2 Description
Sensor KNX AQS/TH-B-UP • as of software 3.1 • Status: 24.09.2014 • Technical changes reserved. Errors reserved.
1. Description
The Sensor KNX AQS/TH-B-UP measures CO2concentration, temperature and
humidity and calculates the dew point. The sensor can receive external measured
values via the bus and process them with the own data to overall vealues (mixed
values, e. g. room average). The KNX AQS/TH-B-UP offers two push buttons that may
be used for changing the ambient temperature (target value), for switching between
operating modes or as free programmable bus push buttons.
The KNX AQS/TH-B-UP provides switching outputs with adjustable threshold values.
The switching outputs and further communication objects can be linked by AND and
OR logic gates. Additionally, an integrated actuating variable comparator can compare
and output values that are received via communication objects.
Integrated PI controllers allows for control of a ventilation (depending on CO2
concentration and air humidity) and a heating/cooling system (depending on
temperature). The KNX AQS/TH-B-UP can can emit a warning to the bus as soon as
the area of optimum comfort (according to DIN 1946) is left.
The integrated display shows the own values and data received from the bus (e. g.
date, time). The housing is completed with a frame of the switching series installed in
the building and thus merges with the interior.
Functions:
• Measurement of CO2concentration of the air, of temperature and air
humidity (absolute and relative), calculation of the dew point
•Mixed values from own measured values and external values (proportions
can be set in percentage)
•Display 1-3 rows (own values or values received from the bus) or display of
temperature control (see Mode display and manual temperature controller,
page 8)
•2 push buttons. Configuration as bus push button or for changing ambient
temperature and switching between operating modes (see Change ambient
temperature with the buttons, page 9)
•PI controller for heating (one or two step) and cooling (one or two step)
depending on temperature. Control according to separate target values or
basic target temperature
•PI controller for ventilation depending on humidity and CO2concentration:
dehumidification/humidification (one step) or dehumidification (one or two
step)
•Switching outputs with adjustable threshold values: 3 × temperature, 2 ×
humidity, 4 × CO2. Threshold values can be set by parameter or via
communication objects
•8 AND and 8 OR logic gates with each 4 inputs. Every switching incident as
well as 8 logic inputs in the form of communication objects, may be used as
inputs for the logic gates. The output of each gate may optionally be configured
as 1 bit or 2 x 8 bits