EC2-712_65108_EN_R03.doc Replacement for Rev.:02 1 / 4 16.09.2009 
 
 
EC2-712 Condenser Controller 
Operating Instructions GB 
Note: This document contains short form instructions for experienced users. 
Use last column in List of Parameters to document your individual settings. 
More detailed information can be found in the User Manual. 
 
The EC2-712 has been designed to control condensers with up to four fans. The 
purpose of the controller is to keep condensing pressure to a minimum by 
switching fans on or off. 
 
The PT5 pressure transmitter (5) senses condensing pressure and feeds the signal 
into a condensing pressure dead band control loop. Condensing pressure is 
modulated by turning fan motors on and off. 
No change occurs as long as the condensing pressure remains within the dead band 
(P1) around the condensing pressure setpoint (P0). The controller will add/remove 
fan capacity when the condensing pressure goes beyond the limits of the 
condensing pressure dead band. For stable condenser operation, adjustable time 
delays for fan motor on and off are available. To avoid premature wear of 
individual fan motors, run time equalization is built into the controller. 
 
 
 remove capacity dead band add capacity 
 
 Condensing Pressure
 
A fast recovery procedure can be used to immediately switch off all fans when the 
condensing pressure falls below a set limit. Similarly an emergency routine can be 
activated automatically if the condensing pressure exceeds a definable limit. 
!Safety instructions: 
•Read installation instructions thoroughly. Failure to comply can result in 
device failure, system damage or personal injury. 
•The product is intended for use by persons having the appropriate 
knowledge and skills. 
•Ensure electrical ratings per technical data are not exceeded. 
•Disconnect all voltages from system before installation. 
•Keep temperatures within nominal limits. 
•Comply with local electrical regulations when wiring 
Technical data: 
Power supply 24VAC ±10%; 50/60 Hz; Class II 
Power consumption 4VA max. 
Communication TCP/IP Ethernet 10MBit/s 
Terminals Removable screw terminals 
wire size 0.14 … 1.5 mm2
Temperature 
 storage 
 operating 
 -20 … +65°C 
 0 … +60°C 
Pressure sensor input 24VDC, 4 … 20mA 
Fan output relays Inductive (AC15) 250V / 2A 
Resistive (AC1) 250V / 6A; 12A total return current
Digital inputs Volt free contacts 5V/0,1mA 
Humidity 0 … 80% rh. non condensing 
Protection class IP65 (front protection with gasket) 
Marking 
 
Mounting 
The EC2-712 can be mounted in panels with a 71 x 
29 mm cutout. See dimensional drawing below for 
space requirements including rear connectors. 
Push controller into panel cutout.(1) 
Make sure that mounting clamps are flush with 
outside of controller housing 
Insert allen key into front panel holes and turn 
clockwise. Mounting clamp will turn and gradually 
move towards panel (2) 
Turn allen key until mounting clamp barely touches 
panel. Then move other mounting clamp to the same 
position (3) 
Tighten both sides very carefully until controller is 
secured. Do not over tighten as mounting clamps 
will break easily. 
 
 
Electrical Installation 
Refer to the electrical wiring diagram 
(right) for electrical connections. A copy 
of this diagram is labelled on the 
controller. 
Use connection wires/cables suitable for 
90°C operation (EN 60730-1). 
EC2 analog inputs are for dedicated 
sensors only and should not be connected 
to any other devices. Volt free digital 
inputs should only be connected to serial 
control loops or relays with gold 
contacts. They should not be connected 
to any other devices 
Important: Keep controller and sensor wiring well separated from mains wiring. 
Minimum recommended distance 30mm. 
Warning: Use a class II category transformer for 24VAC power supply 
(EN 60742). Do not ground the 24VAC lines. We recommend to use one 
transformer per EC2 controller and to use separate transformers for 3rd party 
controllers, to avoid possible interference or grounding problems in the power 
supply. Connecting any EC2 inputs to mains voltage will permanently damage the 
EC2. 
Set-up and Parameter Modification Using the Keypad 
For convenience, an infrared receiver for the optional IR remote control unit is 
build-in, enabling quick and easy modification of the system parameters when a 
computer interface is not available. 
Alternatively, the parameters can be accessed via the 4-button keypad. The 
configuration parameters are protected by a numerical password. The default 
password is “12”. To select the parameter configuration: 
•Press the PRG button for more than 5 seconds 
A flashing 0 is displayed 
•Press or until 12 is displayed; (password) 
•Press SEL to confirm password 
•The first modifiable parameter code is displayed (/1). 
•To modify parameters see Parameters modification below.