7�3 Partial-Stroke Test
The “Partial-Stroke Test” (“On-line”) can be performed to improve the PFDAVG value.
A typical partial-stroke value is 15% of the stroke.
The “Partial-Stroke Test” (“On line”) can be performed to satisfy PFDAVG (average
probability of failure on demand) value.
• Recommended Test Interval = 1 to 3 months.
• Procedure:
— Operate the Actuator/Valve assembly for No 1 open/close cycles 15/20%
of the stroke.
— Verify the Correct performing of partial-stroke operation (for example,
check locally, or automatically via Logic solver, or via the PST system the
correct movement of the actuator/valve till 15/20% of the stroke).
The above parameters to check will depend from the partial-stroke test system available.
Considering the application of the above described Partial-Stroke Test procedure, the
“Diagnostic Coverage” is >90 %.
7�4 Proof Test and Periodic Maintenance
We advise to perform the following checks upon each proof test interval complying with
the rules and regulations of the country of nal installation:
• Visually check the entire actuator as well as the control system (where foreseen).
• Ensure there are no leaks on the actuator parts under pressure.
• Check pneumatic connections for leaks. Tighten tube ttings as required.
• Check if manual override (where foreseen) is regular.
• Check if pneumatic lter cartridge (where foreseen) is sound and lter bowl (where
foreseen) has been cleaned properly.
• Check the setting of the relief valves (where foreseen).
• Verify that the power uid supply pressure value is within the required range.
• Remove built-up dust and dirt from all actuator surfaces.
• Inspect actuator paint work for damages to ensure continued corrosion protection.
Touch-up as required in accordance with the applicable paint specication.
• Operate the Actuator/Valve assembly for No 2 open/close complete cycles with
complete closing of the valve.
• Verify the correct performing of open – close operations (for example, check
locally, or automatically via Logic solver, the correct movement of the actuator).
The Installation, Operation and Maintenance manual denes a minimum maintenance
interval after 500.000 cycles for the EL-O-Matic E and P Series actuators. This addresses
components that may have age related degradation. When the maintenance interval has
elapsed a complete overhaul of the actuator is required.
9