manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Eliwell
  6. •
  7. Controllers
  8. •
  9. Eliwell EWDB 111 User manual

Eliwell EWDB 111 User manual

THE USER INTERFACE
USE OF THE KEYS
The keys of the instrument permit both
the utilisation of the menu and the direct
activation of a function.
USE OF THE MENUS
ACCESS TO THE MAIN MENU
The programming of the instrument is
organised by menu (see Fig. 2, Menu flow-
chart), which can be accessed by keeping
the key pressed down for the time set
by H02 parameter.
NAVIGATION OF THE MENUS
In order to access the contents of each
folder, just press the key once.
If called for, a password will be required.
There are two different passwords. The
first password (PA1) is for access to the
parameters in the PL1 folder. The second
password (PA2) is for access to the para-
meters in the PL2 folder. (see Fig. 2, Menu
flowchart).
At this point in the proceedings it is possi-
ble to scroll through the contents of each
folder & amend them .
If you do not use the keyboard or hit the
key within 15 seconds, the last value
displayed on the screen is confirmed
and you return to the previous screen.
DESCRIPTION OF FOLDERS
PL1 = user parameters (level 1)
This folders contains the parameters
required by the end user in order to make
any minimum amendments to the pro-
gramming parameters (see Table 6 and
Table 7).
PL2 = machine parameters (level 2)
This folders contains the parameters
required by the manufacturer and the
assembler for the optimum configuration
of the controlling machine (see Table 6
and Table 7).
St = machine status
In this folder the status of the input 2 can
be viewed; (see Table 4).
RAPID ACTIVATION
Certain specific functions (Setpoint,
defrost) are associated with keys on the
frontlet (see Table 2, Keys and functions
set directly).
DISPLAY AND DEFINITION OF THE SET-
POINT VALUE
In order to view the Setpoint value, keep
the key pressed down for the time set
by Pa H02 parameter.
The Setpoint value will appear on the dis-
play and the temperature gauge icon will
begin to flash. In order to vary the
Setpoint value operate, within 15 seconds,
on the keys and
If the parameter LOC = y is not possible to
modify the Setpoint.
MANUAL ACTIVATION OF THE DEFROST
CYCLE
Manual activation of the defrost cycle is
achieved by keeping the key pressed
down for “Pa H02” seconds.
KEYPAD LOCK
The instrument anticipates, by means of
appropriately programming the “Loc”
parameter (see Table 6, “Miscellaneous”
parameters), the possibility of disabling the
functioning of the keypad.
In the event the keypad is locked, the user
can always access the programming MENU
by pressing the key
If there is not available to start defrosting,
the defrost LED will blink 5 times
PARAMETERS
The parameters can be viewed in two dif-
ferent tables: the first (see Table 6)
describes the function of the parameter,
while the second (see Table 7) lists the
characteristics of each parameter.
DIAGNOSTICS
The alarm icon indicates an alarm condi-
tion. Breakdowns are indicated on the
screen (see Table 5).
When an alarm status occurs, it is possible
to silence the buzzer and/or relay config-
ured as an alarm, by pressing any key.
The buzzer is optional and is present on
the EWDB 111 B model.
EWDB 111
electronic controller for refrigerating units
KEY DESCRIPTION
UP key
DOWN key
ESC key
ENTER key
FUNCTION
Scrolls through the menu
items
Increases the values
Scrolls through the menu
items
Decreases the values
Returns to the previous
level
Accesses the menus
Confirms the commands
Table 1 Keys and menu
PARAMETER
Pb2
sensor 2
VALUE
sensor 2 value
Table 4 Machine status table
KEY DESCRIPTION
UP
ESC
DOWN
ENTER
FUNCTION
Activates manual defrost
function
Accesses the setpoint
Accesses the program-
ming menu
Table 2 Keys and functions set directly
Fig. 1 Frontlet of instrument ICON INDICATION
alarm active
temperature
range (°F if
icon turn-off)
defrost active
compressor
DETAILS
Permanently lit up in the
event of an alarm, flash-
ing in the event of a
silenced alarm
Flashing in paramete
programming
Permanently lit up in the
event of defrosting in
progress, flashing in the
event of manual defrost
Permanently lit up in the
event of compressor
valve working, flashing in
the event of delay in
activating
Table 3 Icons
BREAKDOWNS
When the sensor detects an error condi-
tion:
• the code E1 is displayed
• the compressor is activated as indicated
by the "On" and "Off" parameters:
MINIMUM AND MAXIMUM TEMPERA-
TURE ALARMS
Regulation of the minimum and maximum
temperature alarms refers to the cold cell
sensor.
The temperature limits defined by the
“HAL” (maximum temperature alarm) and
“LAL” parameters (minimum temperature
alarm) are characterised by the “Att” para-
meter which specifies if they represent the
absolute temperature value or a differen-
tial with respect to the setpoint.
When an alarm status occurs, if no alarm
exclusion phases are underway (see alarm
exclusion parameters), the alarm set icon
is lit up and the buzzer, and/or the relay
configured as an alarm, is activated. The
occurrence of this alarm does not in any-
way effect the control activities in
progress.
FITTER ASSEMBLY
The instruments belonging to the
DIGIFROST series range have been con-
ceived for panel mounting purposes.
Cut a hole and insert the instrument fas-
tening it with the supplied bracket. The
distance between two coupled devices is
79 mm.
With the appropriate adapter, the instru-
ments can also be assembled on holes for
the standard ELIWELL 32x74 mm. The
panel thickness must be between 0.5 mm
and 7 mm.
The room temperature range admitted for
correct operation is between -5 e 60 °C.
Furthermore, avoid mounting the instru-
ments in locations subject to high levels of
humidity and/or dirt: said instruments are
in fact suitable for use in environments
with an ordinary or normal level of pollu-
tion.
Make sure that the area near to the cool-
ing slits is left aerated.
EWDB 111 2/3
PARAMETER
SEt
diF
HSE
LSE
Ont
OFt
dOn
dOF
dbi
OdO
dit
dtU
dCt
dOH
dEt
dPO
dri
Afd
Att
HAL
LAL
PAO
dAO
tAO
AOP
LOC
PA1
PA2
ndt
CAL
LdL
HdL
dLc
dro
H02
H21
H23
reL
tAb
(1) PLEASE NOTE: in the version with the buzzer.
DESCRIPTION
COMPRESSOR CONTROLLER
Setpoint: value ranging between the set minimum (LSE) and the set maximum (HSE).
Operating differential of the setpoint. For applications in the refrigeration sector the compressor
will cut off on reaching the Setpoint value set (on indication of the control sensor), only to
restart at a temperature value equal to the Setpoint plus the differential value.
Note: It will not accept a 0 value.
Maximum value attributable to the setpoint.
Minimum value attributable to the setpoint; normally set at the lowest value measurable by the
sensor.
COMPRESSOR PROTECTION CONTROLLER
ON time of the compressor due to sensor failure.
OFF time of the compressor due to sensor failure.
Start-up delay. The parameter indicates that a protection is active on the realisation of the com-
pressor/general relay.
Delay after shut-down. The parameter indicates that a protection is active on the realisation of
the compressor/general relay. At the very minimum, the time indicated must elapse between
shut-down of the compressor relay and the subsequent start-up.
Delay between start-ups. The parameter indicates that a protection is active on the realisation of
the compressor/general relay. At the very minimum, the time indicated must elapse between
two subsequent start-ups of the compressor relay.
Activation delay of the instrument start-up outputs or after a lack of voltage; expressed in min-
utes.
DEFROST CONTROLLER
Interval between one defrost cycle and the subsequent one; expressed in hours and in minutes
in relation to the “dtU”.
Time measurement unit for intervals/length of defrosting.
0 = interval between two defrost cycles in hours, duration of defrost cycle in minutes;
1 = interval between two defrost cycles in minutes; duration of defrost cycle in seconds.
Defrost interval reckoning mode.
0 = only the running time of the compressor is counted;
1 = the running time of the instrument is counted;
2 = defrosting takes place every time the compressor shuts down.
Delay in commencement of defrost cycle; expressed in minutes.
Defrost cycle Time out; expressed in minutes or seconds in relation to the “dtU”.
Request for activation of the defrost controller on start-up. y = yes; n = no.
By means of this parameter it is possible to decide if, on request of a manual defrost cycle, the
reckoning for the defrost interval must be set to zero or not. y = yes; n = no.
ALARMS
Alarm/fan set differential: temperature difference between the setting off and disconnection of
the minimum or maximum alarm or of the fans.
Mode of interpreting the value of the HAL and LAL parameters.
0 = interprets the values as absolutes (not referring to the setpoint);
1 = interprets the values as relative with respect to the setpoint.
Maximum temperature alarm. Temperature value whose excess upwards will determine the acti-
vation of the alarm signal.
NOTE: To obtain the alarm as relative with respect to the setpoint in case of Att=1 set “LAL” to a
positive value
Minimum temperature alarm. Temperature value whose excess downwards will determine the
activation of the alarm signal.
NOTE: To obtain the alarm as relative with respect to the setpoint in case of Att=1 set “HAL” to
a negative value
Exclusion of the alarms on start-up of the instrument, after a failure in the power supply. In the
event of reactivation of additional delay times the highest among these will be valid.
Exclusion of alarm after defrosting.
Delay time for signalling of temperature alarm.
Indicates the polarity type of the relay/buzzer configured as an alarm.
0 = alarm active and output disabled; 1 = alarm active and output enabled.
MISCELLANEOUS
Keypad lock (blocks the activation of the primary functions). With the keypad disabled, viewing
of the Setpoint is only permitted by means of the key associated with direct functions. However
it remains possible to enter parameter programming and modify the status of the parameter so
as to enable the unlocking of the keypad. n = do not lock; y = lock.
Password 1 (blocks PL1).
Password 2 (blocks PL2).
DISPLAY
Display mode of the temperature on the display.
n = full number; y = decimal number.
Gauging. Positive or negative temperature offset which is added to the value read by the ther-
mostating sensor before being displayed and used for control purposes.
Minimum value of the sensor which can be viewed on the display.
Maximum value of the sensor which can be viewed on the display.
Display mode during the defrost cycle.
0 = displays the temperature read by the cold cell sensor;
1 = displays the temperature read by the cold cell sensor at the time of commencement of
defrosting;
2 = displays the “dEF” label during defrosting. Once defrosting and de-tearing has finished, the
device will continue to display the information anticipated until the cold cell sensor reaches the
setpoint value. If set at zero, the display does not entail the reaching of the setpoint.
°C or °F selection. 0 = °C; 1 = °F.
MACHINE SETTINGS
Key activation time.
Configuration capacity of digital output 1.
0 = disable; 1=compressor; 2 = defrost ( do not use); 3 = fans (do not use); 4 = alarm;
Configuration output buzzer. same as H21.
Release firmware
Table of parameters
Table 6 Description parameters table
DISPLAY
E1
ERROR
Cold cell sensor fault
Table 5 Error table
Ont
0
0
>0
<0
Oft
0
>0
0
>0
Compressor output
OFF
OFF
ON
D.C.
ELECTRICAL
CONNECTIONS
The instrument is provided with screw ter-
minal boards for the connection of wires
with a maximum 2.5 mm2section (one
wire only per terminal for power connec-
tions).
Always turn the machine off before oper-
ating on electrical connections.
Relay outputs are voltage free. Do not
exceed the maximum allowed voltage; in
case of heavier loads use a suitable power
contactor.
Make sure the power supply voltage match
the instrument requirements.
In 12 V powered versions that do not
require probe with reinforced insulation
the power can be supplied through a safe-
ty transformer protected by a delayed 250
mA fuse.
Probes require no insertion polarity and
can be lengthened using standard bipolar
cable (please note that longer probes may
cause worse instrument performance in
terms of electro-magnetic compatibility:
maximum care shall be put in cabling).
Probe, digital input and supply cables shall
be kept far from power cables.
In versions requiring probes with rein-
forced insulation (refer to label on the
rear of the instrument ) probe contacts
are not insulated from power supply.
Therefore probes shall provided reinforced
insulation when they are easily accessible.
Moreover, when such models are installed
on a metal panel, such panel shall be
grounded.
In versions not requiring probes with rein-
forced insulation probe and power supply
contacts feature a reinforced insulation
from relay contacts. Therefore such con-
tacts (power supply and probe) can be
accessible with no risk provided that
power supply is SELV.
A reinforced insulation shall be provided
between relay contacts and accessible sec-
tions.
CONDITIONS OF USE
PERMITTED USE
For safety reasons the instrument must be
installed and used according to the
instruction provided and in particular,
under normal conditions, parts bearing
dangerous voltage levels must not be
accessible.
The device must be adequately protected
from water and dust as per the application
and must also only be accessible via the
use of tools (with the exception of the
frontlet).
The device is ideally suited for use on
household appliances and/or similar refrig-
eration equipment and has been tested
with regard to the aspects concerning
European reference standards on safety. It
is classified as follows:
• according to its manufacture: as an auto-
matic electronic control device to be
incorporated by independent mounting;
• according to its automatic operating fea-
tures: as a 1 B-type operated control type;
• as a Class A device in relation to the cat-
egory and structure of the software.
USE NOT PERMITTED
Any other use other than that permitted is
de facto prohibited.
It should be noted that the relay contacts
provided are of a practical type and there-
fore subject to fault. Any protection
devices required by product standards or
dictated by common sense due to obvious
safety reasons should be applied external-
ly.
LIABILITY AND RESIDUAL
RISKS
Invensys Controls Italy s.r.l. shall not be
liable for any damages deriving from:
- installation/use other than that pre-
scribed and, in particular, that which does
not comply with safety standards anticipat-
ed by regulations and/or those given here-
in;
- use on boards which do not guarantee
adequate protection against electric shock,
water or dust under the conditions of
assembly applied;
- use on boards which allow access to dan-
gerous parts without the use of tools;
- tampering with and/or alteration of the
products;
- installation/use on boards not complying
with the standards and provisions of cur-
rent legislation.
TECHNICAL DATA
Frontlet protection: IP65.
Casing: plastic in PC+ABS resin.
Dimensions: frontlet 72x30 mm, depth
45 mm.
Mounting: panel mounted, with drill holes
of 58x25,4 mm (+0,2/–0,1 mm) in diame-
ter.
Room temperature: –5…60 °C.
Storage temperature: –30…75 °C.
Display range: –50…140 °C on a 3 digit +
sign display.
Analog inputs: one standard NTC type sup-
plied or PTC (according to availability).
Digital outputs: 1 SPDT output on relay
(for ... see bal on the instrument)
Temperature range: from -50 to 110 °C
(from –40 to 230 °F).
Accuracy: the best of 0.5% at bottom of
scale.
Definition: 1 or 0.1 °C.
Power consumption: according to the
model
Power supply: according to the model. See
label on the instrument
NOTE: for the optionals, see label on the
instrument.
DISCLAIMER
This manual and its contents remain the
sole property of Invensys Controls Italy
s.r.l., and shall not be reproduced or dis-
tributed without authorization. Although
great care has been exercised in the
preparation of this document, Invensys
Controls Italy s.r.l., its employees or its
vendors, cannot accept any liability what-
soever connected with its use. Invensys
Controls Italy s.r.l. reserves the right to
make any changes or improvements with-
out prior notice.
EWDB 111 3/3
Invensys Controls Italy s.r.l
via dell'Industria, 15 Zona Industriale Paludi
32010 Pieve d'Alpago (BL) ITALY
Telephone +39 0437 986111
Facsimile +39 0437 989066
Email [email protected]
Internet http:/www.climate-eu.invensys.com
6/2001 ing
cod. 9IS20165
EWDB 111 APPENDIX 1
Table 10 Complete parameters table
PARAMETER
SEt
diF
HSE
LSE
Ont
OFt
dOn
dOF
dbi
OdO
dit
dtU
dCt
dOH
dEt
dPO
dri
Afd
Att
HAL
LAL
PAO
dAO
tAO
AOP
LOC
PA1
PA2
ndt
CAL
LdL
HdL
dLc
dro
H02
H21
H23 (1)
reL
tAb
LEVEL
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
2
2
2
2
2
2
2
2
RANGE
LSE...HSE
0.3...30.0
LSE..302
-67...HSE
0...250
0...250
0...250
0...250
0...250
0...31
0...250
0/1
0/1/2
0...250
1...250
n/y
n/y
1.0...50.0
0/1
LAL..302
-67...HAL
0...10
0..999
0...250
0/1
n/y
0...255
0...255
n/y
-30...30
-67...302
-67..302
0/1/2
0/1
0…250
0…4
0…4
/
/
DEFAULT
0
2
50
-50
10
0
0
0
0
0
6
0
1
0
30
n
y
2
1
50
-50
2
60
0
1
n
0
0
n
0
-50
110
1
0
5
1
3
/
/
U.M.
°C/°F
°C/°F
°C/°F
°C/°F
min
min
sec
min
min
min
h
num
num
min
min/sec
flag
flag
°C/°F
num
°C/°F
°C/°F
h
min
min
num
flag
num
num
flag
°C/°F
°C/°F
°C/°F
num
num
sec
num
num
/
/
DESCRIPTION
SEtpoint
diFFerential
High SEt
Low SEt
On time compressor
OFF time compressor
dealy On compressor
dealy OFF compressor
delay between interval
Output delay at On
defrost interval time
defrost time unit
defrost count type
defrost Offset
defrost Endurance time
defrost at Power ON
defrost reset interval
Alarm fan differential
Alarm temperature type
High ALarm
Low ALarm
Power on Alarm Override
defrost Alarm Override
temperature Alarm Override
Alarm Output Polarity
keyboard LOCK
Password 1
Password 2
number display type
CALibration
Low display
High display
display Lock
display read-out
Tempo attivazione tasti
Configurabilità uscita digitale 1
Configurabilità uscita buzzer
reLease Firmware
tAble of parameters
PA2
PA1
folder PL2
St
PL2
PL1
Main Menu
ENTER Key
Tab. 4
folder PL2
folder PL1 folder PL1
Tab. 4
1 2 3 5 6 7 8
1 2 3 5 6 7 8
1 2 3 4 5 7 8
1 2 3 4 5 7 8
WIRING
1 - 2 - 3
4 - 5
5 - 6
7 - 8
compressor relay output
thermostatic sensor input
thermostatic sensor input
power supply
Fig. 2 Menù flowchart
Fig. 3 Schema di morsettiera

Other Eliwell Controllers manuals

Eliwell ID 974 User manual

Eliwell

Eliwell ID 974 User manual

Eliwell EWDR 981 User manual

Eliwell

Eliwell EWDR 981 User manual

Eliwell IDplus 902 User manual

Eliwell

Eliwell IDplus 902 User manual

Eliwell IWP 740 User manual

Eliwell

Eliwell IWP 740 User manual

Eliwell IC 912 Series User manual

Eliwell

Eliwell IC 912 Series User manual

Eliwell IDplus 961 User manual

Eliwell

Eliwell IDplus 961 User manual

Eliwell IWP 760 LX User manual

Eliwell

Eliwell IWP 760 LX User manual

Eliwell IC 912 LX Pt100 R User manual

Eliwell

Eliwell IC 912 LX Pt100 R User manual

Eliwell IC 915 NTC/PTC User manual

Eliwell

Eliwell IC 915 NTC/PTC User manual

Eliwell EWRC 300 NT Series User manual

Eliwell

Eliwell EWRC 300 NT Series User manual

Eliwell ECH 200BD "Adaptive" User manual

Eliwell

Eliwell ECH 200BD "Adaptive" User manual

Eliwell ID 983LX HACCP User manual

Eliwell

Eliwell ID 983LX HACCP User manual

Eliwell EWPlus 902 User manual

Eliwell

Eliwell EWPlus 902 User manual

Eliwell EWKPlus 978 User manual

Eliwell

Eliwell EWKPlus 978 User manual

Eliwell EWRC 300 NT Series User manual

Eliwell

Eliwell EWRC 300 NT Series User manual

Eliwell ID 985 User manual

Eliwell

Eliwell ID 985 User manual

Eliwell EWDR 983/CS User manual

Eliwell

Eliwell EWDR 983/CS User manual

Eliwell Televis EWCM 809/NH3/S User manual

Eliwell

Eliwell Televis EWCM 809/NH3/S User manual

Eliwell ICPlus 915 User manual

Eliwell

Eliwell ICPlus 915 User manual

Eliwell IC 915 NTC/PTC User manual

Eliwell

Eliwell IC 915 NTC/PTC User manual

Eliwell EWRC 300 NT Series User manual

Eliwell

Eliwell EWRC 300 NT Series User manual

Eliwell ID 400 User manual

Eliwell

Eliwell ID 400 User manual

Eliwell EWRC 500 NT Series User manual

Eliwell

Eliwell EWRC 500 NT Series User manual

Eliwell EWHT 1800LX User manual

Eliwell

Eliwell EWHT 1800LX User manual

Popular Controllers manuals by other brands

IBM 3745 Series Connection and Integration Guide

IBM

IBM 3745 Series Connection and Integration Guide

SmartAV Tango Series install guide

SmartAV

SmartAV Tango Series install guide

Andersen 100 Series Important safety information

Andersen

Andersen 100 Series Important safety information

Samson 3277 Mounting and operating instructions

Samson

Samson 3277 Mounting and operating instructions

Trane 700 user guide

Trane

Trane 700 user guide

Johnson Controls P266 Series installation instructions

Johnson Controls

Johnson Controls P266 Series installation instructions

Hunter Hydrawise HCC-800-PL owner's manual

Hunter

Hunter Hydrawise HCC-800-PL owner's manual

Newport ESP300 Series user manual

Newport

Newport ESP300 Series user manual

Danfoss Optyma Plus OP-MPS instructions

Danfoss

Danfoss Optyma Plus OP-MPS instructions

Carousel USA 40SSV manual

Carousel USA

Carousel USA 40SSV manual

Pixel VIS131.1 Operation manual

Pixel

Pixel VIS131.1 Operation manual

Romstal KJRP-86A/BMFNKD-E Installation & owner's manual

Romstal

Romstal KJRP-86A/BMFNKD-E Installation & owner's manual

RC4 Wireless LumenDimPix quick start guide

RC4 Wireless

RC4 Wireless LumenDimPix quick start guide

Behringer Monitor1 quick start guide

Behringer

Behringer Monitor1 quick start guide

Davey Water Products Torrium 2 Installation and operating instructions

Davey Water Products

Davey Water Products Torrium 2 Installation and operating instructions

ABB ControlMaster CMF manual

ABB

ABB ControlMaster CMF manual

InPOWER SBF94 owner's manual

InPOWER

InPOWER SBF94 owner's manual

Ricoh Fiery E-820 Configuration guide

Ricoh

Ricoh Fiery E-820 Configuration guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.