Instruction Manual Supplement
D103790X012
1052 Actuator
October 2017
8
Appendix A
Sample Startup Checklist
This appendix provides a sample Startup Checklist for a 1052 actuator. A Startup Checklist will provide guidance
during the final control elements employment.
Start-Up Checklist
The following checklist may be used as a guide to employ the 1052 actuator in a safety critical SIF compliant to
IEC61508.
# Activity Result Verified
By Date
Design
Target Safety Integrity Level and PFDAVG determined
Correct valve mode chosen (Failclosed, Failopen)
Design decision documented
Pneumatic compatibility and suitability verified
SIS logic solver requirements for valve tests defined and documented
Routing of pneumatic connections determined
SIS logic solver requirements for partial stroke tests defined and
documented
Design formally reviewed and suitability formally assessed
Implementation
Physical location appropriate
Pneumatic connections appropriate and according to applicable codes
SIS logic solver valve actuation test implemented
Maintenance instructions for proof test released
Verification and test plan released
Implementation formally reviewed and suitability formally assessed
Verification and Testing
Electrical connections verified and tested
Pneumatic connection verified and tested
SIS logic solver valve actuation test verified
Safety loop function verified
Safety loop timing measured
Bypass function tested
Verification and test results formally reviewed and suitability formally
assessed
Maintenance
Tubing blockage / partial blockage tested
Safety loop function tested
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
E2013, 2017 Fisher Controls International LLC. All rights reserved.
Fisher, Control-Disk, and Vee-Ball are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co.
Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property
of their respective owners.
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.