EUROSTER 11Z USER MANUAL 4
Configuration windows are numbered to facilitate manipulations. User may edit the following
controller parameters (presets):
1. CH pump TURN ON temperature
See section 12 for detailed description of conditions in which CH pump is turned
ON/OFF.
2. CH pump hysteresis
Difference between the temperature at which the controller turns the pump on and the
temperature at which the controller turns it off. See section 12 below for details.
. UHW temperature
Mean tank temperature that the controller will attempt to maintain manipulating the
pump.
ATTENTION: Too low tank temperatures ( 5-40ºC) help to grow various
bacteria within the tank, including the Legionella bacteria.
4. UHW pump hysteresis
Difference between the temperature at which the controller turns the pump on and the
temperature at which the controller turns it off. See section 12 below for details.
5. Boiler-tank temperature surplus
The preset tells how much the boiler temperature should exceed the tank temperature
(plus a constant value 3ºC) to enable UHW pump engaging without a risk that the tank
will chill out. Alternatively the preset tells how close tank/boiler temperatures (minus a
constant value 3ºC) will interrupt operation of the UHW pump.
6. UHW priority
Cold UHW tank may heat up faster if this mode of operation is activated: the CH system
pump is unconditionally turned OFF.
7. Boiler temperature sensor correction
A constant added to all values measured by boiler temperature (external) sensor to
compensate for differences in respect to water temperature inside the boiler.
8. UWH tank temperature sensor correction
A constant added to all values measured by tank temperature (external) sensor to
compensate for differences in respect to water temperature inside the tank.
9. CH pump manual operation (test)
Display current pump status commanded by the controller (0/1 = pump
disengaged/engaged). Press the knob and modify the parameter value to manually
control the pump. Press the knob once more or leave it inactive for 10 seconds to
resume automatic mode of control.
10. UHW pump manual operation (test)
Display current pump status commanded by the controller (0/1 = pump
disengaged/engaged). Press the knob and modify the parameter value to manually
control the pump. Press the knob once more or leave it inactive for 10 seconds to
resume automatic mode of control.
All controller presets are listed below:
Parameter Preset value Unit
No Name default min max
1 CH pump TURN ON temperature 40 20 80 °C
2 CH pump hysteresis 4 2 10 °C
3 UHW temperature 60 20 70 °C
4 UHW pump hysteresis 4 2 10 °C
5 Boiler tank temperature surplus 10 3 10 °C
6 UHW priority 1 (ON) 0 (OFF) 1 (ON)
7 Boiler temperature sensor correction 0 5 5 °C
8 UWH tank temperature sensor 0 5 5 °C