EUROSTER UNI2 – INSTRUCTION MANUAL 6
fr st pr tecti n, anti-fr st temperature
The anti-frost algorithm is activated when the temperature of the particular circuit
sensor drops below the preset level. n such case both the boiler and the pump are
activated. The schedule settings do not affect the operation of this protection.
CAUTION! The pr tecti n is disabled by default.
sens r c rrecti n
CH1 or CH2 circuit sensor correction allows to correct temperature reading errors, such
as the ones resulting from improper contact between the sensor and the pipe.
test
The test option allows to switch on the connected devices manually. For safety reasons,
when the selected output is being tested, all other outputs are switched off.
Settings f r DHW circuit
turning the circuit n/ ff
This item enables to switch off the DHW circuit if it is not used.
hysteresis
t is a difference between the temperature at which the tank supplying pump is turned
off and turned on.
excess f DHW
The “excess of DHW” parameter determines the value by which the temperature of the
heat source must exceed the temperature of the tank. Setting a higher temperature
ensures an adequate heating capacity and compensates the heat loss due to the
imperfect insulation of pipes connecting the boiler and the tank.
f the temperature of the heat source is not sufficiently high, then the DHW tank
supplying pump is not switched on.
DHW pri rity
Switching on of the DHW priority means that the controller switches off the CH circuits
for the time of DHW heating in order to achieve the temperature preset for the tank as
fast as possible.
n case of operation with active communication mode, the circuits to perform DHW
priority must be selected in the communication menu.
pri rity perati n time, pri rity break time
Time limit for the DHW priority operation prevents excessive cooling of rooms when the
tank may not be properly heated in a reasonable time.
Non-zero priority break time must be set to use this function.
The DHW tank is heated for the time preset by the “priority operation time” parameter (
symbol active on the display screen), then the DHW priority is switched off for the
“priority break time” ( symbol flashing on the display). Subsequently, the DHW
priority is switched on again.
alarm temperature
f the tank is fed by another, additional heat source and if the tank temperature
exceeds the alarm temperature, then the controller switches on the DHW pump which
cools the tank. The pump is switched on only if the feeding temperature is lower than
the preset alarm temperature of the DHW tank. t is indicated with an error of DHW
overheating.
When using hot water special precautions must be taken in order to avoid burning.
fr st pr tecti n
The anti-frost algorithm is activated when the temperature of the DHW circuit sensor
drops below the preset level. n such case the boiler and the pump are switched on and
“AF” symbol flashes on the display. The schedule settings do not affect the operation of
this protection.
sens r c rrecti n
DHW circuit sensor correction allows to correct temperature reading errors, such as the
ones resulting from improper contact between the sensor and the pipe.
test
The test option allows to switch on the connected devices manually. For safety reasons,
when the selected output is being tested, all other outputs are switched off.