manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Emerson
  6. •
  7. Controllers
  8. •
  9. Emerson Dixell XR06CH BMB Wiring diagram

Emerson Dixell XR06CH BMB Wiring diagram

Other Emerson Controllers manuals

Emerson CASH A-401 User manual

Emerson

Emerson CASH A-401 User manual

Emerson Bettis XTE3000 Operating and maintenance instructions

Emerson

Emerson Bettis XTE3000 Operating and maintenance instructions

Emerson Fisher FIELDVUE DVC6200 HW2 Configuration guide

Emerson

Emerson Fisher FIELDVUE DVC6200 HW2 Configuration guide

Emerson unidrive m201 User manual

Emerson

Emerson unidrive m201 User manual

Emerson YARWAY Series Operation and maintenance manual

Emerson

Emerson YARWAY Series Operation and maintenance manual

Emerson Dixell XC15CX Wiring diagram

Emerson

Emerson Dixell XC15CX Wiring diagram

Emerson Dixell XR03CH Wiring diagram

Emerson

Emerson Dixell XR03CH Wiring diagram

Emerson CSB700 Series User manual

Emerson

Emerson CSB700 Series User manual

Emerson PNC001-A Series User manual

Emerson

Emerson PNC001-A Series User manual

Emerson Fisher 133H User manual

Emerson

Emerson Fisher 133H User manual

Emerson PACSystems RX3i IC695CPE330 User manual

Emerson

Emerson PACSystems RX3i IC695CPE330 User manual

Emerson Fisher FIELDVUE DVC6200 SIS Configuration guide

Emerson

Emerson Fisher FIELDVUE DVC6200 SIS Configuration guide

Emerson dixell XW20LT Wiring diagram

Emerson

Emerson dixell XW20LT Wiring diagram

Emerson Fisher 627 User manual

Emerson

Emerson Fisher 627 User manual

Emerson FXMP25 User manual

Emerson

Emerson FXMP25 User manual

Emerson Fisher Y692 User manual

Emerson

Emerson Fisher Y692 User manual

Emerson Asset Management Tag User manual

Emerson

Emerson Asset Management Tag User manual

Emerson Keystone EPI2 User manual

Emerson

Emerson Keystone EPI2 User manual

Emerson E2 User manual

Emerson

Emerson E2 User manual

Emerson Fisher easy-Drive 200L User manual

Emerson

Emerson Fisher easy-Drive 200L User manual

Emerson EIM HQ Series User manual

Emerson

Emerson EIM HQ Series User manual

Emerson Affinity User manual

Emerson

Emerson Affinity User manual

Emerson Double-Acting Series Installation instructions

Emerson

Emerson Double-Acting Series Installation instructions

Emerson FISHER SR8 User manual

Emerson

Emerson FISHER SR8 User manual

Popular Controllers manuals by other brands

Sunricher SR-ZV9003T3-RGBW-US Installation

Sunricher

Sunricher SR-ZV9003T3-RGBW-US Installation

Ksenia intro Installation and configuration manual

Ksenia

Ksenia intro Installation and configuration manual

Inovance CAN200 Series manual

Inovance

Inovance CAN200 Series manual

Gauzy LC6 FLEX Controller Installation and operation guide

Gauzy

Gauzy LC6 FLEX Controller Installation and operation guide

Viking SLP-1 Technical practice

Viking

Viking SLP-1 Technical practice

CKD KBX-30E-U Series instruction manual

CKD

CKD KBX-30E-U Series instruction manual

Sharp Energy Sun Flux User manual & installation guide

Sharp Energy

Sharp Energy Sun Flux User manual & installation guide

Yamaha RCX40 user manual

Yamaha

Yamaha RCX40 user manual

AB Quality PowerFlex 400 Frames D-H Service bulletin

AB Quality

AB Quality PowerFlex 400 Frames D-H Service bulletin

Yamaha MJC8 owner's manual

Yamaha

Yamaha MJC8 owner's manual

AL-KO ATC operating instructions

AL-KO

AL-KO ATC operating instructions

Savant SmartControl 2 Deployment guide

Savant

Savant SmartControl 2 Deployment guide

GameSir T3S user manual

GameSir

GameSir T3S user manual

Kostal inveor operating manual

Kostal

Kostal inveor operating manual

CoCo ACM-LV24 Quick installation guide

CoCo

CoCo ACM-LV24 Quick installation guide

Brooks SLA5810/20 Installation and operation manual

Brooks

Brooks SLA5810/20 Installation and operation manual

SIGMA TEK SR 011 Technical manual

SIGMA TEK

SIGMA TEK SR 011 Technical manual

Aprilaire 76 installation instructions

Aprilaire

Aprilaire 76 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

1598040340 XR06CH BMB GB r1.0 20.02.2018 XR06CH 1/3
DIGITAL CONTROLLER WITH DEFROST AND
FANS MANAGEMENT
XR06CH BMB
1General warnings.............................................................................................................................................1
2General description..........................................................................................................................................1
3Regulation........................................................................................................................................................1
4Defrost..............................................................................................................................................................1
5Fans..................................................................................................................................................................1
6Front panel commands....................................................................................................................................1
7Parameters.......................................................................................................................................................2
8Digital inputs (ONLY XR03CX)........................................................................................................................2
9Installation and mounting.................................................................................................................................2
10 Electrical connections......................................................................................................................................2
11 Howto usethe hotkey....................................................................................................................................2
12 Alarmsignalling................................................................................................................................................2
13 Technical data..................................................................................................................................................3
14 Connections ..................................................................................................................................................... 3
15 Default setting values....................................................................................................................................... 3
1GENERAL WARNINGS
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick
reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot be
used as a safety device.
Checkthe application limits before proceeding.
Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring
the same and unchanged functionality.
1.2 SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden
temperature changes with high atmospheric humidity to prevent formation of condensation
Warning: disconnect all electrical connections before any kind of maintenance.
Fit the probe where it is not accessible by the End User. The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.p.A.” (see
address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply are separated and far enough from each
other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with
inductive loads could be useful.
Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring the
same and unchanged functionality.
2GENERAL DESCRIPTION
The XR06CH, format 32 x 74 x 60 mm, is microprocessor based controller, suitable for applications
on medium or low temperature ventilated refrigerating units. It has three relay outputs to control
compressor, fan, and defrost which can be either electrical or reverse cycle (hot gas). The device is
also provided with 2 NTC probe inputs, the first one for temperature control and the second one to be
located onto the evaporator, to control the defrost termination temperature and to managed the fan
and it’s provided with a configurable digital input. With the HOTKEY it’s possible to program the
instrument in a quick and easyway.
3REGULATION
The regulation is performed according to
the temperature measured by the
thermostat probe with a positive
differential from the set point: if the
temperature increases and reaches set
point plus differential the compressor is
started and then turned off when the
temperature reaches the set point value
again.
In case of fault in the thermostat probe the start and stop of the compressor are timed through
parameters “Cy”and “Cn”.
4DEFROST
Two defrost modes are available through the “td” parameter:
td=EL defrost through electrical heater (compressor OFF)
td=in hot gas defrost (compressor ON).
Other parameters are used to control the interval between defrost cycles (id) ), its maximum length
(Md) and two defrost modes: timed or controlled by the evaporator’s probe. At the end of defrost
dripping time is started, its length is set in the dt parameter. With dt=0 the dripping time is disabled.
5FANS
With FC parameter it can be selected the fans functioning:
FC=cn willswitch ON and OFF with the compressor and not run during defrost
FC=on fans willrun even if the compressor is off, and not run during defrost
After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fd” parameter.
FC=cy fans willswitch ON and OFF with the compressor and run during defrost
FC=oY fans willrun continuously also during defrost.
An additional parameter “FS” provides the setting of temperature, detected by the evaporator probe,
above which the fans are always OFF. This is used to make sure circulation of air only if his
temperature is lower than set in “FS”
5.1 FANS AND DIGITAL INPUT
When the digital input is configured as door switch iF=do, fans and compressor status depends on the
dC parameter value:
dC=no normal regulation;
dC=Fn fans OFF;
dC=cP compressor OFF;
dC=Fc compressor and fansOFF.
When rd=y, the regulation restart with door open alarm.
6FRONT PANEL COMMANDS
To display target set point, in
programming mode it selects a
parameter or confirm an
operation
To start a manual defrost
In programming mode it browses
the parameter codes or increases
the displayed value
In programming mode it browses
the parameter codes or
decreases the displayed value
KEYS COMBINATION
+
To lock or unlock the keyboard
+
To enter in programming mode
+
To return to room temperature display
LED MODE SIGNIFICATO
On Compressor enabled
Flashing Anti short cycle delay enabled (AC parameter)
On Defrost in progress
Flashing Dripping in progress
On Fans output enabled
Flashing Fans delayafter defrost
On Measurement unit
Flashing Programming mode
On Measurement unit
Flashing Programming mode
6.1 HOW TO SEE THE SET POINT
1. Push and immediately release the SET key, the set point will be showed;
2. Push and immediately release the SET key or wait about 5s to return to normal visualisation.
6.2 HOW TO CHANGE THE SETPOINT
1. Push the SET key for more than 2 seconds to change the Set point value;
2. The value of the set point will be displayed and the “°C” or “°F” LED starts blinking;
3. To change the Set value push the or arrows.
4. To memorise the new set point value push the SET keyagain or wait 10s.
6.3 HOW TO START A MANUAL DEFROST
Push the DEF key for more than 2 seconds and a manual defrost willstart
6.4 HOW TO CHANGE A PARAMETER VALUE
To change the parameter’s value operate as follows:
1. Enter the Programming mode by pressing the SET+ keys for 3s (“°C” or “°F” LED starts
blinking).
2. Select the required parameter. Press the “SET” key to display its value
3. Use or to change its value.
4. Press “SET”to store the new value and move to the following parameter.
To exit: Press SET+ or wait 15s without pressing a key.
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.
6.5 HIDDEN MENU
The hidden menu includes all the parameters of the instrument.
HOW TO ENTER THE HIDDEN MENU
1. Enter the Programming mode by pressing the SET+ keys for 3s (“°C” or “°F” LED starts
blinking).
2. Released the keys, then push again the SET+ keys for more than 7s. The L2 label will be
displayed immediatelyfollowed from the Hyparameter.
NOW YOU ARE IN THE HIDDEN MENU.
3. Select the required parameter.
4. Press the “SET” key to display its value
5. Use or to change its value.
6. Press “SET”to store the new value and move to the following parameter.
To exit: Press SET+ or wait 15s without pressing a key.
NOTE1: if there aren’t any parameter in L1, after 3s the “nP” message is displayed. Keep the keys
pushed till the L2 message is displayed.
NOTE2: the set value is stored even when the procedure is exited by waiting the time-out to expire.
HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST
LEVEL AND VICEVERSA.
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user
level) by pressing SET+ . In HIDDEN MENU when a parameter is present in First Level the decimal
point is on.
1598040340 XR06CH BMB GB r1.0 20.02.2018 XR06CH 2/3
6.6 TO LOCK THE KEYBOARD
1. Keep pressed for more than 3s the and keys.
2. The “OF” message will be displayed and the keyboard will be locked. If a key is pressed more
than 3s the “OF” message will be displayed.
6.7 TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the and keys tillthe “on” message willbe displayed.
7PARAMETERS
REGULATION
Hy Differential: (0,1°C 25°C / 1°F ÷ 45°F) Intervention differential for set point. Compressor Cut
IN is SET POINT + differential (Hy). Compressor Cut OUT is when the temperature reaches the
set point.
LS Minimum SET POINT: (-55°C÷SET/-67°F÷SET): Sets the minimum value for the set point..
US Maximum SET POINT: (SET÷99°C/ SET÷99°F). Set the maximum value for set point.
ot First probe calibration: (-9.9÷9.9°C / -17°F ÷ 17°F) allows to adjust possible offset of the first
probe.
P2 Evaporator probe presence: n= not present; y= the defrost stops by temperature.
oE Second probe calibration: (-9.9÷9.9°C / -17°F ÷ 17°F) allows to adjust possible offset of the
second probe.
od Outputs activation delay at start up: (0÷99min) This function is enabled at the initial start up of
the instrument and inhibits anyoutput activation for the period of time set in the parameter.
AC Anti-short cycle delay: (0÷50 min) minimum interval between the compressor stop and the
following restart.
Cy Compressor ON time with faulty probe: (0÷99 min) time during which the compressor is active
in case of faulty thermostat probe. With Cy=0 compressor is always OFF.
Cn Compressor OFF time with faulty probe: (0÷99 min) time during which the compressor is OFF
in case of faulty thermostat probe. With Cn=0 compressor is always active.
DISPLAY
CF Measurement unit: (°C÷°F) °C =Celsius; °F =Fahrenheit. WARNING: When the measurement
unit is changed the SET point and the values of the parameters Hy, LS, US, oE, o1, AU, AL
have to be checked and modified ifnecessary.
rE Resolution (only for °C):(dE ÷ in) dE= decimal between -9.9 and 9.9°C; in= integer
Ld Default display: (P1 ÷ P2) P1= thermostat probe; P2= evaporator probe. SP=Set point (only
XR04CX)
dy Display delay: (015 min.) when the temperature increases, the display is updated of 1 °C/1°F
after this time.
DEFROST
td Defrost type: (EL – in) EL= electrical heater, compressor OFF; in= hot gas, compressor ON;
dE Defrost termination temperature: (-55÷50°C / -67÷99°F) if P2=Y it sets the temperature
measured by the evaporator probe, which causes the end of defrost.
id Interval between defrost cycles: (0÷99 minutes) Determines the time interval between the
beginning of two defrost cycles.
Md Maximum length for defrost: (0÷99 min. with 0 no defrost) when P2=n, (not evaporator probe:
timed defrost) it sets the defrost duration, when P2 = y (defrost end based on temperature) it sets
the maximum length for defrost.
dd Start defrost delay: ( 0÷99min) Thisis usefulwhen different defrost start times arenecessary to
avoid overloading the plant.
dF Display during defrost: (rt / it / SP/ dF) rt= realtemperature; it= start defrost temperature; SP=
SET-POINT; dF= label dF.
dt Drip time: (0÷99 min) time interval between reaching defrost termination temperature and the
restoring of the control’s normal operation. This time allows the evaporator to eliminate water
drops that might have formed due to defrost.
dP Defrost at power –on: (y÷n) y= at power on defrost starts; n= defrost doesn’t start at power-on
FANS
FC Fans operating mode: (cn, on, cY, oY) cn= in runs with the compressor, OFF during defrost;
on= continuous mode, OFF during defrost;; cY= runs with the compressor, ON during defrost;
oY= continuous mode, ON during defrost.
Fd Fans delay after defrost: (0÷99 min) Interval between end of defrost and evaporator fans start.
FS Fans stop temperature: (-55÷50°C / -67°F ÷ 99°F) setting of temperature, detected by
evaporator probe, above which fans are always OFF.
ALARMS
AU Maximum temperature alarm: (AL÷99°C/99°F) when this temperature is reached the alarm is
enabled, after the “Ad” delay time.
AL Minimum temperature alarm: (-55÷AU°C /-67÷AU°F) when this temperature is reached the
alarm is enabled, after the “Ad” delay time.
Ad Temperature alarm delay: (0÷99 min) time interval between the detection of an alarm condition
and alarm signalling.
dA Exclusion of temperature alarm at startup: (0÷99 min) time interval between the detection of
the temperature alarm condition after instrument power on and alarm signalling.
DIGITAL INPUT
iP Digital input polarity: (oP ÷ cL) oP= activated by closing the contact; cL= activated by opening
the contact;
iF Digital input configuration: (EA/bA/do/dF/Au/Hc) EA= external alarm: “EA” message is
displayed; bA= serious alarm “CA” message is displayed; do= door switch function; dF= defrost
activation; Au =not used; Hc= inversion of the kind of action;
di Digital input delay: (0÷99 min) with iF=EA or bA delay between the detection of the external
alarm condition and its signalling. . With iF=do it represents the delay to activate the door open
alarm.
dC Compressor and fan status when open door: (no/Fn/cP/Fc): no= normal; Fn = Fans OFF; cP
=Compressor OFF; Fc = Compressor and fans OFF;
rd Regulation with door open: (n÷y) n= no regulation if door is opened; Y= when di is elapsed
regulation restarts even if door open alarm is present;
OTHER
d1 Thermostat probe display (read only)
d2 Evaporator probe display (read only)
Pt Parameter code table
rL Software release
8DIGITAL INPUTS (ONLY XR03CX)
The free voltage digital input is programmable in different configurations by the “i1F” parameter.
8.1 DOOR SWITCH (IF=DO)
It signals the door status and the corresponding relay output status through the “dC” parameter: no =
normal (any change); Fn = Fan OFF; CP = Compressor OFF; FC = Compressor and fan OFF.
Since the door is opened, after the delay time set through parameter “di”, the door alarm is enabled,
the display shows the message “dA” and the regulation restarts if rd = y. The alarm stops as soon
as the external digitalinput is disabled again. With the door open, the high and low temperature alarms
are disabled.
8.2 EXTERNAL ALARM (IF=EA)
As soon as the digital input is activated the unit will wait for “di” time delay before signalling the “EA”
alarm message. The outputs status don’t change. The alarm stops just after the digital input is de-
activated.
8.3 SERIOUS ALARM (IF=BA)
When the digital input is activated, the unit will wait for “di” delay before signalling the “CA” alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated.
8.4 START DEFROST (IF=DF)
It starts a defrost if there are the right conditions. After the defrost is finished, the normalregulation will
restart only if the digital input is disabled otherwise the instrument will wait until the “Md” safety time is
expired.
8.5 INVERSION OF THE KIND OF ACTION: HEATING - COOLING (IF=HC)
This function allows to invert the regulation of the controller: from cooling to heating and viceversa.
9INSTALLATION ANDMOUNTING
Instrument XR06CH shall be mounted on vertical panel, in a
29x71 mm hole, and fixed using the special bracket supplied.
The temperature range allowed for correct operation is 060 °C.
Avoid places subject to strong vibrations, corrosive gases,
excessive dirt or humidity. The same recommendations apply to
probes. Let air circulate by the cooling holes.
10 ELECTRICAL CONNECTIONS
The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5
mm2. Before connecting cables make sure the power supply complies with the instrument’s
requirements. Separate the probe cables from the power supply cables, from the outputs and the
power connections. Do not exceed the maximum current allowed on each relay, in case of heavier
loads use a suitable external relay.
10.1 PROBES
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid
infiltration. It is recommended to place the thermostat probe away from air streams to correctly
measure the average room temperature. Place the defrost termination probe among the evaporator
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during
defrost, to prevent premature defrost termination.
11 HOW TO USE THE HOT KEY
11.1 HOW TO PROGRAM THE HOT KEY FROM THE INSTRUMENT (UPLOAD)
1. Program one controller with the front keypad.
2. When the controller is ON, insert the “Hot key” and push key; the "uP" message appears
followed aby flashing “Ed”
3. Push “SET” key and the “Ed” will stop flashing.
4. Turn OFF the instrument remove the “Hot Key”, then turn it ON again.
NOTE: the “Er” message is displayed for failed programming. In this case push again o key if you want
to restart the upload again or remove the “Hot key” to abort the operation.
11.2 HOW TO PROGRAM AN INSTRUMENT USING HOT KEY (DOWNLOAD)
1. Turn OFF the instrument.
2. Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON.
3. Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, the
“do”message is blinking followed a byflashing “Ed”.
4. After 10 seconds the instrument willrestart working with the new parameters.
5. Remove the “Hot Key”..
NOTE: the “Er” message is displayed for failed programming. In this case push again o key if you want
to restart the upload again or remove the “Hot key” to abort the operation.
12 ALARM SIGNALLING
Mess. Cause Outputs
"P1" Room probe failure Compressor output according to “Cy”e “Cn”
"P2" Evaporator probe failure Defrost end is timed
"HA" Maximum temperature alarm Outputs unchanged
"LA" Minimum temperature alarm Outputs unchanged
“EA” External alarm Outputs unchanged
“CA” Serious external alarm All outputs OFF
“dA” Door Open Compressor and fans restarts
1598040340 XR06CH BMB GB r1.0 20.02.2018 XR06CH 3/3
12.1 ALARM RECOVERY
Probe alarms P1” and “P2” start some seconds after the fault in the related probe; they automatically
stop some seconds after the probe restarts normal operation. Check connections before replacing the
probe. Temperature alarms “HA” and “LA” automatically stop as soon as the temperature returns to
normal values.
Alarms “EA” and “CA” (with iF=bL) recover as soon as the digital input is disabled.
13 TECHNICAL DATA
Housing: self extinguishing ABS.
Case: frontal 32x74 mm; depth 60mm;
Mounting: panelmounting in a 71x29mm panel cut-out
Protection: IP20; Frontal protection: IP65
Connections: Screw terminal block 2,5 mm2wiring.
Power supply: according to the model230Vac 10%, 50/60Hz --- 110Vac 10%, 50/60Hz
Power absorption: 3.5VA max
Display: 2 digits, red LED, 14,2 mm high; Inputs: Up to 2NTC.
Digital input: free voltage contact
Relay outputs: compressor SPST 8(3) A, 250Vac; SPST 16(6)A 250Vac or 20(8)A 250Vac
defrost: SPDT 8(3) A, 250Vac
fan: SPST 8(3) A, 250Vac or SPST 5(2) A
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B; Pollution degree: 2;Software class: A.;
Rated impulsive voltage: 2500V; Overvoltage Category: II
Operating temperature: 0÷60 °C;Storage temperature: -25÷60 °C.
Relative humidity: 2085% (no condensing)
Measuring and regulation range: NTC -40÷110°C;
Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±0,1 °C ±1digit
14 CONNECTIONS
14.1 XR06CH – 20A+8A+5A 230VAC
NOTE: The compressor relay is 20(8)A or 16(6)A depending on the model.
15 DEFAULT SETTING VALUES
LABEL DESCRIPTION VALUE LEVEL
SEt Set Point -5.0 Pr1
Hy Differential 2.0 Pr2
LS Minimum Set Point -55.0 Pr2
US Maximum Set Point 99.0 Pr2
ot First probe calibration 0.0 Pr1
P2 Second probe presence Y Pr1
oE Second probe calibration 0.0 Pr2
od Outputs activation delay at start up 0 Pr2
AC Anti-short cycle delay 1 Pr1
Cy Compressor ON time faulty probe 15 Pr2
Cn Compressor OFF time faulty probe 30 Pr2
CF Measurement units °C Pr2
rE Resolution (only for °C) dE Pr1
Ld Default Display P1 Pr2
dy Display delay 0 Pr2
td Defrost type EL Pr1
dE Defrost termination temperature 8.0 Pr1
id Interval between defrost cycles 6 Pr1
Md Maximum length for defrost 30 Pr1
dd Start defrost delay 0 Pr2
dF Display during defrost It Pr2
dt Drip time 0 Pr2
dP Defrost at power-on n Pr2
FC Fans operating mode O_n Pr1
Fd Fans delay after defrost 10 Pr1
FS Fans stop temperature 2.0 Pr2
AU Maximum temperature alarm 99.0 Pr1
AL Minimum temperature alarm -55.0 Pr1
Ad Temperature alarm delay 15 Pr2
dA
Exclusion of temperature alarm at
startup 90 Pr2
iP Digital input polarity CL Pr1
iF Digital input configuration do Pr1
di Digital input delay 15 Pr1
dC
Compressor and fan status when open
door FC Pr2
Rd Regulation with door open Y Pr2
d1 Thermostat probe display - Pr2
d2 Evaporator probe display - Pr1
Pt Parameter code table - Pr2
rL Firmware release - Pr2