ LLAMA
FIRST STAGE OIL SOLENOID VALVE
ELECTROVANNE MAZOUT PETITE ALLURE
ELECTROVALVULA DE GASOLEO 1^ LLAMA
YVg2
YVg1
YVG1
TELERRUPTOR MOTOR VENTILATOR
CONMUTADOR GASOLEO-GAS
INTERRUPTEUR MAZOUT-GAS
COMMUTATORE GASOLIO-GAS
INTERRUPTEUR MANUEL-AUTOMATIQUE
SWITCH (MANUAL-AUTOMATIC))
COMMUTATORE MANUALE-AUTOMATICO
TERMOSTATO DE SEGURIDAD
THERMOSTAT DE SECURITE
TERMOSTATO DI SICUREZZA
SWITCH (OIL-GAS)
SAFETY THERMOSTAT
CONMUTADOR MANUAL-AUTOMATICO
SAMA
SAgG
STS
INTERRUPTEUR DE LIGNE
BOILER THERMOSTAT
TERMOSTATO CALDAIA
PRESOSTATO AIRE
PRESSOSTAT AIR
AIR PRESSURE SWITCH
PRESSOSTATO ARIA
INTERRUPTOR DE LINEA
WORKING SWITCH
INTERRUTTORE DI LINEA
TERMOSTATO CALDERA
THERMOSTAT CHAUDIERE
STC
SPA
SAL
CONTATTORE MOTORE VENTILATORE
CONTACTEUR MOTEUR VENTILATEUR
REMOTE CONTROL SWITCH (FAN MOTOR)
KMV
PRESOSTATO GAS DE MINIMA POT.
SPGmin
PRESSOSTAT GAZ PRESSION MIN
GAS PRESSURE SWITCH MIN
PRESSOSTATO GAS DI MINIMA
POMP REMOTE CONTROL SWITCH
KMP CONTATTORE MOTORE POMPA
CONTACTEUR MOTEUR POMPE
EMPALME MOTOR BOMBA
LAMPADA DI BLOCCO TERMICOHLBT
THERMAL LOCK-OUT LAMP
LAMPE DE THERMAL DE SECURITE
ESPIA DE BLOQUEO RELE TERMICO
00 01 02 03 04 05 06 07 08 09
A
00 01 02 03 04 05 06 07 08 09
B
C
D
E
A
B
C
D
E
S.p.A.
IND.MODIFICA
SOST.DA
SOST.IL
IND.MOD.
PROPRIETA' RISERVATA DELLA DITTA ECOFLAM S.p.A.
DATA-FIRMA
DATA
FIRMA
CONTROLLATO
DESCRIZIONE MODIFICA
DISEGNATO
DATA
FIRMA
COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE.A TERMINE DI LEGGE E' VIETATO RIPRODURRE O
CONTROLLO DI TENUTAAPPARECCHIATURA
UFF.TECNICO-SETTORE ELETTRICO
DENOMINAZIONE
SIST. RIVELAZ. CODICE
MOTORIDUTTORE
BEM43.103
MULTICALOR 300 2 FIAMME LANDIS SQM50.381A2
LANDIS LFL 1.622 DUNGS VPS 504 UV
30-10-2002
BEM43086
30-10-2002
2/2
REGOLAZIONE CAMME PER MULTICALOR 300 2F
CAMMA DI REGOLAZIONE ARIA BASSA FIAMMA GAS
CAMMA REGOLAZIONE ARIA DELLA 1ª FIAMMA GASOLIO
CAMMA APERTURA ELETTROVALVOLA 2ª FIAMMA GASOLIO
CAMMA DI REGOLAZIONE ARIA PARTENZA A GAS
CAMMA NON UTILIZZATA
CAMMA NON UTILIZZATA
CAMMA NON UTILIZZATA
CAMMA DI REGOLAZIONE ARIA MASSIMA
(0°) VI:
(0°) VIII:
(0°) VII:
(15°) II:
(50°) V:
(40°) III:
(45°) IV:
(60°) I:
0 0
I II
000
III IV V VI VII VIII
pag.20
techniques for energy saving
LB1203 MULTICALOR 300.1÷400.1
PER COLLEGAMENTO IN 230V TRIFASE
BORNE R DE LA CAJA DE BORNES
PARA CONEXION EN 230V TRIFASICA
MODIFICAR LAS CONEXIONES DEL MOTOR
Y ALEJAR EL CABLE DEL BORNE N AL
A LA BORNE R DE LA BOITE A BORNES
POUR CONNEXION EN 230V TRIPHASE
MODIFIER LES CONNEXIONS DU MOTEUR
ET DE PLACER LE CABLE DE LA BORNE N
TO TERMINAL R OF THE TERMINAL STRIP
FOR 230V THREE PHASE CONNECTION
CHANGE THE CONNECTIONS OF THE MOTOR
AND MOVE THE WIRE OF TERMINAL N
CAMBIARE I COLLEGAMENTI DEL MOTORE
E SPOSTARE IL FILO DAL MORSETTO N
AL MORSETTO R DELLA MORSETTIERA
TP
3
M
3
M
LINE
LOAD
TP
TP
-
+
BLUE
YELLOW-GREEN
BLACK
BROWN
CONTROLE D'ETANCHEITI
CONTROL DE ESTANQUIDAD
PREDISPOSICION
PREVU POUR LE
PREDISPOSED
LEKAGE CONTROL
PREDISPOSIZIONE
CONTROLLO DI TENUTA
S.p.A.
00 01 02 03 04 05 06 07 08 09
A
00 01 02 03 04 05 06 07 08 09
B
C
D
E
A
B
C
D
E
IND.MODIFICA
SOST.DA
SOST.IL
IND.MOD.
PROPRIETA' RISERVATA DELLA DITTA ECOFLAM S.p.A.
DATA-FIRMA
DATA
FIRMA
CONTROLLATO
DESCRIZIONE MODIFICA
DISEGNATO
DATA
FIRMA
COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE.A TERMINE DI LEGGE E' VIETATO RIPRODURRE O
CONTROLLO DI TENUTAAPPARECCHIATURA
UFF.TECNICO-SETTORE ELETTRICO
DENOMINAZIONE
SIST. RIVELAZ. CODICE
MOTORIDUTTORE
1821
LANDIS LFL 1.622
1043 65 87 9 141211 13 1615 17 32222019 21 2423 31
PAGINA DI
BEM43.106
MULTICALOR 400 3 FIAMME
LANDIS SQM 50.381A2
LANDIS LFL 1.622 PREDISPOSTO UV
09-04-2003
BEM43087
30-10-2002
50 Hz 400V
6SR 5T N 1097 8 11
QHLB STAB
P
T
STC
P
T
STS
MP
UVW
FMP
MV
UVW
FMV
KMP
RSTNO
KMV
RSTNO
FU
SAL
Z
FMP
95
96
SAMA
12 30
GAS (2)
GASOLIO (1)
FMV
95
96
SPA
SPGmin
HLG HLg
YVg1 YVg2YVgS YVg3
pos 0: ARRESTO / STOP
pos 1: ALTA FIAMMA/HIGH FLAME/2meALLURE/ALTA LLAMA
pos 3: AUTOMATICO/AUTOMATIC/AUTOMATIQUE/AUTOMATICO
INTERRRUPTEUR 2me-1re ALLURE
pos 2: BASSA FIAMMA/LOW FLAME/1re ALLURE/BAJA LLAMA
CONMUTADOR ALTA-BAJA LLAMA
SWITCH HIGH-LOW FLAME
COMMUTATORE ALTA-BASSA FIAMMA
T
N
PE
S
R
SAMA
12 3
0
24
KA3
TV UV
KA1
12N 11 1 21 222 313 1423 4
KA2
16515 25 266 17 277
LANDIS SQM 50.381A2
M
1
1/2
YVG1YVGS
SAgG
12 30
HLBT FMV
97
98
YVGP
T1 T2 S3
N
L1
T1 T2 S3
N
L1

This manual suits for next models

1

Other Ecoflam Burner manuals

Ecoflam BLU 1700.1 PR User manual

Ecoflam

Ecoflam BLU 1700.1 PR User manual

Ecoflam BLU TS 15000.1 PR HT User manual

Ecoflam

Ecoflam BLU TS 15000.1 PR HT User manual

Ecoflam OILFLAM 50.1 PR User manual

Ecoflam

Ecoflam OILFLAM 50.1 PR User manual

Ecoflam MAIOR P 150.1 AB User manual

Ecoflam

Ecoflam MAIOR P 150.1 AB User manual

Ecoflam Multiflam 700.1 User manual

Ecoflam

Ecoflam Multiflam 700.1 User manual

Ecoflam BLU 15000.1 User manual

Ecoflam

Ecoflam BLU 15000.1 User manual

Ecoflam MAX 15 User manual

Ecoflam

Ecoflam MAX 15 User manual

Ecoflam MAIOR P 300 AB User manual

Ecoflam

Ecoflam MAIOR P 300 AB User manual

Ecoflam Multicalor 45 User manual

Ecoflam

Ecoflam Multicalor 45 User manual

Ecoflam MAX P 35 AB User manual

Ecoflam

Ecoflam MAX P 35 AB User manual

Ecoflam MAX P 45 AB User manual

Ecoflam

Ecoflam MAX P 45 AB User manual

Ecoflam BLU 3000.1 PRE TC User manual

Ecoflam

Ecoflam BLU 3000.1 PRE TC User manual

Ecoflam MAX GAS 170 P User manual

Ecoflam

Ecoflam MAX GAS 170 P User manual

Ecoflam OILFLAM 500.1 PR User manual

Ecoflam

Ecoflam OILFLAM 500.1 PR User manual

Ecoflam MAXFLAM 10 User manual

Ecoflam

Ecoflam MAXFLAM 10 User manual

Ecoflam MAX 1 TC User manual

Ecoflam

Ecoflam MAX 1 TC User manual

Ecoflam BLU 10000.1 PR User manual

Ecoflam

Ecoflam BLU 10000.1 PR User manual

Ecoflam BLU TS 1500.1 PR User manual

Ecoflam

Ecoflam BLU TS 1500.1 PR User manual

Ecoflam Multicalor 170.1 PR User manual

Ecoflam

Ecoflam Multicalor 170.1 PR User manual

Ecoflam Maior P45 PR User manual

Ecoflam

Ecoflam Maior P45 PR User manual

Ecoflam MAX GAS 350 P CV User manual

Ecoflam

Ecoflam MAX GAS 350 P CV User manual

Ecoflam BLU 2000.1 PR User manual

Ecoflam

Ecoflam BLU 2000.1 PR User manual

Ecoflam BLU 170 User manual

Ecoflam

Ecoflam BLU 170 User manual

Ecoflam BLU 7000.1 PR User manual

Ecoflam

Ecoflam BLU 7000.1 PR User manual

Popular Burner manuals by other brands

Bentone BG 400 manual

Bentone

Bentone BG 400 manual

Riello 580T Installation & operating manual

Riello

Riello 580T Installation & operating manual

Riello 40 F20 Installation, use and maintenance instructions

Riello

Riello 40 F20 Installation, use and maintenance instructions

Lamborghini Caloreclima SILVER 24T Instructions for use, installation & maintenance

Lamborghini Caloreclima

Lamborghini Caloreclima SILVER 24T Instructions for use, installation & maintenance

baltur TBG 1200 ME INSTALLATION, USE AND MAINTENANCE INSTRUCTION MANUAL

baltur

baltur TBG 1200 ME INSTALLATION, USE AND MAINTENANCE INSTRUCTION MANUAL

Unigas KTP1030 Manual of installation - use - maintenance

Unigas

Unigas KTP1030 Manual of installation - use - maintenance

Diamond TPG3-15 quick start guide

Diamond

Diamond TPG3-15 quick start guide

Riello BP R 75 MB Installation, use and maintenance instructions

Riello

Riello BP R 75 MB Installation, use and maintenance instructions

NTGAS HQ-04 Technical installation instructions use and maintenance instructions

NTGAS

NTGAS HQ-04 Technical installation instructions use and maintenance instructions

Beckett AFG Oil Burner 240V Product sheet

Beckett

Beckett AFG Oil Burner 240V Product sheet

Riello RL 300 Installation, use and maintenance instructions

Riello

Riello RL 300 Installation, use and maintenance instructions

Masport CLUTHA Installation & operation manual

Masport

Masport CLUTHA Installation & operation manual

Anderson PBO92 Operation manual

Anderson

Anderson PBO92 Operation manual

Riello RS 190 Installation, use and maintenance instructions

Riello

Riello RS 190 Installation, use and maintenance instructions

Bentone BENTOFLEX ST 120 KAV Installation and maintenance  instruction

Bentone

Bentone BENTOFLEX ST 120 KAV Installation and maintenance instruction

Rasmussen CS General Installation Instructions

Rasmussen

Rasmussen CS General Installation Instructions

baltur BGN 40 DSPGN instructions

baltur

baltur BGN 40 DSPGN instructions

Kudu KU-HP1000-WH instruction manual

Kudu

Kudu KU-HP1000-WH instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.