manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Emerson
  6. •
  7. Controllers
  8. •
  9. Emerson Dixell XR30CX-4S1C1 Wiring diagram

Emerson Dixell XR30CX-4S1C1 Wiring diagram

Page: 1
Falkevej 12
DK – 6705 Esbjerg Ø
Tel.: +45 79 14 22 22
Pages incl. this one: 5
Init.: CEH
Date: 110207
Approved: Drawing No.: 8181101 Version: 01
Supplyer:
Subject: Instr. XR30CX GB (medsendes fra termostat)
Components must comply with the rules and restrictions stated in A/S Vestfrosts List of undesirable components/substances, and be
free from silicone.
This component must comply with the European Directive 2002/95/EC on the restriction of the use of certain hazardous substances in
electrical and electronic equipment (RoHS directive).
This drawing is the property of A/S Vestfrost and must not be copied, passed on to, or otherwise used by any person without the
express consent of A/S Vestfrost.
Date: Last modification: Init:
Denne vare er specificeret ved nedenstående datablad. Med forudgående skriftlig
tilladelse fra Vestfrost, kan alternativ type/fabrikat anvendes.
This product is specified according to the data sheet mentioned below. Alternative products/product types may only be used with the
prior written consent of A/S Vestfrost.
Se vedlagte
1598024xxx XR30CX VST GB r1.0 2011.01.21.doc XR30CX 1/4
Digital controllers with off cycle defrost, AUX relay,
power supply 100 or 230VAC and battery backup.
XR30CX
CONTENTS
1. GENERAL WARNING__________________________________________________________1
2. GENERAL DESCRIPTION ______________________________________________________1
3. CONTROLLING LOADS ________________________________________________________1
4. FRONT PANEL COMMANDS____________________________________________________1
5. MAX & MIN TEMPERATURE MEMORIZATION _____________________________________1
6. MAIN FUNCTIONS ____________________________________________________________2
7. PARAMETERS _______________________________________________________________2
8. DIGITAL INPUT_______________________________________________________________3
9. TTL SERIAL LINE – FOR MONITORING SYSTEMS _________________________________3
10. INSTALLATION AND MOUNTING ________________________________________________3
11. ELECTRICAL CONNECTIONS___________________________________________________3
12. HOW TO USE THE HOT KEY ___________________________________________________3
13. ALARM SIGNALS _____________________________________________________________3
14. TECHNICAL DATA ____________________________________________________________3
15. CONNECTIONS ______________________________________________________________4
16. DEFAULT SETTING VALUES ___________________________________________________4
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick
reference.
The instrument shall not be used for purposes different from those described hereunder. It
cannot be used as a safety device.
Check the application limits before proceeding.
1.2 SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding
sudden temperature changes with high atmospheric humidity to prevent formation of
condensation
Warning: disconnect all electrical connections before any kind of maintenance.
Fit the probe where it is not accessible by the End User. The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.”
(see address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply are separated and far enough from
each other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in
parallel with inductive loads could be useful.
2. GENERAL DESCRIPTION
NOTE: This manual is related to the following model:
Model description
User code
Power Supply
Options
XR30CX -4S1C1
7020115
100VAC
-
XR30CX -5S1C1
7020110
230VAC
-
XR30CX -5S1C1
7020122
230VAC
Battery backup
Model XR30CX, format 32x74mm, is a digital thermostat with off cycle defrosting function designed for
refrigeration applications. It provides two relay outputs, one for the compressor and the other one for
alarm signalling. It is also provided with a PT1000 or PTC probe input for temperature control.
Moreover, the digital input can operate as third temperature probe.
The battery-backup version is also provided with an input for external battery. It is used to supply the
controller in case of main voltage failure.
By using the HOT-KEY input/output port is possible to upload a new parameter map from (program the
controller) or save the actual parameter map to an external memory device (named HOTKEY
memory). Moreover, by using this port is possible to connect the device to a network line (ModBUS-
RTU compatible) such as a dIXEL monitoring units of X-WEB family. In this case, a special adapter
(XJ485-CX) has to be used.
3. CONTROLLING LOADS
3.1 COMPRESSOR
The regulation is performed according to
the temperature measured by the
thermostat probe with a positive
differential (HY) from the set point: if the
temperature increases and reaches set
point plus differential the compressor is
started and then turned off when the
temperature reaches the set point value
again.
Time
Temper.
Compr.
SET
ON
In case of fault in the thermostat probe the start and stop of the compressor are timed through
parameters Con and CoF.
3.2 DEFROST
Defrost is performed through a simple stop of the compressor. Parameter idF controls the interval
between defrost cycles, while its length is controlled by using MdF parameter.
3.3 DEVICE OPERATIONS IN CASE OF POWER FAILURE, IF A BACK UP
BATTERY IS CONNECTED (ONLY FOR 7020122-01 MODEL)
3.3.1 Power failure without temperature alarm
If the controller is connected to the battery, during a power failure:
1. The alarm LED icon will be lit.
2. The alarm relay will be activated according to the Aro parameter.
3. Every 5s the buzzer will ring 3 times during 1s.
The buzzer will be muted after pressing any button. It will restart ringing after the bon time if the power
failure keeps on lasting. After pushing SET button, the controller will display the temperature for 5s.
3.3.2 Power failure and temperature alarms
If a temperature alarm happens during a power failure:
1. The alarm LED icon will be lit.
2. The buzzer will ring continuously.
3. The displays will shows: real temperature for 1s, alarm label for 1s and remains off for 5s.
The buzzer will be muted for the bon time after pressing any button.
The battery can guarantee at least 50 hours of operations in this conditions.
The time for a full charge of the battery is 94 hours.
4. FRONT PANEL COMMANDS
To display target set point.
In programming mode it selects a parameter or confirm an operation.
(DEF) To start a manual defrost.
(UP) To see the max stored temperature. In programming mode it browses
parameters or increases the displayed value.
(DOWN) To see the min stored temperature. In programming mode it
browses the parameters or decreases the displayed value.
To switch the instrument on and off when onF=oFF.
NOT USED
KEY COMBINATIONS:
+
To lock & unlock the keyboard.
+
To enter in programming mode.
+
To return to the room temperature display.
4.1 USE OF LEDS
Each LED function is described in the following table.
LED
MODE
FUNCTION
ON
Compressor enabled
Flashing
Anti-short cycle delay enabled
ON
Defrost enabled
ON
An alarm is occurring
ON
Continuous cycle is running
ON
Energy saving enabled
°C/°F
ON
Measurement unit
Flashing
Programming phase
5. MAX & MIN TEMPERATURE MEMORIZATION
5.1 HOW TO SEE THE MIN TEMPERATURE
1. Press and release the DOWN button.
2. The “Lo” message will be displayed followed by the minimum temperature recorded.
3. By pressing the DOWN button again or by waiting for 5s the normal display will be restored.
1598024xxx XR30CX VST GB r1.0 2011.01.21.doc XR30CX 2/4
5.2 HOW TO SEE THE MAX TEMPERATURE
1. Press and release the UP button.
2. The “Hi” message will be displayed, followed by the maximum recorded temperature.
3. By pressing the UP button again or by waiting for 5s, the normal display will be restored.
5.3 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
1. Keep SET button pressed more than 3s while the max or min temperature is displayed
(“rSt” message will be displayed).
2. To confirm the operation the “rSt” message starts blinking and the normal temperature will be
displayed.
6. MAIN FUNCTIONS
6.1 HOW TO SEE THE SETPOINT
1. Push and immediately release the SET button: the display will show the
Set point value;
2. Push and immediately release the SET button or wait for 5 seconds to
display the probe value again.
6.2 HOW TO CHANGE THE SETPOINT
1. Keep SET button pressed more than 2 seconds to change the Set point value.
2. The value of the set point will be displayed and the “°C” or “°F” LED icon will start blinking.
3. To change the Set-point value, push the UP or DONW buttons within 10s.
4. To memorise the new set point value, push the SET button again or wait for 10s.
6.3 HOW TO START A MANUAL DEFROST
Push the DEF key for more than 2 seconds and a manual defrost will start.
6.4 HOW TO CHANGE A PARAMETER VALUE
To change any parameter value, operate as follows:
1. Enter the Programming mode by pressing SET + DOWN for 3s (the “°C” or “°F” LED icons will
start blinking).
2. Select the required parameter. Press SET to display its value.
3. Use UP or DOWN to change its value.
4. Press SET to store the new value and move to the following parameter.
To exit: Press SET + UP or wait for 15s without pressing any key.
NOTE: the set value is stored even when the procedure is exited by waiting for the time-out to expire.
6.5 THE HIDDEN MENU
The hidden menu includes all the parameters of the instrument.
6.5.1 HOW TO ENTER THE HIDDEN MENU
1. Enter the Programming mode by pressing SET + DOWN for 3s (the “°C” or “°F” LED icons will
start blinking).
2. Released the buttons and then push again them (SET + DOWN) for more than 7s. The Pr2 label
will be displayed immediately, followed from the HY parameter.
Now it is possible to browse the hidden menu.
3. Select the required parameter.
4. Press SET to display its value
5. Use UP or DOWN to change its value.
6. Press SET to store the new value and move to the following parameter.
To exit: Press SET + UP or wait for 15s without pressing any key.
NOTE1: if no parameter is present in Pr1, after 3s the “noP” message will be displayed. Keep the
buttons pushed till the Pr2 message will be displayed.
NOTE2: the set value is stored even when the procedure is exited by waiting for the time-out to expire.
6.5.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE
FIRST LEVEL AND VICEVERSA.
Each parameter present in the hidden menu (Pr2) can be moved into the user level (Pr1) by pressing
SET + DOWN buttons. If a parameter is part of the user level, when showed in the hidden menu the
decimal point will be lit.
6.6 HOW TO LOCK THE KEYBOARD
1. Keep pressed for more than 3 s the UP +DOWN buttons.
2. The “PoF” message will be displayed and the keyboard will be locked. At this point it will be
possible only to see the set point or the MAX o Min temperature stored
3. If a button is pressed more than 3s the “PoF” message will be displayed.
6.7 TO UNLOCK THE KEYBOARD
Keep pressed both UP and DOWN for more than 3s till the “Pon” message will be displayed.
6.8 THE CONTINUOUS CYCLE
When defrost is not in progress, it can be activated by keeping the UP button pressed for about 3
seconds. The compressor operates to maintain the CCS set point for the time set through the CCt
parameter. The cycle can be terminated before the end of the set time using the same activation
button (UP for 3 seconds).
6.9 THE ON/OFF FUNCTION
When “onF=oFF”, pushing the ON/OFF key, the instrument is switched off. The “OFF”
message is displayed. In this configuration, the regulation is disabled.
To switch the instrument on, push again the ON/OFF key.
WARNING: Loads connected to the normally closed contacts of the relays are always supplied
and under voltage, even if the instrument is in stand by mode.
7. PARAMETERS
REGULATION
HY
Differential: (0.1÷25.5°C; 1÷255°F) intervention differential for set point. Compressor
Cut IN is Set Point + differential (HY). Compressor Cut OUT is when the temperature
reaches the set point.
LS
Minimum set point: (-100°C÷SET; -148°F÷SET) it sets the minimum value for the
set point.
US
Maximum set point: (SET÷150°C; SET÷302°F) it sets the maximum value for set
point.
ot
Thermostat probe calibration: (-12.0÷12.0°C; -120÷120°F) allows to adjust
possible offset of the thermostat probe.
odS
Outputs activation delay at start up: (0÷255min) this function is enabled at the
initial start up of the instrument and inhibits any output activation for the period of time
set in the parameter.
AC
Anti-short cycle delay: (0÷50min) minimum interval between the compressor stop
and the following restart.
rtr
Percentage of the second and first probe for regulation: (0÷100; 100=P1, 0=P2)
it allows to set the regulation according to the percentage of the first and second
probe, as for the following formula (rtr(P1-P2)/100 + P2).
CCt
Compressor ON time during continuous cycle: (0.0÷24h00min, res. 10min) allows
to set the length of the continuous cycle. Compressor stays on without interruption
during CCt time. This is useful, for instance, when the room is filled with new
products.
CCS
Set point for continuous cycle: (-100÷150°C; -148÷302°C) it sets the set point
used during the continuous cycle.
Con
Compressor ON time with faulty probe: (0÷255min) time during which the
compressor is active in case of faulty thermostat probe. With Con=0 compressor is
always OFF.
CoF
Compressor OFF time with faulty probe: (0÷255min) time during which the
compressor is OFF in case of faulty thermostat probe. With CoF=0 compressor is
always active.
CH
Type of action: (CL, Ht) CL = cooling; Ht = heating.
DISPLAY
CF
Temperature measurement unit: (°C; °F) °C = Celsius; °F = Fahrenheit.
WARNING: When the measurement unit is changed the SET point and the values of
the parameters HY,LS,US,ot,ALU and ALL have to be checked and modified (if
necessary).
rES
Resolution (for °C): (in=1°C; dE=0.1°C) allows decimal point display.
dLY
Display delay: (0.0÷20min00s; res. 10s) when the temperature increases, the display
is updated of 1°C or 1°F after this time.
DEFROST
idF
Interval between defrost cycles: (0÷120hours) determines the interval of time
between two defrost cycles.
MdF
(Maximum) length for defrost: (0÷255min)
When P2P=n, (not evaporator probe: timed defrost) it sets the defrost duration.
When P2P=Y (defrost end based on temperature) it sets the maximum length for
defrost.
dFd
Temperature displayed during defrost: (rt; it; SEt; dEF) rt = real temperature;
it = temperature at defrost start; SEt = set point; dEF = “dEF” label.
dAd
MAX display delay after defrost: (0÷255min) sets the maximum time between the
end of defrost and the restarting of the real room temperature display.
ALARMS
ALC
Temperature alarms configuration: (Ab; rE) Ab = absolute temperature, alarm
temperature is given by the ALL or ALU values. rE = temperature alarms are referred
to the set point. Temperature alarm is enabled when the temperature exceeds the
[SET+ALU] or [SET-ALL] values.
ALU
MAXIMUM temperature alarm:
ALC=Ab: (SET÷150°C; SET÷302°F)
ALC=rE: (0.1÷50°C; 1÷90°F)
When this temperature is reached, the alarm is enabled, possibly the ALd delay time.
ALL
Minimum temperature alarm:
ALC=Ab: (-100.0 ÷ SET°C; -148÷302°F)
ALC=rE: (0.1÷50°C; 1÷90°F)
When this temperature is reached, the alarm is enabled, possibly the ALd delay time.
AFH
Differential for temperature alarm recovery: (0.1÷25.5°C; 1÷45°F) intervention
differential for recovery of temperature alarm.
ALd
Temperature alarm delay: (0÷255 min) time interval between the detection of an
alarm condition and alarm signalling.
dAo
Exclusion of temperature alarm at start-up: (0.0÷23h 50min, res. 10min) time
interval between the detection of the temperature alarm condition after instrument
power on and alarm signalling.
ALARM RELAY MANAGEMENT – ONLY FOR BATTERY-BACKUP MODELS (7020122-01)
tbA
Alarm relay silencing (with oA1=ALr): (n, Y)
n= silencing disabled; alarm relay stays on till alarm condition lasts.
Y= silencing enabled; alarm relay is switched OFF by pressing a key during an alarm.
Aro
Alarm relay activation with power failure: (n, Y)
n= the alarm relay is never activated during a power failure.
Y= the alarm relay is activated during a power failure.
ALF
Alarm relay activation for all the alarms: (n, Y)
n= the alarm relay is activated only in case of a temperature alarm or regulation
probe failure.
Y= the alarm relay is activated for all the alarms.
1598024xxx XR30CX VST GB r1.0 2011.01.21.doc XR30CX 3/4
bon
Time of buzzer restart after muting, in case of alarm duration: (0÷30min) when 0
the buzzer is always off after muting.
AoP
Alarm relay polarity: it set if the alarm relay is open or closed when an alarm
happens. CL= terminals 1-2 closed during an alarm; oP = terminals 1-2 open during
an alarm
DIGITAL INPUT
i1P
Digital input polarity: (oP; CL) oP = the digital input is activated by opening the
contact; CL = the digital input is activated by closing the contact.
i1F
Digital input configuration: (EAL; bAL; PAL; dor; dEF; AUS; Htr; FAn; ES)
EAL = external alarm: “EA” message is displayed; bAL = serious alarm “CA”
message is displayed. PAL = pressure switch alarm, “CA” message is displayed; dor
= door switch function; dEF = activation of a defrost cycle; AUS =to switch on the
second relay if oA1 = AUS; Htr = kind of action inversion (cooling – heating); FAn =
not set it; ES = Energy saving.
did
Digital input alarm delay when i1F=EAL or i1F=bAL: (0÷255 min) delay between
the detection of the external alarm condition and its signalling.
With i1F= dor: door open signalling delay.
With i1F=PAL: time for pressure switch function. It is the time
interval to calculate the number of the pressure switch activation.
nPS
Number of pressure switch activation: (015) Number of activation, during the did
interval, before signalling an alarm event (i2F=PAL).
If the nPS activation during did time is reached, switch off and on the instrument to
restart normal regulation.
odc
Compressor status when open door: (no; FAn; CPr;F_C;) no = normal;
FAn = normal; CPr = compressor OFF, F_C = compressor OFF.
rrd
Outputs restart after doA alarm: (n; Y) n= outputs not affected by the doA alarm;
Y= outputs restart with the doA alarm.
HES
Temperature increase during the Energy Saving cycle: (-30.030.0°C; -5454°F)
it sets the increasing value of the set point [SET+HES] during the Energy Saving
cycle.
OTHER
Adr
Serial address: (1÷244) identifies the instrument address when connected to a
ModBUS compatible monitoring system.
PbC
Type of probe: (ntC, CtC) it allows to set the kind of probe used by the instrument:
PtC = PTC probe, Pt1 = Pt1000 probe.
onF
On/Off key enabling: (nU; oFF; ES) nU = disabled; oFF = enabled; ES = not set it.
rSE
Real set point: it shows the set point used during the energy saving cycle or during
the continuous cycle.
rEL
Software release for internal use.
Ptb
Parameter table code: readable only.
8. DIGITAL INPUT
The free voltage digital input is programmable in different configurations by the i1F parameter.
8.1 DOOR SWITCH INPUT (i1F = dor)
It signals the door status and the corresponding relay output status through the odC parameter: no,
Fan = normal (any change); CPr, F_C = Compressor OFF.
Since the door is opened, after the delay time set through parameter did, the door alarm is enabled,
the display shows the message “dA” and the regulation restarts is rtr=Y. The alarm stops as soon
as the external digital input is disabled again. With the door open, the high and low temperature alarms
are disabled.
8.2 GENERIC ALARM (i1F = EAL)
As soon as the digital input is activated the unit will wait for did time delay before signalling the “EAL”
alarm message. The outputs status doesn’t change. The alarm stops just after the digital input is de-
activated.
8.3 SERIOUS ALARM MODE (i1F = bAL)
When the digital input is activated, the unit will wait for did delay before signalling the “CA” alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated.
8.4 PRESSURE SWITCH (i1F = PAL)
If during the interval time set by did parameter the pressure switch reaches the nPS number of
activation, the “CA” pressure alarm message will be displayed and the compressor and the regulation
will be stopped. When the digital input is ON the compressor is always OFF.
If the nPS activation in the did time is reached, switch off and on the instrument to restart
normal regulation.
8.5 START DEFROST (i1F = dFr)
A defrost will start if there are the right conditions. After the defrost is finished, the normal regulation
will restart only if the digital input is disabled otherwise the instrument will wait for MdF safety time to
expire.
8.6 INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F = Htr)
This function allows to invert the regulation of the controller: from cooling to heating and viceversa.
8.7 ENERGY SAVING (i1F = ES)
The Energy Saving function allows to change the set point value as the result of the [SET+ HES]
(parameter) sum. This function is enabled until the digital input is activated.
8.8 DIGITAL INPUTS POLARITY
The digital input polarity depends on the i1P parameter.
i1P=CL: the input is activated by closing the contact.
i1P=OP: the input is activated by opening the contact
9. TTL SERIAL LINE – FOR MONITORING SYSTEMS
It is possible to connect the instrument to a ModBUS-RTU compatible monitoring system (e.g.
X-WEB500/3000/300) by using the TTL serial line available on the HOTKEY connector. An external
adapter has to be used to connect the device to the network (e.g. a TTL/RS485 converter XJ485-CX).
10. INSTALLATION AND MOUNTING
Instrument XR30CX shall be mounted on vertical panel, in a 29x71
mm hole, and fixed using the special bracket supplied.
The temperature range allowed for correct operation is 060 °C.
Avoid places subject to strong vibrations, corrosive gases,
excessive dirt or humidity. The same recommendations apply to
probes. Let air circulate by the cooling holes.
11. ELECTRICAL CONNECTIONS
The instrument is provided with screw terminal block to connect cables with a cross section up to
2.5mm2. Before connecting cables make sure the power supply complies with the instrument’s
requirements. Separate the probe cables from the power supply cables, from the outputs and the
power connections. Do not exceed the maximum current allowed on each relay, in case of heavier
loads use a suitable external relay.
11.1 PROBE CONNECTION
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid
infiltration. It is recommended to place the thermostat probe away from air streams to correctly
measure the average room temperature. Place the defrost termination probe among the evaporator
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during
defrost, to prevent premature defrost termination.
12. HOW TO USE THE HOT KEY
12.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1. Program one controller with the front keypad.
2. When the controller is ON, insert the “HOT-KEY” and push UP button; the “uPL” message
appears followed a by a flashing “End” label.
3. Push SET button and the “End” will stop flashing.
4. Turn OFF the instrument, remove the “HOT-KEY” and then turn it ON again.
NOTE: the “Err” message appears in case of a failed programming operation. In this case push again
button if you want to restart the upload again or remove the “HOT-KEY” to abort the operation.
12.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD)
1. Turn OFF the instrument.
2. Insert a pre-programmed “Hot Key” into the 5-PIN receptacle and then turn the Controller
ON.
3. The parameter list of the “Hot Key” will be automatically downloaded into the Controller
memory. The “doL” message will blink followed a by a flashing “End” label.
4. After 10 seconds the instrument will restart working with the new parameters.
5. Remove the “HOT-KEY”.
NOTE: the message “Err” is displayed for failed programming. In this case turn the unit off and then
on if you want to restart the download again or remove the “HOT-KEY” to abort the operation.
13. ALARM SIGNALS
Message
Cause
Outputs
“P1”
Room probe failure
Compressor output acc. to par. Con and CoF.
“HA”
Maximum temperature alarm
Outputs unchanged.
“LA”
Minimum temperature alarm
Outputs unchanged.
“dA”
Door open
Compressor restart according to rrd.
“EA”
External alarm
Output unchanged.
“CA”
Serious external alarm (i1F=bAL)
All outputs OFF.
“CA”
Pressure switch alarm (i1F=PAL)
All outputs OFF
13.1 ALARM RECOVERY
Probe alarm “P1” starts some seconds after the fault in the related probe; they automatically stop
some seconds after the probe restarts normal operation. Check connections before replacing the
probe.
Temperature alarms “HA” and “LA” automatically stop as soon as the temperature returns to normal
values.
Alarms “EA” and “CA” (with i1F=bAL) recover as soon as the digital input is disabled.
Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument.
13.2 OTHER MESSAGES
Pon
Keyboard unlocked.
PoF
Keyboard locked
noP
In programming mode: none parameter is present in Pr1
On the display or in dP2, dP3, dP4: the selected probe is nor enabled
noA
No alarm recorded.
14. TECHNICAL DATA
Housing: self extinguishing ABS.
Case: XR30CX frontal 32x74mm; depth 60mm.
Mounting: XR30CX panel mounting in a 71x29mm panel cut-out.
Protection: IP20. Frontal protection: XR30CX IP65.
Connections: Screw terminal block 2.5 mm2wiring.
Power supply: 100Vac 10%, 50/60Hz; 230Vac 10%, 50/60Hz.
1598024xxx XR30CX VST GB r1.0 2011.01.21.doc XR30CX 4/4
Power absorption: 3VA max.
Display: 3 digits red LEDs, 14.2 mm high.
Digital input: free voltage contact.
Analogue Input: a PT1000 or PTC probe, set via parameter.
Relay outputs:
Compressor: 20(8)A, 250Vac.
Alarm: SPDT 8(3)A, 250Vac.
Connectors for external backup battery (only for battery-backup model).
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B. Pollution degree: 2. Software class: A.
Rated impulsive voltage: 2500V. Overvoltage Category: II.
Operating temperature: 0÷60°C.
Storage temperature: -30÷85 °C.
Relative humidity: 2085% (no condensing).
Measuring and regulation range:
Pt1000 probe: -100÷100°C (-148÷212°F).
PTC probe: -55÷150°C (-67÷302°F).
Resolution: 0.1°C or 1°C or 1°F (selectable).
Accuracy (ambient temp. 25°C): ±0.7 °C ±1 digit.
Only for battery backup model:
Type of battery: 6Vdc, 1.2Ah.
Charging time: 94hours.
15. CONNECTIONS
15.1 XR30CX -4S1C1 (7020115)
15.2 XR30CX -5S1C1 WITH BATTERY BACKUP (7020122)
15.3 XR30CX -5S1C1 WITHOUT BATTERY BACKUP (7020110)
16. DEFAULT SETTING VALUES
Label
Name
Range
No batt.
backup
With batt.
backup
Level
SEt
Set point
LS ÷ US
-62
-82
- - -
HY
Differential
[0.1 25.5°C]
[1255°F]
[1°C]
[1°F]
[1°C]
[1°F]
Pr1
LS
Minimum set point
[-100,0°C ÷ SET]
[-148°F ÷ SET]
[-63°C]
[-81°F]
[-95°C]
[139°F]
Pr2
US
Maximum set point
[SET ÷ 150,0°C]
[SET ÷ 302°F]
[-30°C]
[-22°F]
[-60°C]
[-76°F]
Pr2
ot
Thermostat probe calibration
[-12 12°C]
[-120120°F]
[0°C]
[0°F]
[0°C]
[0°F]
Pr1
odS
Outputs delay at start up
0 ÷ 255 min
0
0
Pr2
AC
Anti-short cycle delay
050 min
5
5
Pr1
CCt
Continuous cycle duration
0.0 ÷ 24h 00min, res. 10min
0.0
0.0
Pr2
CCS
Set point for continuous cycle
[-100 ÷ 150°C]
[-148 ÷ 302°F]
[-62°C]
[-79°F]
[-82°C]
[-115°F]
Pr2
Con
Compressor ON time with faulty
probe
0255 min
60
60
Pr2
CoF
Compressor OFF time with faulty
probe
0255 min
5
5
Pr2
CH
Kind of action
CL=cooling; Ht= heating
CL
CL
Pr2
CF
Temperature measurement unit
°C; °F
°C
°C
Pr2
rES
Resolution
in = integer; dE = dec.point
in
in
Pr2
dLY
Display temperature delay
0 ÷ 20min 00s, res. 10s
0.0
0.0
Pr2
idF
Interval between defrost cycles
1120 hours
0
0
Pr1
MdF
(Maximum) length for defrost
0255 min
0
0
Pr1
dFd
Displaying during defrost
rt; it; SEt; DEF
rt
rt
Pr2
dAd
MAX display delay after defrost
0 ÷ 255 min
0
0
Pr2
ALC
Temperature alarms configuration
rE= related to set
Ab = absolute
rE
rE
Pr2
ALU
MAXIMUM temperature alarm
[Set 110°C]
[Set ÷ 230°F]
[15°C]
[59°F]
[15°C]
[59°F]
Pr1
ALL
Minimum temperature alarm
[-100°C Set]
[-148°F Set]
[50°C]
[122°F]
[50°C]
[122°F]
Pr1
AFH
Differential for temperature alarm
recovery
[0.1°C ÷ 25.5°C]
[1°F÷45°F]
[1°C]
[1°F]
[1°C]
[1°F]
Pr2
ALd
Temperature alarm delay
0255 min
0
0
Pr2
dAo
Delay of temperature alarm at start
up
023h 50min, res. 10min
1.3
1.3
Pr2
tbA
Alarm relay disabling
n; Y
Y
Y
Pr2
Aro
Alarm relay activation with power
failure
n; Y
Y
Y
Pr2
ALF
Alarm relay activation for all the
alarms
n; Y
Y
Y
Pr2
bon
Time of buzzer restart after muting,
in case of alarm duration
0 ÷ 30 min
30
30
Pr2
AoP
Alarm relay polarity (oA1=ALr)
oP; CL
CL
CL
Pr2
i1P
Digital input polarity
oP=opening; CL=closing
CL
CL
Pr1
i1F
Digital input configuration
EAL; bAL; PAL; dor;
dEF; Htr, AUS
AUS
AUS
Pr1
did
Digital input alarm delay
0 ÷ 255 min
15
15
Pr1
nPS
Number of activation of pressure
switch
0 ÷ 15
15
15
Pr2
odc
Compress status when open door
no; FAn; CPr; F_C
no
no
Pr2
rrd
Regulation restart with door open
alarm
n; Y
Y
Y
Pr2
HES
Differential for Energy Saving
[-30°C ÷ 30°C]
[-54°F÷54°F]
[1°C]
[1°F]
[1°C]
[1°F]
Pr2
Adr
Serial address
0 ÷ 247
1
1
Pr2
PbC
Kind of probe
PtM; PtC
PtM
PtM
Pr2
onF
on/off key enabling
nU; oFF; ES
nU
nU
Pr2
rSE
Real set point value
actual set
--
--
Pr2
rEL
Software release
--
--
--
Pr2
Ptb
Map code
--
--
--
Pr2

This manual suits for next models

4

Other Emerson Controllers manuals

Emerson REGAL 3F User manual

Emerson

Emerson REGAL 3F User manual

Emerson Fisher LR125 Series User manual

Emerson

Emerson Fisher LR125 Series User manual

Emerson BETTIS RTS FQ User manual

Emerson

Emerson BETTIS RTS FQ User manual

Emerson FISHER 912N Series User manual

Emerson

Emerson FISHER 912N Series User manual

Emerson VSG User manual

Emerson

Emerson VSG User manual

Emerson Site Supervisor User manual

Emerson

Emerson Site Supervisor User manual

Emerson Fisher KC Series User manual

Emerson

Emerson Fisher KC Series User manual

Emerson Fisher HSRL Series User manual

Emerson

Emerson Fisher HSRL Series User manual

Emerson EZH Series User manual

Emerson

Emerson EZH Series User manual

Emerson Vilter MicroVission Operation manual

Emerson

Emerson Vilter MicroVission Operation manual

Emerson Dixell iChill IC200D EVO Series Wiring diagram

Emerson

Emerson Dixell iChill IC200D EVO Series Wiring diagram

Emerson Dixell XR44CX Wiring diagram

Emerson

Emerson Dixell XR44CX Wiring diagram

Emerson Fisher 1051 User manual

Emerson

Emerson Fisher 1051 User manual

Emerson TESCOM 04 Series Setup guide

Emerson

Emerson TESCOM 04 Series Setup guide

Emerson MR105 User manual

Emerson

Emerson MR105 User manual

Emerson EL-O-Matic F-Series User guide

Emerson

Emerson EL-O-Matic F-Series User guide

Emerson Bettis RTS User manual

Emerson

Emerson Bettis RTS User manual

Emerson Y696 User manual

Emerson

Emerson Y696 User manual

Emerson Bettis 2000 Series Manual

Emerson

Emerson Bettis 2000 Series Manual

Emerson ControlWave MICRO Quick guide

Emerson

Emerson ControlWave MICRO Quick guide

Emerson EXD-SH2K User manual

Emerson

Emerson EXD-SH2K User manual

Emerson EXD-TEVI User manual

Emerson

Emerson EXD-TEVI User manual

Emerson EC2-552 User manual

Emerson

Emerson EC2-552 User manual

Emerson Yarway 20-55 Quick guide

Emerson

Emerson Yarway 20-55 Quick guide

Popular Controllers manuals by other brands

IDEC SmartAXIS Touch FT1A Series user manual

IDEC

IDEC SmartAXIS Touch FT1A Series user manual

dalap TRR Series user manual

dalap

dalap TRR Series user manual

Samson Trovis 6400 Mounting and operating instructions

Samson

Samson Trovis 6400 Mounting and operating instructions

SBC PCD2.M4160 user manual

SBC

SBC PCD2.M4160 user manual

Ametek MP3 SCR DeviceNet Head HDR HMI Manual

Ametek

Ametek MP3 SCR DeviceNet Head HDR HMI Manual

progressive automations PA-12 manual

progressive automations

progressive automations PA-12 manual

Pretorian iClick AUS instructions

Pretorian

Pretorian iClick AUS instructions

Toro TEMPUS Series user guide

Toro

Toro TEMPUS Series user guide

AMX AXB-EM232 Specifications

AMX

AMX AXB-EM232 Specifications

Enttec PIXELATOR MINI Quick start manual

Enttec

Enttec PIXELATOR MINI Quick start manual

vanEE 41303 Installation and user guide

vanEE

vanEE 41303 Installation and user guide

SCAD SensiStat manual

SCAD

SCAD SensiStat manual

Zmotion XPLC300 manual

Zmotion

Zmotion XPLC300 manual

Ude WZ-600 manual

Ude

Ude WZ-600 manual

Omron ES100P user manual

Omron

Omron ES100P user manual

Mitsubishi Electric MELSEC Q Series Handbook

Mitsubishi Electric

Mitsubishi Electric MELSEC Q Series Handbook

Sonelco PCB1245 manual

Sonelco

Sonelco PCB1245 manual

Siemens SIMATIC S7-200 Driver manual

Siemens

Siemens SIMATIC S7-200 Driver manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.