
Table 2-1: Troubleshooting (continued)
Error Recommended action(s)
Configuration lost The meter configuration has reset to default values and the
meter is not configured correctly to measure flow and the
meter has performed a Cold Start.
•Unless the Cold Start occurred after upgrading firmware,
replace the CPU Module (see Replace the CPU Module).
•If the cold start occurred after a firmware upgrade, fully re-
configure the meter from a previously saved configuration
using the Tools → Edit/Compare Configuration in
MeterLink.
Electronics Temperature is Out
Of Nominal Range
Temperature of the electronics is out of nominal operating
range (below -40 °C or above 100 °C) which could lead to a
system failure.
•Attempt to warm or cool the meter electronics housing.
•If the electronics is mounted to the meter and the process
fluid in the meter is over 65 °C, you must remote mount the
electronics off of the meter body.
•Collect a Maintenance log using MeterLink while the meter
is experiencing the issue and contact your Emerson Flow
service representative.
Flow pressure is outside the
alarm limits
•Startup Issues:
—Verify that there is voltage to the pressure sensor from
either the meter's power supply board or from an
external power supply.
—If using an analog pressure device, verify that the
pressure sensor is properly wired to the connector.
—Verify the input is properly configured for your pressure
input.
—If using a flow computer to write pressure to the meter,
verify that it is properly writing to fixed flow pressure in
the proper units.
•Run Time Issues:
—If using an analog pressure device and input reading is 0,
check if IsAI2Avail is equal to 1 in the Meter Information
dialog in MeterLink. If it is not 1, either the I/O Board has
been removed or is damaged. Reinstall or replace the
CPU Module if this value is 0.
—If using an analog pressure device, verify that the
pressure sensor is working properly.
—If using an analog pressure device, recheck wiring and
switch settings.
—If a flow computer is writing values to the fixed flow
pressure, verify that the flow computer is still writing
valid values without Modbus write errors.
—Re-verify the pressure input settings are correct.
Troubleshooting Maintenance and Troubleshooting Manual
April 2022 00809-0100-3812
20 Emerson.com/Rosemount