manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. elsner elektronik
  6. •
  7. Accessories
  8. •
  9. elsner elektronik WG AQS/TH-UP User manual

elsner elektronik WG AQS/TH-UP User manual

WG AQS/TH-UP sensor 1
WG AQS/TH-UP sensor • Version: 19.12.2018 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
EN
WG AQS/TH-UP
Indoor Sensor
Technical specifications and installation instructions
Item numbers 20553 (white), 20554 (aluminium coloured)
1. Description
The WG AQS/TH-UP sensor transmits via radio the temperature, humidity and
CO2 content of the air to the WS1 Colour/Style or (KNX) WS1000 Colour/ Style con-
troller. Several sensors can be "taught" on one controller. The teaching procedure is
described in the chapter "Learning wireless connections" (Controller manual).
The WG AQS/TH-UP consists of the housing, the sensor printed circuit board/base-
plate, the CO2 sensor and a frame. As an alternative to the frame provided, a frame
in the switch series used in the building can be used. You also need a junction box
(Ø 60 mm, 42 mm deep, not included in the deliverables).
For the power supply (11...30 V DC) e.g. 12 V DC can be drawn from the connector
board for the control system (multifunction-input).
Suitable for:
• WS1 Color, WS1 Style (from software version 1.819)
• WS1000 Color, WS1000 Style (from software version 1.819)
• KNX WS1000 Color, KNX WS1000 Style (from software version 1.819)
1.0.1. Deliverables
• Housing
• Baseplate (circuit board)
•CO
2-Sensor unit
•Frame
You also need (not included in deliverables):
• Junction box Ø 60 mm, 42 mm depth
1.1. Technical specifications
The product is compliant with the provisions of the following EC guidelines.
1.1.1. Measurement accuracy
Deviations in measured values due to interfering sources (see chapter installation
site) must be corrected in the controller menu in order to achieve the specified sen-
sor accuracy.
The specified CO2 measurement accuracy is achieved after a run-in of 24 hours
(without voltage interruption), if the sensor comes into contact with fresh air
(350…450 ppm) at least once during this period. During the warm-up phase the rea-
ding may not be displayed at all or wrongly, or remain frozen at 2001.
After this, the CO2-sensor performs a self-calibration every two weeks, in which the
lowest CO2value measured during this period (without voltage interruption) is taken
as a reference for fresh air.
In order to ensure permanent accuracy, the sensor should be supplied with fresh air
at least once every two weeks. This is normally the case during room ventilation.
The measured temperature and humidity values can be corrected in the cont-
roller menu. This may be necessary if the values at the sensor do not correspond to
the room average (for example, if the sensor is positioned in a location which is war-
mer than average). Please be aware that usable measured values can only be achie-
ved approx. two hours after putting the sensor into operation (warm-up phase).
Radio connections > Status (In the controller manual)
System > Installation > Radio connection > Status > [Device]
2. Installing the indoor sensor
2.1. Installation notes
Installation, testing, operational start-up and troubleshooting should
only be performed by an electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
• National legal regulations are to be followed.
• Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.
• Do not use the device if it is damaged.
• Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is no
longer guaranteed.
The device is only to be used for its intended purpose. Any improper modification
or failure to follow the operating instructions voids any and all warranty and gua-
rantee claims.
After unpacking the device, check it immediately for possible mechanical damage.
If it has been damaged in transport, inform the supplier immediately.
The device may only be used as a fixed-site installation; that means only when as-
sembled and after conclusion of all installation and operational start-up tasks and
only in the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.
2.1.1. Installation location
Install and use only in dry interior rooms.
Avoid condensation.
When selecting an installation location, please ensure that the measurement results
are affected as little as possible by external influences. Possible sources of interfe-
rence include:
• Direct sunlight
• Draughts from windows and doors
• Draughts from ducts which lead from other rooms, or the outside to the
junction box in which the sensor is mounted
• Warming or cooling of the building structure on which the sensor is mounted,
e.g. due to sunlight, heating or cold water pipes
• Connection lines and empty ducts which lead from warmer or colder areas to
the sensor
Temperature deviations caused by such sources of interference must be corrected
in the control system menu, in order to achieve the specified sensor accuracy (see
manual chapter Wireless connections > Status).
For a correct CO2measurement it is necessary to install the device in a windproof
junction box.
Housing Plastic (partially painted)
Colours • White, glossy (similar to RAL 9016 Traffic White)
• Matt aluminium
Assembly Flush mounting (Flush mounting in junction box Ø 60
mm, 42 mm depth)
Protection category IP 20
Dimensions Housing approx. 55 x 55 (W x H, mm), construction
depth
approx. 15 mm baseplate approx. 71 x 71 (W x H,
mm)
Total weight approx. 50 g
Ambient temperature Operation -20…+70°C, storage -30…+70°C
Ambient humidity max. 95% RH, avoid condensation
Operating voltage 11…30 V DC
Power max. 35 mA
Data output Via wireless
Wireless frequency 868.2 MHz
Protocol own protocol (Elsner RF)
Temperature measurement
range
-20…+70°C
Resolution (temperature) 0.1°C
Accuracy (temperature) ±0,6°C at -20...-10°C
±0,5°C at -10...+65°C
±0,6°C at +65...+70°C
Humidity measurement
range
0…95% RH
Humidity resolution 0.1%
Humidity accuracy ±7,5% RH at 0...10% RH
±4,5% RH at 10...90% RH
±7,5% RH at 90…95% RH
Humidity drift ± 0.5% RH per year in normal atmosphere
CO2 measurement range 0...2000 ppm
CO2 resolution 1 ppm
CO2 accuracy ±50 ppm ±3% of the measured value
WG AQS/TH-UP sensor 2
WG AQS/TH-UP sensor • Version: 19.12.2018 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
2.2. Construction of the sensor
2.2.1. Housing
2.2.2. Rear view of the baseplate (circuit board) with connection
2.3. Sensor assembly
1. First, place the windproof box with the supply connection. Seal the inlet tubes as
well, in order to prevent drafts.
5. Then screw the baseplate (circuit board) on to the box. The lettering OBEN/TOP
must be at the top and at the front.
6. Position the frame of the switch series and firmly put the sensor housing with the
latches onto the baseplate (circuit board) so that this is fixed to the frame.
2.4. Notes on mounting and commissioning
Never expose the device to water (e.g. rain) or dust. This can damage the electro-
nics. You must not exceed a relative humidity of 95%. Avoid condensation.
2.5. Establish wireless connection
1. Set the control system to teaching (follow the chapter Teaching wireless connec-
tion in the manual).
2. Press the programming button on the WG AQS/TH-UP sensor
3. Observe the response from the control system ("device taught").
Fig. 1
1 Baseplate (circuit board)
2 Catches
3 Openings for air circulation
4 Programming LED (recessed)
5 Programming button (recessed) for
teaching the device
6 Openings for air circulation
(LOWER)
3
2
5
4
6
1
Fig. 2
1 Catches
2 Terminal power supply 11…30 V DC
(+/-), Connection polarity independent
3CO
2socket - sensor unit
4CO
2plug - sensor unit
5CO
2sensor unit
Cable length approx. 110 mm
a Hole distance approx. 43 mm
b Membrane diameter approx. 18 mm
2
1
3
45
a
b
2. Connect the CO2sensor to the sensor circuit board.
3. Connect the power supply.
4. Place the CO2sensor unit into the box. The side with the
sensor membrane must face the front (Fig. 3)
Fig. 3
The programming button is behind the lower
housing opening on the right.
Use, for example, a paper-clip or a piece of wire to
press the button

This manual suits for next models

2

Other elsner elektronik Accessories manuals

elsner elektronik KNX AQS/TH-B-UP User manual

elsner elektronik

elsner elektronik KNX AQS/TH-B-UP User manual

elsner elektronik KNX LW 70128 User manual

elsner elektronik

elsner elektronik KNX LW 70128 User manual

elsner elektronik KNX VOC/TH-UP Touch User manual

elsner elektronik

elsner elektronik KNX VOC/TH-UP Touch User manual

elsner elektronik 20550 User manual

elsner elektronik

elsner elektronik 20550 User manual

elsner elektronik Vari KNX 3L-TH-D GPS Guide

elsner elektronik

elsner elektronik Vari KNX 3L-TH-D GPS Guide

elsner elektronik KNX LW sl User manual

elsner elektronik

elsner elektronik KNX LW sl User manual

elsner elektronik KNX R sl User manual

elsner elektronik

elsner elektronik KNX R sl User manual

elsner elektronik KNX L Guide

elsner elektronik

elsner elektronik KNX L Guide

elsner elektronik KNX L User manual

elsner elektronik

elsner elektronik KNX L User manual

elsner elektronik KNX T-L-Pr-UP Touch Guide

elsner elektronik

elsner elektronik KNX T-L-Pr-UP Touch Guide

elsner elektronik KNX R Guide

elsner elektronik

elsner elektronik KNX R Guide

elsner elektronik KNX TH-UP Touch User manual

elsner elektronik

elsner elektronik KNX TH-UP Touch User manual

elsner elektronik TH-UP basic User manual

elsner elektronik

elsner elektronik TH-UP basic User manual

elsner elektronik KNX B8-TH Guide

elsner elektronik

elsner elektronik KNX B8-TH Guide

elsner elektronik KNX AQS TH-B-UP Guide

elsner elektronik

elsner elektronik KNX AQS TH-B-UP Guide

elsner elektronik Sewi KNX L Guide

elsner elektronik

elsner elektronik Sewi KNX L Guide

elsner elektronik 30170 User manual

elsner elektronik

elsner elektronik 30170 User manual

elsner elektronik KNX VOC/TH-UP Touch CH User manual

elsner elektronik

elsner elektronik KNX VOC/TH-UP Touch CH User manual

elsner elektronik Vari KNX 3L-TH-D GPS User manual

elsner elektronik

elsner elektronik Vari KNX 3L-TH-D GPS User manual

elsner elektronik KNX W Series Guide

elsner elektronik

elsner elektronik KNX W Series Guide

elsner elektronik P04i-W User manual

elsner elektronik

elsner elektronik P04i-W User manual

elsner elektronik R 24 V User manual

elsner elektronik

elsner elektronik R 24 V User manual

elsner elektronik AQS/TH PF User manual

elsner elektronik

elsner elektronik AQS/TH PF User manual

elsner elektronik KNX AQS/TH-B-UP User manual

elsner elektronik

elsner elektronik KNX AQS/TH-B-UP User manual

Popular Accessories manuals by other brands

T'nB SHBULBADA user manual

T'nB

T'nB SHBULBADA user manual

Chef's Choice Pronto Diamond Hone 464 Instructions for use

Chef's Choice

Chef's Choice Pronto Diamond Hone 464 Instructions for use

Aqua Medic Titan 150 Operation manual

Aqua Medic

Aqua Medic Titan 150 Operation manual

Flo-tech FT394 instruction manual

Flo-tech

Flo-tech FT394 instruction manual

Chef's Choice Diamond UltraHone 312 user manual

Chef's Choice

Chef's Choice Diamond UltraHone 312 user manual

d & b audiotechnik E6530 Mounting instructions

d & b audiotechnik

d & b audiotechnik E6530 Mounting instructions

REV IComfort Operating	 instruction

REV

REV IComfort Operating instruction

AutomationDirect DFT-AN-1A quick start guide

AutomationDirect

AutomationDirect DFT-AN-1A quick start guide

Heath Zenith 7762 manual

Heath Zenith

Heath Zenith 7762 manual

Chef's Choice Diamond Hone 440 user manual

Chef's Choice

Chef's Choice Diamond Hone 440 user manual

ICON Mobile Umini VST user manual

ICON

ICON Mobile Umini VST user manual

Clear-Com FreeSpeak Edge quick start guide

Clear-Com

Clear-Com FreeSpeak Edge quick start guide

AOK HELIOS AC302-02 BI quick start guide

AOK

AOK HELIOS AC302-02 BI quick start guide

Rcom MINI user guide

Rcom

Rcom MINI user guide

Blue Wave NG1205 Assembly instructions

Blue Wave

Blue Wave NG1205 Assembly instructions

ICON Umix1008Rack-VST user manual

ICON

ICON Umix1008Rack-VST user manual

Turboair TBC-24Sx-N series Installation and operation manual

Turboair

Turboair TBC-24Sx-N series Installation and operation manual

Baicells Nova-227 installation guide

Baicells

Baicells Nova-227 installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.