Introduction
This installation guide provides instructions for installation, 
startup and adjustment. To receive a copy of the 
instruction manual, contact your local Sales Office or view 
a copy at www.fisher.com. For further information refer to: 
Type 627F Instruction Manual, D101545X012.
PED Categories
This product may be used as a safety accessory with 
pressure equipment in the following Pressure Equipment 
Directive categories. It may also be used outside of the 
Pressure Equipment Directive using sound engineering 
practice (SEP) per table below. For information on the 
current PED revision see Bulletin: D103053X012.
PRODUCT SIZE CATEGORIES FLUID TYPE
DN 20, 25 / NPS 3/4, 1 SEP 1
DN 50 / NPS 2 II
Specifications
Body Sizes and End Connection Styles
Ductile Iron: 3/4, 1 or 2 NPT 
Steel: 3/4, 1 or 2 NPT; DN 25 or 50 / NPS 
1 or 2, CL150 RF, CL300 RF, CL600 RF, 
PN 16/25/40 RF Flanged 
Maximum Inlet and Differential Pressures(1)
See Table 1
Minimum Pressure Differential
1.4 bar d / 20 psid 
Maximum Emergency Outlet Pressure(1)
17.2 bar / 250 psig for all Type 627F actuators and 
Type 6351F pilot components
Outlet Pressure Ranges
0.34 to 6.9 bar / 5 to 100 psig
Proof Test Pressure
All Pressure Retaining Components have been 
proof tested per Directive.
Temperature Capabilities(1)
-29 to 82°C / -20 to 180°F
Installation 
!
WARNING
Only qualied personnel should install 
or service a regulator. Regulators 
should be installed, operated and 
maintained in accordance with 
international and applicable codes 
and regulations and Emerson Process 
Management Regulator Technologies, 
Inc. instructions.
If the regulator vents uid or a leak 
develops in the system, it indicates that 
service is required. Failure to take the 
regulator out of service immediately may 
create a hazardous condition.
Personal injury, equipment damage or 
leakage due to escaping uid or bursting 
of pressure-containing parts may result 
if this regulator is overpressured or 
is installed where service conditions 
could exceed the limits given in the 
Specications section, or where 
conditions exceed any ratings of the 
adjacent piping or piping connections.
To avoid such injury or damage, provide 
pressure-relieving or pressure-limiting 
devices (as required by the appropriate 
code, regulation or standard) to prevent 
service conditions from exceeding limits.
Additionally, physical damage to the 
regulator could result in personal injury 
and property damage due to escaping 
uid. To avoid such injury and damage, 
install the regulator in a safe location.
Clean out all pipelines before installation of the 
regulator and check to be sure the regulator has not 
been damaged or has collected foreign material during 
shipping. For NPT bodies, apply pipe compound to the 
external pipe threads. For anged bodies, use suitable 
line gaskets and approved piping and bolting practices. 
Install the regulator in any position desired, unless 
otherwise specied, but be sure ow through the body 
is in the direction indicated by the arrow on the body.
1. The pressure/temperature limits in this installation guide or any applicable standard limitation should not be exceeded.
Type 627F
Installation Guide
D101545X014