eltherm ELTC-15 User manual

Documentation
Measurement and Control
Type: ELTC-15
Content
1. Installation instructions
2. Data sheets
3. Declarations of conformity

eltherm GmbH
Ernst-Heinkel-Str. 6-10
57299 Burbach
T.: +49 2736 4413-0
F.: +49 2736 4413-50
BU-101
Bedienungsanleitung für
Temperaturregler ELTC/L-15
Autor
Peter Schmidt
Revision 0
18.12.2018
BU-101
Bedienungsanleitung für
Temperaturregler ELTC-15
Operating Manual for
Temperature Controller ELTC-15
(Artikel-Nr. / Part No. 0621500)

BU-101
Bedienungsanleitung für
Temperaturregler ELTC-15
Autor
Peter Schmidt
Revision 0
14.09.2015
2 / 15
Inhalt
1. Allgemein / Product Description .......................................................................................3
2. Funktionsbeschreibung / Functional Description...............................................................3
3. Bedienung / Operation .....................................................................................................4
3.1 Parameter aufrufen und verändern / Changing Parameters .............................................. 4
3.2 Schutz gegen unautorisierte Bedienung / Parameter Protection ....................................... 4
3.3 Autoscrolling / Autoscrolling ............................................................................................... 5
4. Fehlermeldungen / Error Messages ..................................................................................5
4.1 Fehlercodes / Error Codes................................................................................................... 5
4.2 Meldungen zum Rampenstatus / Ramp Status Codes ........................................................ 5
5. Parameter und deren Bedeutung / Parameter Explanation...............................................6
5.1 Modus Freigaberelais / Releasing Relay Mode ................................................................... 8
5.2 Modus Alarmrelais / Alarm Relay Mode ............................................................................. 8
6. Rampenmodi / Ramp Modes ............................................................................................8
6.1 Rampenstart / Start of Ramp .............................................................................................. 8
6.2 Pause / Pause ...................................................................................................................... 8
6.3 Rampe kontrolliert abbrechen / controlled cancellation of Ramp ..................................... 9
6.4 Rampe sofort abbrechen / immediate cancellation of Ramp ............................................. 9
7. Technische Daten / Technical Data ...................................................................................9
8. Installation / Sicherheitshinweise / Installation / Safety Instructions..............................11
9. Bauteilzeichnung / Drawing ............................................................................................12
10. Lieferumfang / Purchase parts package: .........................................................................13
11. Verwendung Verschraubungen / Using glands ................................................................14

BU-101
Bedienungsanleitung für
Temperaturregler ELTC-15
Autor
Peter Schmidt
Revision 0
14.09.2015
3 / 15
1. Allgemein / Product Description
Temperaturregler für Heizanwendungen wie Heizleitungen in Industrieanlagen, mit Lastrelais,
Alarmrelais und programmierbarer Rampenfunktion. Temperaturfühler Pt100 in 3- oder 2-Leitertechnik
und
Thermoelement Typ K.
Temperature controller for heating applications with output relay, alarm relay and programmable
temperatureramp.Thecontrollerisdesignedtooperatewith3-wireor2-wirePt100RTDtemperature sensors
as well as with a thermocouple type K.
2. Funktionsbeschreibung / Functional Description
UnterschreitetderIst-Wert(P01)deneingestelltenSollwert(P10abz.HystereseP11),soschaltetdas Relais K1
die Heizung ein. Das integrierte Alarmrelais ermöglicht über einen Wechselkontakt
Fehlermeldungen bei
Über- / Untertemperatur, Sensor-Unterbrechung oder Sensor-Kurzschluss. Bei Sensorfehlern schaltet das
Relais K1, abhängig von der Konfiguration des Reglers, die Heizleitung aus
bzw. ein.
Iftheactualtemperature(P01)fallsbelowthecontrolsetpoint(P10minushysteresisP11),relayK1will switch
heatingcircuitON.Theintegrated alarmrelayprovideserrormessaging(viaSPDTcontact)to
indicate over-/
under temperature, sensor-interrupt or short circuit. During sensor malfunctions, the relay
K1 switches
continuously on or off, depending on configuration.
ein/ on = Rampe aktiv / ramp effective
ein/on
Lastrelais EIN
Heater Relay ON ein/ on
Alarmrelais aktiviert (=offen)
Blinken/blinking= Alarm relay activated
Funktion verzögert (=contact open)
Functiondelayed
Blinken/ blinking =
Funktion verzögert
Erhöhen von Werten Function delayed
Increase values
Programmiertaste
Verringern von Werten Programming mode
Decrease values
Bitte Sicherheitshinweise beachten!
Please Note Safety Instructions!
Vor Inbetriebnahme Betriebsanleitung sorgfältig lesen! Entstehen durch Nichtbeachtung
Schäden, erlöschen die Garantieansprüche. Diese Dokumentation wurde mit größter Sorgfalt
erstellt, dennoch können wir für die vollständige Richtigkeit keine Garantie übernehmen.
Please read this manual carefully before using this product. Warranty claims cannot be
considered in case of damage caused by failure to comply with these operating instructions!
This documentation was compiled with utmost care, however, we cannot guarantee for its
correctness in everyrespect.

BU-101
Bedienungsanleitung für
Temperaturregler ELTC-15
Autor
Peter Schmidt
Revision 0
14.09.2015
4 / 15
3. Bedienung / Operation
Die Bedienung gestaltet sich sehr einfach. Nach dem Einschalten erscheint die Typennummer des
Gerätes (C15) und nach ca. drei Sekunden der gemessene Istwert. Bei kurzem Drücken der Taste
„P“ erscheint die Anzeige „Set“ und anschließend die Anzeige des Sollwertes mit automatischem
Rücksprung nach 5 Sekunden. Wird die Taste „P“ ca. 3 Sek. gedrückt, gelangt man in die Parameterliste
„P10“. Hält man die Taste „P“ für weitere 3 Sek. gedrückt, wird " dC" für Grad Celsius oder " dF" für
Grad Fahrenheit angezeigt.
Controller operation is very simple. After power-on, the type number of the controller appears (C15),
followed by a 3 second delay after which the actual temperature will be displayed. Upon a short
duration press of the “P” button, “Set” is displayed, followed by the set temperature, with an
automatic return to the main display after 5 seconds. Pressing button “P” for a duration of 3 seconds
provides access to parameter list “P10”. Pressing button “P” for an additional 3 seconds provides
display “P” of “dC” for degrees Centigrade or “dF” for degrees Fahrenheit.
3.1 Parameter aufrufen und verändern / Changing Parameters
Um die Parameterliste zu erreichen muss „P“ gedrückt und ca. 3 Sek. gehalten werden, bis „P10“
erscheint. / For access to the parameter lists, press and hold the „P“ button for 3 seconds until „P10“
appears.
•
„P“ 3 sec.drücken
Parameter-Nr.erscheint
•
„▲/▼“drücken
Parameter auswählen
•
„P“ nochmals
Parameterwert sichtbar
•
„▲/▼“drücken
Parameterwert verändern
•
„P“ nochmals
Neuer Wert gespeichert, zurück
zur Parameter-Nr.
•
„▲/▼“drückenbis„P1“oderT>1Min.
Eingabemodus verlassen
•
•
Press „P“ for 3 sec
parameter No. appears
•
„▲/ ▼“
select parameter
•
„P“ again
parameter value visible
•
„▲/ ▼“
change parameter value
•
„P“ again
new value is
saved,
back to
parameter No.
•
Press „▲/ ▼“until „P1“ or T>1 Min.
Exit settings menu
3.2 Schutz gegen unautorisierte Bedienung / Parameter Protection
Der Regelsollwert ist grundsätzlich ungehindert einstellbar, sofern er nicht durch P13/14 begrenzt wird.
Alle anderen Parameter sind durch einen Code geschützt.
Wird ein Code benötigt, zeigt das Display „C00“. Sie stellen mit den Pfeiltasten die nötige Codenummer
ein (C42) und bestätigen mit „P“.
Nach ca. 1 Min. ohne Tastendruck wird der Code erneut angefordert.
The control set point may be changed at any time to within the limits set by P13 and P14. All other
parameters are code protected. If a code is required, the display will indicate „C00“.
Usingthearrowkeys,entertheappropriatecodenumber(C42).Confirmbypressingthe“P”button. If you do not
press any key for approximately 1 minute, the access code is cancelled

BU-101
Bedienungsanleitung für
Temperaturregler ELTC-15
Autor
Peter Schmidt
Revision 0
14.09.2015
5 / 15
3.3 Autoscrolling / Autoscrolling
Mit Halten der ‚▲/ ▼'-Tasten laufen die Werte automatisch weiter.
By keeping pressed the ‚▲/ ▼'-keys, the values scroll automatically.
4. Fehlermeldungen / Error Messages
Bei einem Fehler zeigt das Display einen Fehlercode. Sensorfehler werden ca. 20 Sek. verzögert
angezeigt.
In case of an error condition, the display indicates an error code after a 20 sec. delay.
4.1 Fehlercodes / Error Codes
E01
Pt100 Unterbrechung oder Temperatur > 410°C / Pt100 interrupt or temperature > 410°C
E02 Pt100KurzschlussoderTemperatur<-60°C/Pt100shortcircuitortemperature<-60°C
E03 Pt1003.LeiterfehltoderR>= 10 Ohm/Pt100 3rd wire missing/not connectedorR >= 10 ohm
E04 Thermoelement fehlerhaft /thermocouple fault
C00
Geschützte Parameter, Codeeingabe erforderlich / protected parameters, code entry
required
E07 Fehler Relais K1 offen / Error relay K1 open
E08 Fehler Relais K1 Kurzschluss / Error relay K1 short circuit
E09 Interner Fehler / Internalerror
Bei den Fehlern E07…E09 ist eine weitere Bedienung des Gerätes unterbunden. /
Error codes E07...E09: controller inoperable.
4.2 Meldungen zum Rampenstatus / Ramp Status Codes
rF0 Rampe korrekt beendet / Ramp completed without any issues
rF1
Rampe abgebrochen und kontrolliert heruntergefahren / Ramp cancelled and cooled down in
controlled
manner
rF2 Bandalarm während Betriebs aufgetreten / Bandgap alarm occured at least one time
rF3 Rampe abgebrochen /Ramp cancelled
Der Rampenstatus wird durch blinkende Anzeige im Wechsel mit Parameter P01 angezeigt (3 sek.
P01, 1 sek.
Rampenstatus). Zurück zur Normalanzeigegelangt man mit Taste „P“
The rFx display information is displayed alternating to the P01 parameter (3sec P01; 1sec “rFx”)
The ramp state
information "rFx" can be cleared by pressing button "P"
Gerätetyp feststellen / Check of device type
Nach dem Einschalten erscheint die Typennummer des Gerätes („C15“) für ca. drei Sekunden.
After power-on, the type number of the controller (“C15”) is displayed for 3 seconds.

BU-101
Bedienungsanleitung für
Temperaturregler ELTC-15
Autor
Peter Schmidt
Revision 0
14.09.2015
6 / 15
5. Parameter und deren Bedeutung / Parameter Explanation
P01 .. Istwert am Temperatursensor (nur Anz)
P10 .. Regelsollwert
Wirkt auf Relais 1, Bereich P13...P14, [5°C]
P11
..
Schalthysterese
von P10
Bereich 2...P41-1K, [2K]
P12 .. Mindest-Stillstandszeit (Relais K1)
0..30.0 Min., [0.0 Min, Auflösung 0,1Min.]
P13
.. Größter einstellbarerSollwert
Bereich P14..+950°C,[+950°C]
P14 .. Kleinster einstellbarer Sollwert
Bereich -50°C...P13, [0°C]
P20 .. Fühlertyp
0 = Pt100, 3-Draht, °C (Auflösung 1K)
[1]=Pt100,2-Draht,°C(Auflösung1K)
2=Pt100,3-Draht,°F(Auflösung2°F)
3=Pt100,2-Draht,°F(Auflösung2°F)
4=ThermoelementK,°C(Auflösung1K)
5 = Thermoelement K, °F (Auflösung 2°F)
P21 .. Fühlerkorrektur -30...+10K, [0]
P30
..
Übertemperaturalarm
P31...999°C [999°C]
P31 .. Untertemperaturalarm
-60...P30, [-60°C]
P32 .. Alarmverzögerung im Betrieb
0...99 Min., [0.0 Min., Auflösung 0,1 Min.]
P33 .. Alarmverzögerung nach Einschalten
0...500 Min., [0 Min.]
P34 .. Alarmrelais Modus (Relais K2)
0=RelaisK2(aktiv)ziehtbeiSensorfehleran
LastrelaisK1fällt bei Sensorfehlerab
[1]=RelaisK2(passiv)fälltbeiSensorfehlerab
LastrelaisK1fälltbeiSensorfehlerab
2 = K2 Arbeitet als Freigaberelais
Lastrelais
K1 fällt bei Sensorfehler ab
3=RelaisK2(aktiv)ziehtbeiSensorfehleran
LastrelaisK1ziehtbeiSensorfehleran
4=RelaisK2(passiv)fälltbeiSensorfehlerab
LastrelaisK1ziehtbeiSensorfehleran
5 = K2 Arbeitet als Freigaberelais
Lastrelais
K1 zieht bei Sensorfehler an
P40…Rampenfunktion
0…1 [1] =: Rampe inaktiv, 1: Rampe aktiv
P41…Bandalarm-Hysterese
P11+1…11 [5K]
P50…Rampensollwert 1 (Startwert)
Nop,0…950°C [100°C] Nop: inaktiv
P01 ..Actual sensor temp. °C (disp.only)
P10 ..Control Setpoint
Affects relay 1, range P13...P14, [5°C]
P11..SwitchinghysteresisofP10
range 2..P41-1K[2K]
P12 ..Min. Relay Idle Time (Relay K1)
0..30.0Min.,[0.0Min,(Resolution0,1min.]
P13 HighestadjustableControlSetpoint
Range P14...+950°C [+950°C]
P14 ..Lowest adjustable Control Setpoint
Range -50°C...P13. [0°C]
P20 ..Sensor/probe Type
0 = Pt100, 3-wire, °C (Resolution 1K)
[1]=Pt100,2-wire,°C(Resolution1K) 2=
Pt100,3-wire,°F(Resolution2°F) 3=Pt100,2-
wire,°F(Resolution2°F)
4=ThermocoupleK,°C(Resolution1K)
5 =
Thermocouple K, °F (Resolution 2°F)
P21 ..Sensor Correction -30...+10K, [0]
P30 ..High Temp. Alarm Threshold
P31...999°C, [999°C]
P31 ..Low Temp. Alarm Threshold
-60...P30, [-60°C]
P32 ..Alarm Delay while Operation
0...99min.,[0.0Min.,Resolution0,1Min.]
P33 ..Alarm Delay while Power-on
0...500 min., [0 min.]
P34 ..Alarm Relay Mode (Relay K2)
0 = Relay K2 ON at sensor fault Powerrelay
K1OFFatsensorfault
[1] = Relay K2 OFF at sensor fault Power
relayK1OFFatsensorfault
2=RelayK2worksasreleasingrelay Power
relayK1OFFatsensorfault
3 = Relay K2 ON at sensor fault Powerrelay
K1ONatsensorfault
4 = Relay K2 OFF at sensor fault Powerrelay
K1ONatsensorfault
5=RelayK2worksasreleasingrelay Power
relayK1ONatsensorfault
P40…Ramp Mode
0…1[1]=: Rampinactive,1: Rampactive
P41…Band Alarm Hysteresis
P11+1…11 [5K]
P50…Ramp set point 1 (start temperature)
Nop,0…950°C [100°C] Nop: inactive

BU-101
Bedienungsanleitung für
Temperaturregler ELTC-15
Autor
Peter Schmidt
Revision 0
14.09.2015
7 / 15
P51…Zeit für Rampe 1
1…999 Min [30 Min]
P52…Rampensollwert 2
Nop,0…950°C [100°C]
P53…Zeit für Rampe 2
1…999 Min [30 Min]
P54…Rampensollwert 3
Nop,0…950°C [100°C]
P55…Zeit für Rampe 3
1…999 Min [30 Min]
P56…Rampensollwert 4
Nop,0…950°C [100°C]
P57…Zeit für Rampe 4
1…999 Min [30 Min]
P58…Rampensollwert 5
Nop,0…950°C [100°C]
P59…Zeit für Rampe 5
1…999 Min [30 Min]
P60…Rampensollwert 6
Nop,0…950°C [100°C]
P61…Zeit für Rampe 6
1…999 Min [30 Min]
P62…Rampensollwert 7
Nop,0…950°C [100°C]
P63…Zeit für Rampe 7
1…999 Min [30 Min]
P64…Rampensollwert 8
Nop,0…950°C [100°C]
P65…Zeit für Rampe 8
1…999 Min [30 Min]
P66…Rampensollwert 9
Nop,0…950°C [100°C]
P67…Zeit für Rampe 9
1…999 Min [30 Min]
P68…Rampensollwert 10 (Endwert)
Nop,0…950°C [100°C]
P70
…
Anzeige des aktuellen Rampensollwerts
-60…999°C
P71…Anzeige der aktuellen Rampenphase
0 = Rampe aus 1=vor
Sollwert 1
2 = zwischen Sollwert 1 und 2
10 = zwischen Sollwert 9 und 10
WICHTIGER HINWEIS:
P34=3, P34=4 und P34=5 ist nur bei
Frostschutzanwendungen und Einsatz von
selbstregulierenden Heizkabeln zulässig
P51…time for Ramp 1
1…999 Min [30 Min]
P52…Ramp set point 2
Nop,0…950°C [100°C]
P53…time for Ramp 2
1…999 Min [30 Min]
P54…Ramp set point 3
Nop,0…950°C [100°C]
P55…time for Ramp 3
1…999 Min [30 Min]
P56…Ramp set point 4
Nop,0…950°C [100°C]
P57…time for Ramp 4
1…999 Min [30 Min]
P58…Ramp set point 5
Nop,0…950°C [100°C]
P59…time for Ramp 5
1…999 Min [30 Min]
P60…Ramp set point 6
Nop,0…950°C [100°C]
P61…time for Ramp 6
1…999 Min [30 Min]
P62…Ramp set point 7
Nop,0…950°C [100°C]
P63…time for Ramp 7
1…999 Min [30 Min]
P64…Ramp set point 8
Nop,0…950°C [100°C]
P65…time for Ramp 8
1…999 Min [30 Min]
P66…Ramp set point 9
Nop,0…950°C [100°C]
P67…time for Ramp 9
1…999 Min [30 Min]
P68…Ramp set point 10 (end temperature)
Nop,0…950°C [100°C]
P70…Display of the current Ramp set point
-60…999°C
P71… Display of the current Ramp phase
0 = Rampe off
1=reachingsetpoint1
2=reachingsetpoint2
10 = reaching set point 10
IMPORTANT NOTE :
P34=3, P34=4 and P34=5
Is only for frost protection applications and use of
self-regulating heating cables permitted.

BU-101
Bedienungsanleitung für
Temperaturregler ELTC-15
Autor
Peter Schmidt
Revision 0
14.09.2015
8 / 15
5.1 Modus Freigaberelais / Releasing Relay Mode
In diese Betriebsart (P34=2) schaltet das Relais K2 unabhängig von P32 und P33 sobald der Istwert innerhalb
P30 und P31 liegt.
Inthismode(P34=2)relayK2switchesindependentfromP32andP33oncetheactualranges between settings
P30 andP31.
5.2 Modus Alarmrelais / Alarm Relay Mode
(P34 = 0 oder 1): Liegt beim Gerätestart die Isttemperatur unterhalb von P31, wird als Alarmverzögerung
einmalig P33 verwendet, um der Anlage mehr Zeit zu gewähren. Im normalen Betrieb wird P32 als
Alarmverzögerung verwendet.
(P34=0or1):If,afterinitialpoweron,theactualtemperaturefallsbelowP31,P33isusedasthealarm relayto
provideadditionaltimeforwarm-up.Innormaloperatingconditions,P32isusedasalarmdelay parameter.
6. Rampenmodi / Ramp Modes
6.1 Rampenstart / Start of Ramp
Taste “Up” für >5 Sekunden drücken, LED „2“ leuchtet dauerhaft. Liegt die aktuelle Temperatur unter
dem für P50 hinterlegten Wert, wird zunächst auf diesen Wert aufgeheizt. Dann startet die hinterlegte
Rampenfunktion (P50…P68). Liegt die aktuelle Temperatur über dem für P50 hinterlegten Wert,
startet die Rampenfunktion mit der aktuellen Temperatur. Nach Erreichen des letzten hinterlegten
Rampenwertes erlischt LED „2“, anschließend wird der eingestellte Temperatursollwert (P10)
angefahren und dauerhaft gehalten.
Press key „Up“ for >5 seconds, LED “2” is on continuously. If the current temperature is below the
programmed value of P50, the heater will be switched on until that temperature is reached. Then the
programmed ramp (P50…P68) starts. If the current temperature is above the programmed value of
P50, the ramp starts directly with the current temperature. When the last programmed ramp
temperature has been reached, LED “2” is switched off. The workpiece will then be brought to the
temperature set point (P10) and maintained at that temperature continuously.
6.2 Pause / Pause
Taste “Down” für >5 Sekunden drücken, LED „2“ blinkt in gleichmäßigem Takt. Aktuelle Temperatur
wird dauerhaft gehalten. Bei erneutem Drücken der Taste „Down“ für >5 Sekunden wird die Rampe
fortgeführt.
Press key „Down“ for >5 seconds, LED2 blinks with regular pattern. Current temperature will be
maintained permanently. On repeated pressing of key „Down“ for >5 seconds, ramp will be continued.
Wertein[..]sindWerkseinstellungen
Values in [..] are factory set

BU-101
Bedienungsanleitung für
Temperaturregler ELTC-15
Autor
Peter Schmidt
Revision 0
14.09.2015
9 / 15
6.3 Rampe kontrolliert abbrechen / controlled cancellation of Ramp
Taste “UP” und „Down“ gleichzeitig für >5 Sekunden drücken, LED „2“ blinkt wechselnd lang / kurz.
Ausgehend von der aktuellen Temperatur wird die Rampe jetzt mit dem letzten hinterlegten fallenden
Ast heruntergefahren. Nach Erreichen des letzten Rampenwertes erlischt LED „2“, anschließend wird
der eingestellte Temperatursollwert (P10) angefahren und dauerhaft gehalten.
Press keys “Up” and „Down“ simultaneously for >5 seconds, LED2 blinks with long / short pattern.
Starting with the current temperature, ramp will be terminated with the last programmed falling
branch. When the last ramp temperature has been reached, LED “2” is switched off. The workpiece
will then be brought to the temperature set point (P10) and maintained at that temperature
continuously.
6.4 Rampe sofort abbrechen / immediate cancellation of Ramp
Taste “UP” und „Down“ gleichzeitig für >5 Sekunden drücken, LED „2“ blinkt wechselnd lang / kurz.
Taste “UP” und „Down“ ein weiteres Mal gleichzeitig für >5 Sekunden drücken, LED „2“ erlischt. Die
Rampenfunktion ist jetzt inaktiv, der eingestellte Temperatursollwert (P10) wird angefahren und
dauerhaft gehalten.
Press keys “Up” and „Down“ simultaneously for >5 seconds, LED2 blinks with long / short pattern.
Again press keys “Up” and „Down“ simultaneously for >5 seconds, LED2 is off. The ramp is now
inactive, the workpiece will be brought to the temperature set point (P10) and maintained at that
temperature continuously.
7. Technische Daten / Technical Data
Reglertyp
ELTC-15
Betriebsspannung
90…260 VAC, 50/60 Hz
Leistungsaufnahme
max. 5 W
Relais K1
20A bis max 250 VAC
Relais K2
8A bei 250 VAC / 1A bei 24 VAC
Betriebstemperatur
-25...+55°C
Lagertemperatur
-30...+60°C
rel. Luftfeuchte
max. 80%
Einstellbereich
-50…+410°C (mit Pt100) / -50...+999°C (mit Thermoelement Typ K)
Anzeigebereich / Auflösung
1K (2°F)
Genauigkeit
±1K,±2Digits(mit Pt100) / +/-0.5%F.S. ( mit ThermoelementTyp K)
Display / Relaisanzeige
LED, rot, 11mm
Anschlussklemmen
Federkraftklemme
Fühler: 0,2…1,5mm² Kupferleitung, Abisolierlänge 9…10mm
Sonstige:
0,1…2,5mm² Kupfer eindrähtig, Abisolierlänge 5…6mm
Meßstrom / Leitungslänge
Pt100
max. 1 mA / 140m mit 0,5mm² bzw. 280 m mit 1mm² (10 Ohm)
Schutzart
IP 65; spannungsführende Teile mit Berührschutz
controller type
ELTC-15
operating voltage
90…260 VAC, 50/60 Hz
power consumption
max. 5 W

BU-101
Bedienungsanleitung für
Temperaturregler ELTC-15
Autor
Peter Schmidt
Revision 0
14.09.2015
10 / 15
Relay K1
20A at max 250 VAC
RelayK2
8A at 250 VAC / 1A at 24 VAC
ambient temperature
-25...+55°C
humidity
max. 80%
storage temperature
-30...+60°C
adjustable range
-50…+410°C (with Pt100) / -50...+999°C (with thermocouple type K)
display range / resolution
1K (2°F)
accuracy
±1K,±2 Digits (with Pt100)/ +/-0.5%F.S. (with thermocouple typeK)
display / relay indicators
LED, red, 11mm
terminals
Sensor: 0,2…1,5mm² copper wire, (exposed wire) length 9…10mm
Others: 0,1…2,5 mm² copper single
-wire, length (exposed wire)
5…6mm
Measuring current / cable
length
max. 1 mA / 140m with 0,5mm² or 280m with 1mm² (10 Ohm)
IP rating
IP 65; live parts with touch guard

BU-101
Bedienungsanleitung für
Temperaturregler ELTC-15
Autor
Peter Schmidt
Revision 0
14.09.2015
11 / 15
8. Installation / Sicherheitshinweise / Installation / Safety Instructions
•
Elektr. Anschluss / Inbetriebnahme muss durch eine Elektrofachkraft
durchgeführt
werden.
/ Electrical installation/commissioning must be performed by authorized personnel.
•Dieeinschlägigen örtlichen Sicherheitsvorschriften sind zu beachten.
/ Please note local safety requirements!
•Anschlusswerte gemäß Typenschildbeachten.
/ Please note maximum ratings as per provided type label!
•
Bei Wahl des Aufstellungsortes die IP-Schutzart und zulässige Betriebs-
temperatur
beachten. Vorteilhaft sind Orte, die vor direktem Niederschlag und Sonneneinstrahlung
geschützt sind. Betrieb nur mit geschlossenem Deckel, angezogenen Verschraubungen /
Blindstopfen und eingebauten Dichtungen.
/ Observe IP-rating and permitted operating temperature when choosing the
locationof
thecontroller.Preferredmountinglocationsofferprotection against precipitation and
direct sunlight Operate only with closed lid, tightened cable entries and installed
sealings.
Zugbeanspruchung und Torsion der angeschlossenen Leitungen vermeiden
/ Avoid torsion and pulling stress of the cables terminated to the controller
Die Fühlerleitungen müssen bei Verlängerung abgeschirmt sein, die Abschirmung
ist einseitig nahe des Reglers zu erden. Die Leitung darf nicht parallel zu
netzspannungsführenden Leitungen verlegt werden. Der Leitungswiderstand darf
in der Summe 10 Ohm nicht überschreiten. Nach Einschalten des Reglers zeigt das
Display den aktuellen Istwert./ If you have to lengthen the sensor cables, use a
shielded type with one end of the shield connected to a ground terminal near the
controller. Don‘t install
the cable in parallel to mains voltage wires. The sum of the wire resistance should
not exceed 10 ohms. After the power has been switched on, the controller will
display the actual sensor temperature.

BU-101
Bedienungsanleitung für
Temperaturregler ELTC-15
Autor
Peter Schmidt
Revision 0
14.09.2015
12 / 15
9. Bauteilzeichnung / Drawing

BU-101
Bedienungsanleitung für
Temperaturregler ELTC-15
Autor
Peter Schmidt
Revision 0
14.09.2015
13 / 15
10. Lieferumfang / Purchase parts package:
Menge
QTY
Artikel
Item
Position
1
Regler / controller ELTC-15
-
1
Betriebsanleitung / manual BU-101
-
2
M25x1,5 Kabelverschraubung / cable gland
[3] + [4]
2
M25 O-Ring / O-ring seal
[3] + [4]
2
M25 2x6mm Mehrfachdichteinsatz / Multiple seal
[3] + [4]
1
M25 Gegenmutter / locking nut
[3]
2
M20x1,5 Kabelverschraubung / cable gland
[2] + [5]
2
M20 O-Ring / O-ring seal
[2] + [5]
1
M20 Gegenmutter / locking nut
[5]
1
M12x1,5 Kabelverschraubung / cable gland
[1]
1
M12 O-Ring / O-ring seal
[1]
1
Klemmenabdeckung / terminal cover
[7]
2
Wiederlösbare Nieten / removeable rivets
[6]

BU-101
Bedienungsanleitung für
Temperaturregler ELTC-15
Autor
Peter Schmidt
Revision 0
14.09.2015
14 / 15
11. Verwendung Verschraubungen / Using glands
Zuleitung
Supply cable
Alarmkontakt
Alarm contact
Temp. Fühler
Temperature sensor
ELSR-xx
ELP-xx
ELK-xx
ELW-xx
Klemmkasten
Junction box
EL-CLIC P
Position in Zecinung
Position in drawing
Verschraubung
Gland
Beschreibung
Description
Klemmbereich
Clamping
range
X
[1] M12 und O-Ring
M12 and O-ring seal
Temperatur Fühler
Temperature sensor
3-6,5
mm
X
X
X
[2]
M20 und O-Ring
M20 and O-ring seal
ELW-x einseitiger
Anschluss, EL-CLIC P,
Klemmkasten
ELW-x single ended, EL-
CLIC P, junction box
6-13
mm
X
[2] M20 und O-Ring 2x6mm
M20 and O-ring seal
ELK-x beidseitiger
Anschluss
ELK-x double-ended
2x6
mm
X
[2]
M20, aus dem Anschlussset
ELVB-SR
M20, part of connection set
ELVB-SR
ELSR-x
X
[2]
M20, aus dem Anschlussset
ELVB-ELP
M20, part of connection set
ELVB-ELP
ELP-x
X
X
X
[3]
M25 und O-Ring und
Gegenmutter
M25 and O-ring seal and
locking nut
Anschlusskabel für
zweiten Heizkreis: ELW-x
einseitiger Anschluss, EL-
CLIC P, Klemmkasten
Connection cable for second
heating circuit: ELW-x single
ended, EL-CLIC P, junction box
6-13
mm
X
[3]
M25 und O-Ring und
Gegenmutter
M25 and O-ring seal and
locking nut
Anschlusskabel für
zweiten Heizkreis:
ELK-x beidseitiger
Anschluss
Connection cable for second
heating circuit:
ELK-x double sided
2x6
mm
X
[3]
M25, im Anschlussset
ELVB-SR
und Gegenmutter
M25, part of connection set
ELVB-SR and locking nut
Anschlusskabel für
zweiten Heizkreis:
ELSR-x
Connection cable for second
heating circuit:
ELSR-x
X
[3]
M25, im Anschlussset
ELVB-ELP
und Gegenmutter
M25, part of connection set
ELVB-ELP and locking nut
Anschlusskabel für
zweiten Heizkreis:
ELP-x
Connection cable for second
heating circuit:
ELSR-x
X
[4] M20 und O-Ring
M20 and O-ring seal
Zuleitung
Supply cable
6-12
mm
X
[5]
M20 und O-Ring und
Gegenmutter
M20 and O-ring seal and
locking nut
Anschlusskabel
Alarmkontakt
Connection cable
alarm contact
6-12
mm

BU-101
Bedienungsanleitung für
Temperaturregler ELTC-15
Autor
Peter Schmidt
Revision 0
14.09.2015
15 / 15
RTEW
Konformitätserklärung / Declaration of conformity
Wir erklären, dass das beschriebene Produkt die Richtlinien 2014/35/EU, 2014/30/EU
und 2011/65/EU voll erfüllt. Wenn Sie eine detaillierte Konformitätserklärung
benötigen, sprechen Sie uns bitte an.
We declare that the described product is in full compliance with the directives
2014/35/EU, 2014/30/EU and 2011/65/EU. If a detailed declaration of conformity is
required, please contact us.

6.26 Measurement and Control
Advantages:
LED display operable down to -25 °C
Programmable 0 °C up to +999 °C
For switching 20 A resistive load with
hybridrelay
Signaling contact (configurable to operate
either as alarm or release contact, potential-free)
Suitable for Pt100 with 2 or 3 wires and
Thermocouples type K
For connection of up to 2 heating cables
(only self-regulating)
Operating voltage: 90 - 260 VAC / 50/60 Hz
Rampmode functionality
Applications:
Industrial applications
Applications at high temperatures
The ELTC-15 is an electronic temperature controller with digital display and rampmode functionality. It supports
a 2- or 3-wire Pt100 input or thermocouple type K. After having evaluated the actual and preset values, the ap-
propriate output relays are switched, depending on the configuration.
Cable glands and terminals are provided for the power connection. The unit is supplied in a weather proof plas-
tic enclosure, with a transparent cover.
Temperature Controller
Electronic
Type ELTC-15

6.27www.eltherm.com
Operating voltage 90-260 VAC 50/60 Hz
Power consumption Max. 4 mA, < 5 W
Switching capacity relay 1 20 A with hybridrelay
Switching capacity relay 2 8 A, changover contact
(alarm)
Operating temperature -25 up to +55 °C
Storage temperature -30 up to +60 °C
Display range -50 up to +999 °C
Adjustable range 0 up to +950 °C,
optional configuration
Sensor connection Pt100 2-wire, 3-wire,
thermocouple type K
Display LED, red
IP rating IP 65
Dimensions (wx hxd) 130 x 130 x 75 mm
polycarbonate enclosure
Technical Information
Data
Type ELTC-15
Wiring diagram
Type Designation Art. No.
ELTC-15 Standard: set with cable glands,
reducer and blind cover 0621500
Sensors and display: It is possible to use three types of sensors, either Pt100/2-wire, Pt100/3-wire or thermocouples type K. Optional display of °C or °F
values. In case of use of a Pt100/2-wire unit the actual temperature value can be corrected. Range +/- 10K or +/-18F, respectively. In case of use of a Pt100/3-
wire unit the temperature is automatically corrected. Also suitable for use with ELTF-PTEx 1 and 2 sensor.
Relay conguration: relay 1: regulator, relay 2: alarm / temperature reached
Temperature alarm: If the actual value deviates from the preset limit values, an alarm is given and transmitted via alarm relay K2.
Rampmode functionality:
Specific heating-up and defined cooling with counter heating to avoid
rapid cooling of the heated components.
T (°C)
1
20
100
200
300
400
2 3 4 5

Other manuals for ELTC-15
1
Table of contents
Other eltherm Temperature Controllers manuals

eltherm
eltherm ELTC-14 User manual

eltherm
eltherm ELTC-14P User manual

eltherm
eltherm Ex-TC It Series User manual

eltherm
eltherm ELTC-14 User manual

eltherm
eltherm ELTC-41 User manual

eltherm
eltherm ELTC-15 User manual

eltherm
eltherm ELTF User manual

eltherm
eltherm ELTC-14 User manual

eltherm
eltherm ELTC-W User manual

eltherm
eltherm ELTC-14P User manual