manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Emerson
  6. •
  7. Transmitter
  8. •
  9. Emerson Rosemount 3051HT User manual

Emerson Rosemount 3051HT User manual

Other manuals for Rosemount 3051HT

4

Other Emerson Transmitter manuals

Emerson Rosemount 5600 Series User manual

Emerson

Emerson Rosemount 5600 Series User manual

Emerson Rosemount 708 User manual

Emerson

Emerson Rosemount 708 User manual

Emerson Rosemount Analytical Oxymitter 4000 User manual

Emerson

Emerson Rosemount Analytical Oxymitter 4000 User manual

Emerson PT4 User manual

Emerson

Emerson PT4 User manual

Emerson Rosemount 5408 User manual

Emerson

Emerson Rosemount 5408 User manual

Emerson Rosemount 2088 User manual

Emerson

Emerson Rosemount 2088 User manual

Emerson Rosemount 1199 User manual

Emerson

Emerson Rosemount 1199 User manual

Emerson Rosemount 4600 User manual

Emerson

Emerson Rosemount 4600 User manual

Emerson Rosemount 1066 User manual

Emerson

Emerson Rosemount 1066 User manual

Emerson Rosemount 2051 User manual

Emerson

Emerson Rosemount 2051 User manual

Emerson Rosemount 848T User manual

Emerson

Emerson Rosemount 848T User manual

Emerson Rosemount HART Modbus VeriCase 3308 Series User manual

Emerson

Emerson Rosemount HART Modbus VeriCase 3308 Series User manual

Emerson Rosemount Oxymitter 4000 User manual

Emerson

Emerson Rosemount Oxymitter 4000 User manual

Emerson Rosemount TCL User manual

Emerson

Emerson Rosemount TCL User manual

Emerson Rosemount 644h User manual

Emerson

Emerson Rosemount 644h User manual

Emerson Rosemount MultiVariable 3051SMV User manual

Emerson

Emerson Rosemount MultiVariable 3051SMV User manual

Emerson Rosemount 3051S Series User manual

Emerson

Emerson Rosemount 3051S Series User manual

Emerson Micro Motion 4200 User manual

Emerson

Emerson Micro Motion 4200 User manual

Emerson Rosemount 708 User manual

Emerson

Emerson Rosemount 708 User manual

Emerson MICRO MOTION 2700 Quick guide

Emerson

Emerson MICRO MOTION 2700 Quick guide

Emerson Rosemount 3051 User manual

Emerson

Emerson Rosemount 3051 User manual

Emerson Rosemount 5408 User manual

Emerson

Emerson Rosemount 5408 User manual

Emerson Rosemount 644 User manual

Emerson

Emerson Rosemount 644 User manual

Emerson Rosemount OCX 8800 User manual

Emerson

Emerson Rosemount OCX 8800 User manual

Popular Transmitter manuals by other brands

Seneca K120RTD installation manual

Seneca

Seneca K120RTD installation manual

Nautel GV40 installation manual

Nautel

Nautel GV40 installation manual

HumanTechnik cm-light operating instructions

HumanTechnik

HumanTechnik cm-light operating instructions

INOR APAQ C130 TC User instructions

INOR

INOR APAQ C130 TC User instructions

Linear DXS-64 operating instructions

Linear

Linear DXS-64 operating instructions

FeinTech ABT00102 instruction manual

FeinTech

FeinTech ABT00102 instruction manual

Geo Web Pack quick start guide

Geo

Geo Web Pack quick start guide

Inovonics EchoStream EN1210W installation instructions

Inovonics

Inovonics EchoStream EN1210W installation instructions

IKONNIK KA-6 quick start guide

IKONNIK

IKONNIK KA-6 quick start guide

Rohde & Schwarz SR8000 Series System manual

Rohde & Schwarz

Rohde & Schwarz SR8000 Series System manual

Audio Technica UniPak ATW-T93 Installation and operation

Audio Technica

Audio Technica UniPak ATW-T93 Installation and operation

NIVELCO EasyTREK SCA-300 Series Programming manual

NIVELCO

NIVELCO EasyTREK SCA-300 Series Programming manual

Honeywell 5816WMBR installation instructions

Honeywell

Honeywell 5816WMBR installation instructions

Kamstrup READy MTU Installation and operation guide

Kamstrup

Kamstrup READy MTU Installation and operation guide

Omega ZW Series user guide

Omega

Omega ZW Series user guide

ABB Field 264H Instructions for installation

ABB

ABB Field 264H Instructions for installation

Dejero EnGo 3x manual

Dejero

Dejero EnGo 3x manual

Rosemount 4600 Reference manual

Rosemount

Rosemount 4600 Reference manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Quick Start Guide
00825-0300-4091, Rev BA
June 2020
Rosemount™ 3051HT Hygienic Pressure
Transmitter
with PROFIBUS® PA Protocol
Safety messages
NOTICE
This guide provides basic guidelines for the Rosemount 3051HT Transmitter. It does not provide
instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof,
Flameproof, or intrinsically safe (I.S.) installations.
WARNING
Explosions could result in death or serious injury.
Installation of device in an explosive environment must be in accordance with appropriate local,
national, and international standards, codes, and practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is
applied to the unit.
Ensure device is installed in accordance with intrinsically safe or non-incendive field practices.
Before connecting a handheld communicator in an explosive atmosphere, ensure the instruments are
installed in accordance with intrinsically safe or non-incendive field wiring practices.
Verify that the operating environment of the gauge is consistent with the appropriate hazardous
locations certifications.
Electrical shock can result in death or serious injury.
Care must be taken during transportation of power module to prevent electrostatic charge build-up.
Device must be installed to ensure a minimum antenna separation distance of 8 in. (20 cm) from all
persons.
Process leaks may cause harm or result in death.
Handle the device carefully.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end
users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your
system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for
all systems used within the facility.
Failure to follow safe installation guidelines could result in death or serious injury.
Ensure only qualified personnel perform the installation.
Apply wrench only to the flats, not on housing.
The battery is not replaceable in a hazardous location.
Quick Start Guide June 2020
2 Emerson.com/Rosemount
CAUTION
Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by
mounting the device so the process can drain away.
Interfering or blocking the atmospheric reference port will cause the device to output erroneous
pressure values.
Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by
mounting the device so the process can drain away.
Absolute pressure devices are calibrated at the factory. Trimming adjusts the position of the factory
characterization curve. It is possible to degrade performance of the device if any trim is done
improperly or with inaccurate equipment.
Individuals who handle products exposed to a hazardous substance can avoid injury if they are
informed of and understand the hazard. The product being returned will require a copy of the required
Material Safety Data Sheet (MSDS) for each substance must be included with the returned goods.
Contents
Transmitter installation................................................................................................................ 5
Basic configuration.....................................................................................................................11
Product certifications................................................................................................................. 14
June 2020 Quick Start Guide
Quick Start Guide 3
Quick Start Guide June 2020
4 Emerson.com/Rosemount
1 Transmitter installation
1.1 Mount the transmitter
Place the transmitter to the desired orientation before mounting.
Transmitter must not be securely mounted or clamped in place when
changing transmitter orientation.
Conduit entry orientation
When installing a Rosemount 3051HT, it is recommended installing so a
conduit entry faces downward or parallel to the ground to maximize
drainability when cleaning.
Environmental seal for housing
Thread sealing (PTFE) tape or paste on male threads of conduit is required to
provide a watertight/dustproof conduit seal and meets requirements of
NEMA® Type 4X, IP66, IP68, and IP69K. Consult factory if other Ingress
Protection ratings are required.
Note
IP69K rating only available on units with a SST housing and option code V9 in
the model string.
For M20 threads, install conduit plugs to full thread engagement or until
mechanical resistance is met.
In-line gauge transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage
transmitter is located on the neck of the transmitter via a protected gage
vent (See Figure 1-1).
Keep the vent path free from obstructions including but not limited to paint,
dust, and viscous fluids by mounting the transmitter so the process can drain
away.
June 2020 Quick Start Guide
Quick Start Guide 5
Figure 1-1: In-line Protected Gage Vent Low Side Pressure Port
Aluminum Polished 316 SST
A. Low side pressure port (atmospheric reference)
Clamping
When installing clamp, follow recommended torque values provided by
gasket manufacturer.
Note
To maintain performance, torquing a 1.5-in. Tri Clamp beyond 50 in-lb. is
not recommended on pressure ranges below 20 psi.
1.2 Setting the security switch
The security switch allows ( ) or prevents ( ) any configuration of the
transmitter.
Note
Default security is off ( ).
Setting the simulate switch
The security switch can be enabled or disabled in the software.
Procedure
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side.
Quick Start Guide June 2020
6 Emerson.com/Rosemount
WARNING
Explosions could result in death or serious injury.
In an explosion-proof/flameproof installation, do not remove the
transmitter covers when power is applied to the unit.
3. Slide the security switch into the preferred position.
4. Reattach the transmitter housing cover.
Tighten the cover until there is no gap between the cover and
housing to comply with explosion proof requirements.
1.3 The security and simulate switches
The security and simulate switches are located on the electronics.
Figure 1-2: Transmitter Electronics Board
Aluminum Polished 316 SST
A
B
A. Simulate switch
B. Security switch
1.4 Connect the wiring and power up
Procedure to connect the wiring and power up the transmitter.
Prerequisites
•Use copper wire of sufficient size to ensure the voltage across the
transmitter power terminals does not drop below 9 Vdc. A minimum of
12 Vdc under normal operating conditions is recommended. Shielded
twisted pair Type A cable is recommended.
June 2020 Quick Start Guide
Quick Start Guide 7
•Power supply voltage can be variable, especially under abnormal
conditions such as when operating on battery backup.
Procedure
1. To power the transmitter, connect the power leads to the terminals
indicated on the terminal block label.
Note
The Rosemount 3051 power terminals are polarity insensitive, which
means the electrical polarity of the power leads does not matter
when connecting to the power terminals. If polarity sensitive devices
are connected to the segment, terminal polarity should be followed.
When wiring to the screw terminals, the use of crimped legs is
recommended.
2. Ensure full contact with terminal block screw and washer. When
using a direct wiring method, wrap wire clockwise to ensure it is in
place when tightening the terminal block screw. No additional power
is needed.
Note
The use of a pin or a ferrule wire terminal is not recommended as the
connection may be more susceptible to loosening over time or under
vibration.
3. Ensure proper grounding. It is important the instrument cable shield
be:
a) Trimmed close and insulated from touching the transmitter
housing.
b) Connected to the next shield if cable is routed through a
junction box.
c) Connected to a good earth ground at the power supply end.
4. If transient protection is needed, refer to section Signal ground
wiring for grounding instructions.
5. Plug and seal unused conduit connections.
6. Reattach the transmitter covers.
a) The covers must only be capable of being released or
removed with the aid of a tool to comply with applicable
ordinary locations requirements.
Figure 1-3: Wiring
Aluminum Polished 316 SST
Quick Start Guide June 2020
8 Emerson.com/Rosemount
DP
A
B
D
E
C
DP
A
B
D
E
C
A. Minimize distance
B. Trim shield and insulate
C. Protective grounding terminal (do not ground cable shield at the
transmitter)
D. Insulate shield
E. Connect shield back to the power supply ground
1.4.1 Signal ground wiring
Do not run signal wiring in conduit or open trays with power wiring, or near
heavy electrical equipment. Grounding terminations are provided on the
outside of the electronics housing and inside the Terminal Compartment.
These grounds are used when transient protect terminal blocks are installed
or to fulfill local regulations.
Procedure
1. Remove the field terminals housing cover.
2. Connect the wiring pair and ground as indicated in Figure 1-3
a) Trim the cable shield as short as practical and insulate from
touching the transmitter housing.
Note
Do NOT ground the cable shield at the transmitter; if the
cable shield touches the transmitter housing, it can create
ground loops and interfere with communications.
b) Continuously connect the cable shields to the power supply
ground.
c) Connect the cable shields for the entire segment to a single
good earth ground at the power supply.
June 2020 Quick Start Guide
Quick Start Guide 9
Note
Improper grounding is the most frequent cause of poor
segment communications.
3. Replace the housing cover. It is recommended that the cover be
tightened until there is no gap between the cover and the housing.
4. Plug and seal unused conduit connections.
Note
The Rosemount 3051HT polished 316 SST housing only provides
ground termination inside the terminal compartment.
Quick Start Guide June 2020
10 Emerson.com/Rosemount