manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Emerson
  6. •
  7. Transmitter
  8. •
  9. Emerson Rosemount 644 User manual

Emerson Rosemount 644 User manual

Other manuals for Rosemount 644

8

Other Emerson Transmitter manuals

Emerson Rosemount 2051 User manual

Emerson

Emerson Rosemount 2051 User manual

Emerson Rosemount 1152 Alphaline User manual

Emerson

Emerson Rosemount 1152 Alphaline User manual

Emerson Rosemount 3051S Series User manual

Emerson

Emerson Rosemount 3051S Series User manual

Emerson Rosemount 5408 User manual

Emerson

Emerson Rosemount 5408 User manual

Emerson Rosemount 4088B MultiVariable User manual

Emerson

Emerson Rosemount 4088B MultiVariable User manual

Emerson Rosemount 56 User manual

Emerson

Emerson Rosemount 56 User manual

Emerson Oxymitter 5000 User manual

Emerson

Emerson Oxymitter 5000 User manual

Emerson Rosemount 2088 User manual

Emerson

Emerson Rosemount 2088 User manual

Emerson Rosemount 644h User manual

Emerson

Emerson Rosemount 644h User manual

Emerson Rosemount 3308 User manual

Emerson

Emerson Rosemount 3308 User manual

Emerson Rosemount 644h User manual

Emerson

Emerson Rosemount 644h User manual

Emerson Micro Motion Transmitters and Discrete Controllers Series... Operational manual

Emerson

Emerson Micro Motion Transmitters and Discrete Controllers Series... Operational manual

Emerson Rosemount OCX 8800 User manual

Emerson

Emerson Rosemount OCX 8800 User manual

Emerson Rosemount 3051 User manual

Emerson

Emerson Rosemount 3051 User manual

Emerson Rosemount 3051 User manual

Emerson

Emerson Rosemount 3051 User manual

Emerson Rosemount 2051 User manual

Emerson

Emerson Rosemount 2051 User manual

Emerson Rosemount 4600 User manual

Emerson

Emerson Rosemount 4600 User manual

Emerson wirelessHART Rosemount Series User manual

Emerson

Emerson wirelessHART Rosemount Series User manual

Emerson Rosemount 644 User manual

Emerson

Emerson Rosemount 644 User manual

Emerson Rosemount 550PT User manual

Emerson

Emerson Rosemount 550PT User manual

Emerson Rosemount Oxymitter 4000 User manual

Emerson

Emerson Rosemount Oxymitter 4000 User manual

Emerson 6081-P User manual

Emerson

Emerson 6081-P User manual

Emerson Rosemount 3051S Series User manual

Emerson

Emerson Rosemount 3051S Series User manual

Emerson Rosemount 148 User manual

Emerson

Emerson Rosemount 148 User manual

Popular Transmitter manuals by other brands

NIVELCO EasyTREK SCA-300 Series Programming manual

NIVELCO

NIVELCO EasyTREK SCA-300 Series Programming manual

Honeywell 5816WMBR installation instructions

Honeywell

Honeywell 5816WMBR installation instructions

Kamstrup READy MTU Installation and operation guide

Kamstrup

Kamstrup READy MTU Installation and operation guide

Omega ZW Series user guide

Omega

Omega ZW Series user guide

ABB Field 264H Instructions for installation

ABB

ABB Field 264H Instructions for installation

Alinco DJ-V17T Service manual

Alinco

Alinco DJ-V17T Service manual

Dejero EnGo 3x manual

Dejero

Dejero EnGo 3x manual

Rosemount 4600 Reference manual

Rosemount

Rosemount 4600 Reference manual

Speaka Professional 2342740 operating instructions

Speaka Professional

Speaka Professional 2342740 operating instructions

trubomat GAB 1000 instruction manual

trubomat

trubomat GAB 1000 instruction manual

Teledyne Analytical Instruments LXT-380 instructions

Teledyne Analytical Instruments

Teledyne Analytical Instruments LXT-380 instructions

Rondish UT-11 quick start guide

Rondish

Rondish UT-11 quick start guide

MG 10JRE instruction manual

MG

MG 10JRE instruction manual

Burkert 8177 operating instructions

Burkert

Burkert 8177 operating instructions

Firetide HotPort 3203 Hardware installation guide

Firetide

Firetide HotPort 3203 Hardware installation guide

Tele Radio T9-02 User instructions

Tele Radio

Tele Radio T9-02 User instructions

Rotronic HygroFlex HF3 Series user guide

Rotronic

Rotronic HygroFlex HF3 Series user guide

Jamara FCX6 Pro Tel Instruction

Jamara

Jamara FCX6 Pro Tel Instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Quick Start Guide
00825-0200-4728, Rev GA
April 2017
Note
Before installing the transmitter, confirm the correct device driver is loaded on the host
systems. See page 3 for System Readiness.
Rosemount™644 Temperature
Transmitter
with 4–20 mA HART®(Revision 5 and 7) Protocol
April 2017
2
Quick Start Guide
NOTICE
This guide provides basic guidelines for Rosemount 644 Transmitters. It does not provide instructions for
configuration, diagnostics, maintenance, service, troubleshooting, explosion-proof, flameproof, or intrinsically
safe (I.S.) installations. Refer to the Rosemount 644 Reference Manual for more instruction. The manual and
this guide is also available electronically on Emerson.com/Rosemount.
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local,
national, and international standards, codes, and practices. Review the approvals section of the Rosemount
644 Reference Manual for any restrictions associated with a safe installation.
Before connecting a HART-based communicator in an explosive atmosphere, make sure the instruments in
the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and the terminals. High voltage may be present on leads can cause electrical
shock.
Conduit/cable entries
Unless marked, the conduit/cable entries in the transmitter housing use a 1/2–14 NPT thread form. Entries
marked “M20” are M20 x 1.5 thread form. On devices with multiple conduit entries, all entries will have the
same thread form. Only use plugs, adapters, glands, or conduit with a compatible thread form when closing
these entries.
When installing in a Hazardous Location, use only appropriately listed or Ex certified plugs, adapters, or
glands in cable/conduit entries.
Contents
System readiness . . . . . . . . . . . . . . . . . . . . . . . . . 3
Transmitter installation . . . . . . . . . . . . . . . . . . . 3
Safety instrumented systems . . . . . . . . . . . . . 17
Product Certifications . . . . . . . . . . . . . . . . . . . . 18
Quick Start Guide
3
April 2017
1.0 System readiness
1.1 Confirm HART Revision capability
If using HART based control or asset management systems, confirm the
HART capability of those systems prior to transmitter installation. Not all
systems are capable of communicating with HART Revision 7 Protocol. This
transmitter can be configured for either HART Revision 5 or 7.
For instructions on how to change the HART Revision of your transmitter, see
“Verify configuration” on page 4.
1.2 Confirm correct device driver
1. Verify the latest Device Driver files are loaded on your systems to ensure
proper communications.
2. Download the latest Device Driver at
Emerson.com/Device-Install-Kits/Device-Install-Kit-Search
Rosemount 644 Transmitter device revisions and files
Table 1 provides the information necessary to ensure the correct Device Driver
files and documentation are being used.
2.0 Transmitter installation
2.1 Set the alarm switch
Set the Rosemount 644 Transmitter alarm switch before putting the device into
operation.
Without an LCD display:
1. Set the loop to manual (if applicable) and disconnect the power.
2. Remove the housing cover.
3. Set the switch to the desired position (Hindicates High, Lindicates Low),
then reattach the housing cover. Enclosure covers must be fully engaged to
meet explosion-proof requirements.
Table 1. Rosemount 644 Device Revisions and Files
Software
date
NAMUR
software
revision
HART
software
revision
HART
universal
revision(1)
1. NAMUR software revision is located on the hardware tag of the device. HART software revision can be read using
a HART communication tool.
Device
revision(2)
2. Device Driver file names use Device and DD Revision, e.g. 10_01. HART Protocol is designed to enable legacy
device driver revisions to continue to communicate with new HART devices. To access new functionality, the
new Device Driver must be downloaded. It is recommended to download new Device Driver files to ensure full
functionality.
Manual document
number
Changes to
software (3)
3. HART Revision 5 and 7 Selectable, Dual Sensor support, Safety Certified, Advanced Diagnostics (if ordered),
Enhanced Accuracy and Stability (if ordered).
June 2012 1.1.1 3
5 8
00809-0100-4728 See Footnote 3 for
list of changes.
7 9
April 2017
4
Quick Start Guide
4. Apply power and set the loop to automatic control.
Figure 1. Alarm Switch Placement
A. Alarm switch
Note
If using an LCD display, remove the display by detaching it from the top of the device, set
the switch to the desired position, reattach the LCD display, and reattach the housing
cover. Enclosure covers must be fully engaged to meet explosion-proof requirements.
2.2 Verify configuration
Verify the configuration of the Rosemount 644 Transmitter device upon
receiving your transmitter using any HART-compliant configuration tool. See
the Rosemount 644 Reference Manual for configuration instructions using AMS
Device Manager.
The Rosemount 644 Transmitter communicates using the Field Communicator
(communication requires a loop resistance between 250 and 1100 ohms). Do
not operate when power is below 12 Vdc at the transmitter terminal. See
Rosemount 644 Reference Manual and Field Communicator Reference Manual
for more information.
Verify configuration with a Field Communicator
A Rosemount 644 DD (Device Descriptor) must be installed on the Field
Communicator to verify the configuration. Fast Key sequences for the latest DD
are shown in Table 2 on page 5. For Fast Key sequences using legacy DD's,
contact your local Emerson™representative.
Perform the following steps to determine if an upgrade is required.
1. Connect the sensor (see the wiring diagram located on the device’s top
label).
Rosemount 644 Transmitter Rosemount 644 Field Mount
A
Quick Start Guide
5
April 2017
2. Connect the bench power supply to the power terminals (“+” or “–”).
3. Connect a Field Communicator to the loop across a loop resistor or at the
power/signal terminals on the transmitter.
4. The following message will appear if the communicator has a previous
version of the DDs:
Device Description Not Installed…The Device Description for manufacturer 0x26
model 0x2618 dev rev 8/9 is not installed on the System Card…see Programming
Utility for details on Device Description updates…Do you wish to proceed in forward
compatibility mode?
If this notice does not appear, the latest DD is installed. If the latest version is not
available, the communicator will communicate properly, however, when the
transmitter is configured to utilize advanced transmitter features, there will be
trouble communicating and a prompt to turn off the communicator will display.
To prevent this from happening, upgrade to the latest DD or answer NO to the
question and default to the generic transmitter functionality.
Note
Emerson recommends installing the latest DD to access the complete functionality. Visit
Emerson.com/Field-Communicator for information on updating the DD Library.
Field Communicator user interface
Two user interfaces are available to configure this device.
The Device Revision 8 and 9 (HART 5 and 7), DD Revision 1 Fast Key Sequence in
Table 2 may be used for transmitter configuration and startup.
Figure 2. Device Dashboard Field Communicator Interface
Table 2. Device Revision 8 and 9 (HART 5 and 7), DD Revision 1 Fast Key Sequence
Function HART 5 HART 7
Alarm Values 2, 2, 5, 6 2, 2, 5, 6
Analog Calibration 3, 4, 5 3, 4, 5
Analog Output 2, 2, 5, 1 2, 2, 5, 1
April 2017
6
Quick Start Guide
Average Temperature Setup 2, 2, 3, 3 2, 2, 3, 3
Burst Mode 2, 2, 8, 4 2, 2, 8, 4
Comm Status N/A 1, 2
Configure additional messages N/A 2, 2, 8, 4, 7
Configure Hot Backup™2, 2, 4, 1, 3 2, 2, 4, 1, 3
D/A Trim 3, 4, 4, 1 3, 4, 4, 1
Damping Values 2, 2, 1, 5 2, 2, 1, 6
Date 2, 2, 7, 1, 2 2, 2, 7, 1, 3
Display Setup 2, 1, 4 2, 1, 4
Descriptor 2, 2, 7, 1, 4 2, 2, 7, 1, 5
Device Information 1, 8, 1 1, 8, 1
Differential Temperature Setup 2, 2, 3, 1 2, 2, 3, 1
Drift Alert 2, 2, 4, 2 2, 2, 4, 2
Filter 50/60 Hz 2, 2, 7, 4, 1 2, 2, 7, 4, 1
First Good Temperature Setup 2, 2, 3, 2 2, 2, 3, 2
Hardware Revision 1, 8, 2, 3 1, 8, 2, 3
HART Lock N/A 2, 2, 9, 2
Intermittent Sensor Detect 2, 2, 7, 4, 2 2, 2, 7, 4, 2
Loop Test 3, 5, 1 3, 5, 1
Locate Device N/A 3, 4, 6, 2
Lock Status N/A 1, 8, 3, 8
LRV (Lower Range Value) 2, 2, 5, 5, 3 2, 2, 5, 5, 3
LSL (Lower Sensor Limit) 2, 2, 1, 7, 2 2, 2, 1, 8, 2
Message 2, 2, 7, 1, 3 2, 2, 7, 1, 4
Open Sensor Holdoff 2, 2, 7, 3 2, 2, 7, 3
Percent Range 2, 2, 5, 2 2, 2, 5, 2
Sensor 1 Configuration 2, 1, 1 2, 1, 1
Sensor 2 Configuration 2, 1, 1 2, 1, 1
Sensor 1 Serial Number 2, 2, 1, 6 2, 2, 1, 7
Sensor 2 Serial Number 2, 2, 2, 7 2, 2, 2, 8
Sensor 1 Type 2, 2, 1, 2 2, 2, 1, 3
Sensor 2 Type 2, 2, 2, 2 2, 2, 2, 3
Sensor 1 Unit 2, 2, 1, 4 2, 2, 1, 5
Sensor 2 Unit 2, 2, 2, 4 2, 2, 2, 5
Sensor 1 Status N/A 2, 2, 1, 2
Sensor 2 Status N/A 2, 2, 2, 2
Table 2. Device Revision 8 and 9 (HART 5 and 7), DD Revision 1 Fast Key Sequence
Function HART 5 HART 7
Quick Start Guide
7
April 2017
Input or verify Callendar Van-Dusen constants
If sensor matching is being used with this combination of a transmitter and
sensor, verify the constants input.
1. From the HOME screen, select 2 Configure, 2 Manual Setup, 1 Sensor.
2. Set the control loop to manual and select OK.
3. At the ENTER SENSOR TYPE prompt, select Cal VanDusen.
4. At the ENTER SENSOR CONNECTION prompt, select the appropriate number of
wires.
5. Enter the Ro, Alpha, Delta, and Beta values from the stainless steel tag
attached to the special-order sensor when prompted.
6. Return the control loop to automatic control and select OK.
7. To disable the transmitter-sensor matching feature from the HOME screen
select 2 Configure, 2 Manual Setup, 1 Sensor, 10 SensorMatching-CVD.
8. Choose the appropriate sensor type from the ENTER SENSOR TYPE prompt.
Verifying configuration with Local Operator Interface (LOI)
The optional LOI can be used for commissioning the device. The LOI is a
2-button design. To activate the LOI, push any button. LOI button functionality
is shown on the bottom corners of the display. See Table 3 and Figure 4 for
button operation and menu information.
Simulate Digital Signal N/A 3, 5, 2
Software Revision 1, 8, 2, 4 1, 8, 2, 4
Tag 2, 2, 7, 1, 1 2, 2, 7, 1, 1
Long Tag N/A 2, 2, 7, 1, 2
Terminal Temperature 2, 2, 7, 1 2, 2, 8, 1
URV (Upper Range Value) 2, 2, 5, 5, 2 2, 2, 5, 5, 2
USL (Upper Sensor Limit) 2, 2, 1, 7, 2 2, 2, 1, 8, 2
Variable Mapping 2, 2, 8, 5 2, 2, 8, 5
2-wire Offset Sensor 1 2, 2, 1, 9 2, 2, 1, 10
2-wire Offset Sensor 2 2, 2, 2, 9 2, 2, 2, 10
Table 2. Device Revision 8 and 9 (HART 5 and 7), DD Revision 1 Fast Key Sequence
Function HART 5 HART 7
April 2017
8
Quick Start Guide
Figure 3. Local Operator Interface
Figure 4. LOI Menu
Switch HART Revision mode
Not all systems are capable of communicating with HART Revision 7 Protocol.
This transmitter can be configured for either HART Revision 5 or 7 using a HART
capable configuration tool.
Table 3. LOI Button Operation
Button
Left No SCROLL
Right Yes ENTER
Quick Start Guide
9
April 2017
Updated configuration menus include a HART Universal Revision parameter that
can be configured to 5 or 7 if accessible by your system. See Table 2 for the Fast
Key sequence.
If the HART configuration tool is not capable of communicating with HART
Revision 7, the configuration menus in Table 2 will not be available. To switch
the HART Universal Revision parameter from generic mode, follow the
instructions below.
1. Go to Configure>Manual Setup>Device Information>Identification>Message.
a. To change your device to HART Revision 7, Enter: “HART7” in the
Message field.
b. To change your device to HART Revision 5, Enter: “HART5” in the
Message field.
Note
See Table 2 on page 5 to change HART Revision when the correct Device Driver is loaded.
2.3 Mount the transmitter
Mount the transmitter at a high point in the conduit run to prevent moisture
from draining into the transmitter housing.
Head mount transmitter with DIN plate style sensor installation
1. Attach the thermowell to the pipe or process container wall.
2. Install and tighten the thermowell before applying process pressure.
3. Verify the transmitter failure mode switch position.
4. Assemble the transmitter to the sensor. Push the transmitter mounting
screws through the sensor mounting plate.
5. Wire the sensor to the transmitter (see “Wire and apply power” on page 12).
6. Insert the transmitter-sensor assembly into the connection head.
a. Thread the transmitter mounting screw into the connection head
mounting holes.
b. Assemble the extension to the connection head.
c. Insert the assembly into the thermowell.
7. If using a cable gland, properly attach the cable gland to a housing conduit
entry.
8. Insert the shielded cable leads into the connection head through the cable
entry.
9. Connect the shielded power cable leads to the transmitter power terminals.
Avoid contact with sensor leads and sensor connections.
10. Connect and tighten the cable gland.
April 2017
10
Quick Start Guide
11. Install and tighten the connection head cover. Enclosure covers must be
fully engaged to meet explosion-proof requirements.
Head mount transmitter with threaded sensor installation (two
or three conduit entries)
1. Attach the thermowell to the pipe or process container wall.
2. Install and tighten thermowells before applying process pressure.
3. Attach necessary extension nipples and adapters to the thermowell.
4. Seal the nipple and adapter threads with silicone tape.
5. Screw the sensor into the thermowell. Install drain seals if required for
severe environments or to satisfy code requirements.
6. Verify the transmitter failure mode switch is in the desired position.
7. To verify the correct installation of Integral Transient Protection (option
code T1) on the Rosemount 644 Transmitter, confirm the following steps
have been completed:
a. Ensure the transient protector unit is firmly connected to the
transmitter puck assembly.
b. Ensure the transient protector power leads are adequately secured
under the transmitter power terminal screws.
c. Verify the transient protector’s ground wire is secured to the internal
ground screw found within the universal head.
Note
The transient protector requires the use of an enclosure of at least 3.5-in. (89 mm) in
diameter.
8. Pull the sensor wiring leads through the universal head and transmitter
center hole.
9. Mount the transmitter in the universal head by threading the transmitter
mounting screws into the universal head mounting holes.
10. Mount the transmitter-sensor assembly into the thermowell, or remote
mount if desired.
11. Seal adapter threads with silicone tape.
12. Pull the field wiring leads through the conduit into the universal head.
Attach the sensor and power leads to the transmitter. Avoid contact with
other terminals.
A. Connection head cover
B. Connection head
C. Thermowell
D. Transmitter mounting screws
E. Integral mount sensor with flying leads
F. Extension
AB C
DEF