Fike FCP-75 User manual

B
P/N LS10147-003FK-E:B • ECN 00003636
Document LS10147-003FK-E
6/20/2022
Addressable Fire Alarm Control Panel
FCP-75
Manual

2FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control panel (FACP) with remote
notification capability—can provide early warning of a developing fire.
Such a system, however, does not assure protection against property
damage or loss of life resulting from a fire.
An emergency communication system—typically made up of an
automatic fire alarm system (as described above) and a life safety
communication system that may include an autonomous control unit
(ACU), local operating console (LOC), voice communication, and
other various interoperable communication methods—can broadcast
a mass notification message. Such a system, however, does not
assure protection against property damage or loss of life resulting
from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors be
located throughout a protected premises following the
recommendations of the current edition of the National Fire
ProtectionAssociation Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the recommendations
contained in the Guide for Proper Use of System Smoke Detectors,
which is made available at no charge to all installing dealers. This
document can be found at http://www.systemsensor.com/appguides/.
A study by the Federal Emergency Management Agency (an agency
of the United States government) indicated thatsmoke detectors may
not go off in as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not guarantee
warning or protection against fire. A fire alarm system may not
provide timely or adequate warning, or simply may not function, for a
variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the
detectors such as in chimneys, in or behind walls, on roofs, or on the
other side of closed doors. Smoke detectors also may not sense a
fire on another level or floor of a building.A second-floor detector, for
example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not
reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chimneys,
even wet or humid areas may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the
ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets,
such as air conditioning vents.
• Smoke particles may be drawn into air returns before reaching the
detector.
The amount of “smoke” present may be insufficient to alarm smoke
detectors. Smoke detectors are designed to alarm at various levels of
smoke density. If such density levels are not created by a developing
fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing chambers
tend to detect smoldering fires better than flaming fires, which have
little visible smoke. Detectors that have ionizing-type sensing
chambers tend to detect fast-flaming fires better than smoldering
fires. Because fires develop in different ways and are often
unpredictable in their growth, neither type of detector is necessarily
best and a given type of detector may not provide adequate warning
of a fire.
Smoke detectors cannot be expected to provide adequate warning of
fires caused by arson, children playing with matches (especially in
bedrooms), smoking in bed, and violent explosions (caused by
escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only
when heat on their sensors increases at a predetermined rate or
reaches a predetermined level. Rate-of-rise heat detectors may be
subject to reduced sensitivity over time. For this reason, the rate-of-
rise feature of each detector should be tested at least once per year
by a qualified fire protection specialist. Heat detectors are designed
to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room
as the control panel and in rooms used by the system for the
connection of alarm transmission wiring, communications, signaling,
and/or power. If detectors are not so located, a developing fire may
damage the alarm system, compromising its ability to report a fire.
Audible warning devices such as bells, horns, strobes, speakers
and displays may not alert people ifthese devices are located on the
other side of closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert people with a
disability or those who have recently consumed drugs, alcohol, or
medication. Please note that:
• An emergency communication system maytake priority over a fire
alarm system in the event of a life safety emergency.
• Voice messaging systems must be designed to meet intelligibility
requirements as defined by NFPA, local codes, andAuthorities
Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dissemi-
nated on any local displays.
• Strobes can, under certain circumstances, cause seizures in peo-
ple with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a
fire alarm signal, do not respond to or comprehend the meaning of
the signal.Audible devices, such as horns and bells, can have dif-
ferent tonal patterns and frequencies. It is the property owner's
responsibility to conduct fire drills and other training exercises to
make people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause
temporary or permanent hearing loss.
A life safety system will not operate without any electrical power. If
AC power fails, the system will operate from standby batteries only
for a specified time and only if the batteries have been properly
maintained and replaced regularly.
Equipment used in the system may not be technically compatible
with the control panel. It is essential to use only equipment listed for
service with your control panel.
Alarm Signaling Communications:
•IP connections rely on available bandwidth, which could be lim-
ited if the network is shared by multiple users or if ISP policies
impose restrictions on the amount of data transmitted. Service
packages must be carefully chosen to ensure that alarm signals
will always have available bandwidth. Outages by the ISP for
maintenance and upgrades may also inhibit alarm signals. For
added protection, a backup cellular connection is recommended.
•Cellular connections rely on a strong signal. Signal strength can
be adversely affected by the network coverage of the cellular car-
rier, objects and structural barriers at the installation location. Uti-
lize a cellular carrier that has reliable network coverage where the
alarm system is installed. For added protection, utilize an external
antenna to boost the signal.
•Telephone lines needed to transmit alarm signals from a premise
to a central monitoringstation may be out of service or temporarily
disabled. For added protection against telephone line failure,
backup alarm signaling connections are recommended.
The most common cause of life safety system malfunction is
inadequate maintenance. To keep the entire life safety system in
excellent working order, ongoing maintenance is required per the
manufacturer's recommendations, and UL and NFPA standards.At a
minimum, the requirements of NFPA 72 shall be followed.
Environments with large amounts of dust, dirt, or high air velocity
require more frequent maintenance. A maintenance agreement
should be arranged through the local manufacturer's representative.
Maintenance should be scheduled as required by National and/or
local fire codes and should be performed by authorized professional
life safety system installers only. Adequate written records of all
inspections should be kept. Limit-F-2020

FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be con-
nected to the fire alarm control panel. Disconnect all sources of
power before servicing. Control unit and associated equipment may
be damaged by removing and/or inserting cards, modules, or inter-
connecting cables while the unit is energized. Do not attempt to
install, service, or operate this unit until manuals are read and under-
stood.
CAUTION - System Re-acceptance Test after Software Changes:
To ensure proper system operation, this product must be tested in
accordance with NFPA 72 after any programming operation or
change in site-specific software. Re-acceptance testing is required
after any change, addition or deletion of system components, or after
any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions
known to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected, at
least 10% of initiating devices that are not directly affected by the
change, up to a maximum of 50 devices, must also be tested and
proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-
120º F and at a relative humidity 93% ± 2% RH (non-condensing) at
32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's
standby batteries and the electronic components may be adversely
affected by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and its peripherals be installed in
an environment with a normal room temperature of 15-27º C/60-80º
F.
Verify that wire sizes are adequate for all initiating and indicating
device loops. Most devices cannot tolerate more than a 10% I.R.
drop from the specified device voltage.
Like all solid state electronic devices, this system may operate
erratically or can be damaged when subjected to lightning induced
transients.Although no system is completely immune from lightning
transients and interference, proper grounding will reduce susceptibil-
ity. Overhead or outside aerial wiring is not recommended, due to an
increased susceptibility to nearby lightning strikes. Consult with the
Technical Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting
circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, ream-
ing, or punching of the enclosure. When possible, make all cable
entries from the sides or rear. Before making modifications, verify
that they will not interfere with battery, transformer, or printed circuit
board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening
may damage threads, resulting in reduced terminal contact pressure
and difficulty with screw terminal removal.
This system contains static-sensitive components. Always
ground yourself with a proper wrist strap before handling any circuits
so that static charges are removed from the body. Use static sup-
pressive packaging to protect electronic assemblies removed from
the unit.
Units with a touchscreen display should be cleaned with a dry,
clean, lint free/microfiber cloth. If additional cleaning is required,
apply a small amount of Isopropyl alcohol to the cloth and wipe
clean. Do not use detergents, solvents, or water for cleaning. Do not
spray liquid directly onto the display.
Follow the instructions in the installation, operating, and program-
ming manuals.These instructions must be followed to avoid damage
to the control panel and associated equipment. FACP operation and
reliability depend upon proper installation.
Precau-D2-11-2017
FCC Warning
WARNING: This equipment generates, uses, and can radi-
ate radio frequency energy and if not installed and used in
accordance with the instruction manual may cause interfer-
ence to radio communications. It has been tested and found
to comply with the limits for classA computing devices pur-
suant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against such
interference when devices are operated in a commercial
environment. Operation of this equipment in a residential
area is likely to cause interference, in which case the user
will be required to correct the interference at his or her own
expense.
Canadian Requirements
This digital apparatus does not exceed the ClassA limits for
radiation noise emissions from digital apparatus set out in
the Radio Interference Regulations of the Canadian Depart-
ment of Communications.
Le present appareil numerique n'emet pas de bruits radio-
electriques depassant les limites applicables aux appareils
numeriques de la classeAprescrites dans le Reglement sur
le brouillage radioelectrique edicte par le ministere des
Communications du Canada.
Flexput®, Honeywell®, JumpStart®, and SWIFT® are registered trademarks of Honeywell International Inc.Microsoft® and Windows® are registered trademarks of the
Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered trademark of The Mozilla Foundation.
©2022. All rights reserved. Unauthorized use of this document is strictly prohibited.

4FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent
upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly
recommend that you download the most current version of software for each product prior to commissioning any system. Contact
Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online
Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
or call (800)979-3453, x21 in US or (816)229-3405 international
This symbol (shown left) on the product(s) and / or accompanying documents means that used electrical and electronic products
should not be mixed with general household waste. For proper treatment, recovery and recycling, contact your local authorities or
dealer and ask for the correct method of disposal.
Electrical and electronic equipment contains materials, parts and substances, which can be dangerous to the environment and harmful
to human health if the waste of electrical and electronic equipment (WEEE) is not disposed of correctly.

FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022 5
Table of Contents
Section 1: Introduction ..................................................................................................................................................... 9
1.1: Basic System Overview.....................................................................................................................................................................................9
1.1.1: Hardware Features..................................................................................................................................................................................9
1.1.2: Network System Hardware Features ......................................................................................................................................................9
1.1.3: Software Features ...................................................................................................................................................................................9
1.2: About this Manual............................................................................................................................................................................................10
1.2.1: Terms Used in this Manual...................................................................................................................................................................10
1.3: Compatible Products........................................................................................................................................................................................10
1.4: Related Documentation ...................................................................................................................................................................................11
Section 2: Agency Listings, Approvals, and Requirements........................................................................................ 12
2.1: Federal Communications Commission (FCC).................................................................................................................................................12
2.1.1: Electrical Safety Advisory....................................................................................................................................................................12
2.2: Underwriters Laboratories (UL)......................................................................................................................................................................13
2.2.1: Requirements for All Installations........................................................................................................................................................13
2.2.2: UL 864 9th and 10th Edition ................................................................................................................................................................13
2.2.3: Requirements for Central Station Fire Alarm Systems ........................................................................................................................13
2.2.4: Requirements for Local Protected Fire Alarm Systems .......................................................................................................................13
2.2.5: Requirements for Remote Station Protected Fire Alarm Systems........................................................................................................13
2.2.6: Requirements for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, NFPA 720..................................14
2.2.7: NFPA Requirements.............................................................................................................................................................................14
Section 3: Prerequisites for Installation........................................................................................................................ 15
3.1: Inventory..........................................................................................................................................................................................................15
3.2: Environmental Specifications..........................................................................................................................................................................15
3.3: Software Downloads........................................................................................................................................................................................15
3.4: Electrical Specifications ..................................................................................................................................................................................15
3.5: Calculating Current Draw and Standby Battery..............................................................................................................................................16
3.5.1: Worksheet Requirements......................................................................................................................................................................16
3.5.2: Current Draw Worksheet for SLC Devices..........................................................................................................................................16
Section 4: Control Panel Installation............................................................................................................................. 20
4.1: Mounting the Control Panel Cabinet...............................................................................................................................................................20
4.1.1: Preventing Water Damage....................................................................................................................................................................20
4.1.2: Removing the FCP-75 Assembly from the Housing............................................................................................................................20
4.1.3: Dead Front Installation and Removal...................................................................................................................................................20
4.2: Board Assembly Diagram................................................................................................................................................................................22
4.3: Wiring Specifications.......................................................................................................................................................................................22
4.4: AC Power Connection .....................................................................................................................................................................................23
4.5: Battery Power ..................................................................................................................................................................................................24
4.5.1: Battery Accessory Cabinet ...................................................................................................................................................................25
4.6: Wiring Specifications.......................................................................................................................................................................................26
4.6.1: Length Limitations................................................................................................................................................................................26
4.6.2: Calculating Wiring Distance for SBUS Modules.................................................................................................................................27
4.6.3: Wiring Configurations..........................................................................................................................................................................28
4.7: FIK-RA100 Remote Annunciator Installation.................................................................................................................................................28
4.7.1: Mounting the FIK-RA100 ....................................................................................................................................................................29
4.7.2: FIK-RA100 Connection to the Panel....................................................................................................................................................31
4.8: FIK-RA1000R Remote Annunciator Installation............................................................................................................................................31
4.8.1: Mounting the FIK-RA1000R................................................................................................................................................................31
4.9: FIK-RA2000 Remote Annunciator Installation...............................................................................................................................................34
4.9.1: Mounting the FIK-RA2000 ..................................................................................................................................................................34
4.9.2: FIK-RA2000 Connection to the Panel..................................................................................................................................................36
4.10: FIK-5824 Serial/Parallel Printer Interface Module Installation ....................................................................................................................36
4.10.1: Selecting FIK-5824 Options...............................................................................................................................................................36
4.11: FIK-5880 LED Driver Module......................................................................................................................................................................37
4.11.1: FIK-5880 Board Layout .....................................................................................................................................................................37
4.11.2: FACP Connection...............................................................................................................................................................................38
4.11.3: LED Wiring ........................................................................................................................................................................................38
4.11.4: Dry Contact Wiring ............................................................................................................................................................................39
4.12: FIK-5865-3/FIK-5865-4 LED Annunciator Installation ...............................................................................................................................40
4.12.1: FACP Connection...............................................................................................................................................................................40

6FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022
Table of Contents
4.12.2: FIK-5865 Mounting............................................................................................................................................................................41
4.13: Configuring Modules.....................................................................................................................................................................................41
4.13.1: Assigning Module IDs........................................................................................................................................................................41
4.14: Telephone Connection ...................................................................................................................................................................................42
4.15: Notification Appliance/Auxiliary Power Circuits .........................................................................................................................................42
4.15.1: Conventional Notification Appliance.................................................................................................................................................43
4.16: Class A Notification Wiring...........................................................................................................................................................................43
4.16.1: Auxiliary Power Installation...............................................................................................................................................................44
4.17: Onboard Relays (Conventional) ....................................................................................................................................................................44
4.17.1: Common Trouble Relay .....................................................................................................................................................................45
4.17.2: Programmable Relays.........................................................................................................................................................................45
4.18: Remote Station Applications .........................................................................................................................................................................45
4.18.1: Keltron Model 3158 Installation.........................................................................................................................................................45
4.18.2: City Box Connection Using the 5220 Module ...................................................................................................................................45
4.18.3: NFPA 72 Polarity Reversal ................................................................................................................................................................46
4.18.4: Using a MR-201/T Control Relay From Air Products .......................................................................................................................47
4.18.5: Transmitter Activated by Dry Contacts..............................................................................................................................................48
Section 5: Networking..................................................................................................................................................... 49
5.1: Network System Hardware Features ...............................................................................................................................................................49
5.1.1: Networked Panels.................................................................................................................................................................................49
5.2: Direct Connect Wiring Option.........................................................................................................................................................................49
5.3: SK-NIC Wiring Options ..................................................................................................................................................................................49
5.3.1: Fiber Loop Modules .............................................................................................................................................................................50
5.3.2: FIK-NIC Mounting Kits .......................................................................................................................................................................50
5.4: SK-NIC Installation.........................................................................................................................................................................................50
5.4.1: Wiring...................................................................................................................................................................................................51
5.5: Setting the Network ID for Each Panel ...........................................................................................................................................................53
Section 6: Network Management................................................................................................................................... 54
6.1: Network Diagnostics .......................................................................................................................................................................................54
6.1.1: Ping Panel.............................................................................................................................................................................................54
6.1.2: Data Network Status.............................................................................................................................................................................54
6.2: Network Programming ....................................................................................................................................................................................54
6.2.1: Learn Network......................................................................................................................................................................................54
6.2.2: Edit Network Names.............................................................................................................................................................................54
6.2.3: Edit Panel ID.........................................................................................................................................................................................54
6.2.4: Computer Access..................................................................................................................................................................................55
6.2.5: Access Codes........................................................................................................................................................................................55
6.2.6: Communicator Options.........................................................................................................................................................................55
6.3: Sync Network Options.....................................................................................................................................................................................56
6.4: Network Management Quick Reference .........................................................................................................................................................57
Section 7: Programming Overview................................................................................................................................ 58
7.1: JumpStart Auto-Programming.........................................................................................................................................................................58
7.1.1: Input Points...........................................................................................................................................................................................58
7.1.2: Output Points ........................................................................................................................................................................................58
7.1.3: Running JumpStart Auto-Programming...............................................................................................................................................58
7.2: Mapping Overview ..........................................................................................................................................................................................59
7.2.1: Input Point Mapping.............................................................................................................................................................................60
7.2.2: Output Circuit Mapping........................................................................................................................................................................60
7.2.3: Event Mapping.....................................................................................................................................................................................60
7.2.4: Mapping LED Points............................................................................................................................................................................62
7.3: Programming Using the HFSS Software Suite................................................................................................................................................62
7.4: Programming Using an Annunciator ...............................................................................................................................................................62
7.4.1: Entering / Exiting the Program Menu..................................................................................................................................................62
7.4.2: Moving through the Menus ..................................................................................................................................................................63
7.4.3: Selecting Options and Entering Data....................................................................................................................................................63
7.5: Programming Menu Quick Reference.............................................................................................................................................................63
Section 8: Programming................................................................................................................................................. 70
8.1: UL 864 Programming Requirements...............................................................................................................................................................70
8.2: Modules ...........................................................................................................................................................................................................70
8.2.1: Edit Modules.........................................................................................................................................................................................70

FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022 7
Table of Contents
8.2.2: Adding Modules ...................................................................................................................................................................................71
8.2.3: Deleting Modules..................................................................................................................................................................................71
8.2.4: View Module List.................................................................................................................................................................................71
8.3: Zone.................................................................................................................................................................................................................71
8.3.1: Edit Zone ..............................................................................................................................................................................................71
8.3.2: View Zone Points .................................................................................................................................................................................74
8.4: Group...............................................................................................................................................................................................................74
8.4.1: Edit Group ............................................................................................................................................................................................74
8.4.2: View Group Points ...............................................................................................................................................................................75
8.4.3: Edit Output Group Template................................................................................................................................................................75
8.5: Point.................................................................................................................................................................................................................75
8.5.1: Point Programming for SLC.................................................................................................................................................................75
8.5.2: Point Programming for the Internal or External Power Module ..........................................................................................................78
8.5.3: Point Programming for FIK-5880 and FIK-5865 Modules..................................................................................................................79
8.5.4: Point Programming for the FIK-5496...................................................................................................................................................80
8.6: System Options................................................................................................................................................................................................80
8.6.1: Communication Options.......................................................................................................................................................................80
8.6.2: Daytime/Nighttime Sensitivity.............................................................................................................................................................83
8.6.3: Holiday Days ........................................................................................................................................................................................83
8.6.4: Time Options ........................................................................................................................................................................................83
8.6.5: Miscellaneous Options..........................................................................................................................................................................85
8.6.6: Daylight Saving Options.......................................................................................................................................................................85
8.6.7: Edit Banner...........................................................................................................................................................................................85
8.6.8: SLC Family...........................................................................................................................................................................................86
8.7: JumpStart Auto-Programming.........................................................................................................................................................................86
8.8: Restore Defaults...............................................................................................................................................................................................86
Section 9: System Operation.......................................................................................................................................... 87
9.1: Annunciator Description..................................................................................................................................................................................87
9.1.1: LCD Display.........................................................................................................................................................................................87
9.1.2: Banner...................................................................................................................................................................................................87
9.2: Menu System ...................................................................................................................................................................................................87
9.2.1: Panel Login Menu.................................................................................................................................................................................87
9.2.2: Main Menu Overview...........................................................................................................................................................................89
9.2.3: Using the Menus...................................................................................................................................................................................89
9.3: Basic Operation ...............................................................................................................................................................................................89
9.3.1: Setting Time and Date ..........................................................................................................................................................................89
9.3.2: Disable / Enable a Point........................................................................................................................................................................89
9.3.3: View Event History ..............................................................................................................................................................................90
9.3.4: Conduct a Fire Drill..............................................................................................................................................................................90
9.3.5: Conduct an Indicator Test.....................................................................................................................................................................90
9.3.6: Conduct a Walk Test ............................................................................................................................................................................90
9.3.7: Conduct a Communicator Test.............................................................................................................................................................91
9.3.8: Manual AlarmNet Registration.............................................................................................................................................................91
9.3.9: Silence Alarms or Troubles..................................................................................................................................................................91
9.3.10: Reset Alarms.......................................................................................................................................................................................91
9.3.11: Check Detector Sensitivity Through Point Status ..............................................................................................................................91
9.3.12: View Status of a Point ........................................................................................................................................................................92
9.3.13: View Alarms, Supervisories, or Troubles...........................................................................................................................................92
9.3.14: View System Information...................................................................................................................................................................92
9.4: Operation Mode Behavior ...............................................................................................................................................................................93
9.5: Panel Operating Modes....................................................................................................................................................................................94
9.5.1: Multi-Site Annunciator and Multi-Site User Access............................................................................................................................96
9.6: Releasing Operations.......................................................................................................................................................................................96
9.6.1: Single Interlock Zone Releasing...........................................................................................................................................................97
9.6.2: Double Interlock Zone Releasing.........................................................................................................................................................97
9.7: Smoke Alarm Verification ...............................................................................................................................................................................98
9.8: Function Keys.................................................................................................................................................................................................98
9.8.1: Recording an F-Key Macro ..................................................................................................................................................................98
9.8.2: Aborting an F-Key Macro Recording Session......................................................................................................................................98
9.8.3: Erasing an F-Key Macro.......................................................................................................................................................................98
9.8.4: Using a Recorded F-Key Macro...........................................................................................................................................................99

8FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022
Table of Contents
9.8.5: F-Key Status Event...............................................................................................................................................................................99
9.8.6: F-Key Map Inhibit................................................................................................................................................................................99
Section 10: Reporting ................................................................................................................................................... 100
10.1: Receivers Compatible with the Control Panel.............................................................................................................................................100
10.2: SIA / FCP-75 Panels PI Modifier Reporting ...............................................................................................................................................109
10.3: SIA– FCP-75 Panel Communicator.............................................................................................................................................................110
Section 11: Testing and Troubleshooting................................................................................................................... 111
11.1: Troubleshooting ...........................................................................................................................................................................................111
11.2: Troubleshooting Common Problems ...........................................................................................................................................................111
11.2.1: Periodic Testing And Maintenance ..................................................................................................................................................111
11.2.2: Event History....................................................................................................................................................................................112
11.3: Built-in Troubleshooting and Testing Tools.................................................................................................................................................112
11.3.1: SLC Device Locater .........................................................................................................................................................................112
11.3.2: SLC Multi Locater............................................................................................................................................................................112
11.3.3: I/O Point Control ..............................................................................................................................................................................113
11.4: Earth Fault Resistance..................................................................................................................................................................................113
Section 12: Installation Records.................................................................................................................................. 114
12.1: SLC Device Point Record............................................................................................................................................................................114
Appendix A: Editing Text Using the Built-In Programmer......................................................................................... 115
A.1: Characters Used for Editing Text..................................................................................................................................................................115
A.2: Edit Name Example......................................................................................................................................................................................115
Appendix B: Expanded Receiver/Panel Relationship................................................................................................ 116
Appendix C: Cadence Patterns....................................................................................................................................117
Appendix D: Panel Security.......................................................................................................................................... 118
Model FCP-75 Basic Operating Instructions............................................................................................................... 119

FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022 9
Section 1: Introduction
The FCP-75 Fire Alarm Control / Communicator is an Addressable Fire Alarm Control System that meets the requirements of UL 864
10th Edition Standard.
1.1 Basic System Overview
1.1.1 Hardware Features
• The FCP-75 has one built in signaling line circuit (SLC) that supports 75 detectors and 75 modules.
• The FCP-75 is capable of outputting 2.5A of output power during an alarm activation through 2 sets of terminals for the notification
appliance circuits or an auxiliary application. Each circuit is power-limited and can source up to 2.5A during an alarm activation. The
constant auxiliary power load must not exceed 1A for normal standby.
• Built-in dual phone line, digital alarm communicator/transmitter (DACT), or IP technologies.
•Reports events to central station by point or by zone.
•UL Listed for pre-action and deluge releasing systems.
•Two general purpose Form C programmable relays.
•One FormC Trouble Relay.
•Basic system operation can be performed from the onboard, or any remote annunciator.
• Up to 20 user profiles can be programmed, each having custom Access Code, and Main Menu items.
•Can be used with any combination of up to 8 Model FIK-RA100, FIK-RA1000R, or FIK-RA2000 Remote LCD Annunciators (sold
separately).
•Can be used with Model FIK-5865-3, FIK-5865-4, and FIK-5880 in any combination for a total of eight devices on one control panel.
See Figure 4.34 and Figure 4.30 for additional information on these models.
•Printing of event log available through the Model FIK-5824 serial/parallel printer interface module.
•125 software zones, 125 Output Groups.
•Add four Notification/Auxiliary power circuits with each FIK-5496 NAC Expander. See note below.
1.1.2 Network System Hardware Features
• The default network setup can contain up to 32- FCP-75 panels connected.
• Network support for up to 32 Sites.
• Each building is referred to as a “site”.
• Panels can be interconnected using CLASS B or CLASS A topology.
• Use the FIK-NIC Network Interface Card to create a network. Copper wire or fiber-optic cable panel connectivity can be used within
the same networked System.
• The network architecture provides true peer-to-peer capability allowing network survivability for all hardware that remains operational
in the event of partial system failure.
1.1.3 Software Features
• Advanced smoke detector features:
– Automatic drift compensation
– Maintenance alert region
– Point status meets calibrated smoke test requirements for NFPA 72
• “JumpStart” feature for easy programming
• Non-volatile event history stores 1000 events
• A choice of output patterns available for notification outputs, including Temp 4 along with ANSI 3.41 temporal signal
• Built-in synchronization appliance support forAMSECO, Gentex, Wheelock, or System Sensor
NOTE: Total output power for both circuits must not exceed 2.5A in alarm condition, and total output power for both circuits must not exceed
1.0A for all other activation conditions (i.e. Supervisory, Trouble, etc.).
NOTE: The system can support a maximum of eight intelligent power modules, either the FIK-RPS1000 or FIK-5496, in any combination.

10 FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022
Introduction About this Manual
1.2 About this Manual
This manual is intended to be a complete reference for all installation and operation tasks for the FCP-75.
1.2.1 Terms Used in this Manual
The following terminology is used with the FCP-75 system:
1.3 Compatible Products
The chart below lists the products available for use with the FCP-75.
Term Description
SLC Signaling Line Circuit
Module The term module is used for all hardware devices except for SLC addressable devices and notification
appliances. This includes the FCP-75 panel itself.
Input Point An addressable sensing device, such as a smoke or heat detector or a contact monitor device.
Input Zone A protected area made up of input points.
Output Point (or Output Circuit) Anotification point or circuit for notification appliances. Relay circuits and auxiliary power circuits are also
considered output points.
Group (or “Output Group”) A group of output points. Operating characteristics are common to all output points in the group.
Output (or “Cadence”) Pattern The pattern that the output will use, for example, Constant, March Code, ANSI 3.41. Applies to zones
and special system events. See Appendix D for additional information.
Mapping Mapping is the process of specifying which outputs are activated when certain events occur in the
system. Figure 7.2 describes mapping in detail.
Network System Consists of any combination of 32 panels of these model numbers: FCP-75, FCP-300, FCP-300ECS,
FCP-2100, or FCP-2100ECS.
SWIFT Smart Wireless Integrated Fire Technology
Table 1.1 Manual Terminology
Type of Device Model Description
Fike Addressable SLC
Devices For a list of compatible devices, refer to the SLC Wiring Manual, P/N: LS10179-000FK-E.
SWIFT Wireless SLC Devices For a list of compatible devices, refer to the SWIFT Manual, P/N: LS10036-000FK-E.
Other Modules FIK-5824Serial/Parallel
Printer Interface Module Allows a printer to be attached for the on-site event logging. Maximum of four FIK-5824s per
control panel.
FIK-RPS1000 Power
Supply Provides additional power, six Flexput circuits, and two Form C relays. Max 8 per system. See
FIK-RPS1000 Installation Manual (PN LS10259-001FK-E) for more information.
FIK-5496 NAC
Expander Provides 4 additional Notification Appliance Circuits/Auxiliary power. (Up to 8 per FCP-75
System).
FIK-RA100 and FIK-
RA1000R LCD
Annunciator
4 x20 Remote LCD annunciator. Can be used in any combination, up to a total of 8 devices on
one panel.
FIK-RA2000LCD
Annunciator 4 x 40 Remote LCD annunciator can be used in any combination, up to a total of 8 devices on
one panel.
FIK-5865-3 and
FIK-5865-4 LED
Annunciator
LED annunciator can display up to 30 LEDs (15 red and 15 yellow). FIK-5865-4 has key
switches for silence and reset, and a system trouble LED. FIK-5865-3, FIK-5865-4, and FIK-
5880 can be used in any combination, up to a total of eight devices on one panel.
RA-100TR Trim Ring Trim ring kit for surface mounting the FIK-RA2000/FIK-RA100 annunciators.
5860TR Trim Ring Trim ring kits for surface mounting the FIK-RA1000R annunciator.
FIK-5880 LED Driver
Module Driver for up to 40 LEDs. Interfaces with customized annunciator boards. In addition the FIK-
5880 has eight generic switch input points.
FIK-5883 General
Purpose Relay Module Provides 10 Form C relays. Designed to be driven by the FIK-5880. Up to four, FIK-5883s can
be used with each FIK-5880 module.
FIK-NIC Network Interface Card
FIK-FML Fiber-Optic Multi Mode
FIK-FSL Fiber-Optic Single Mode
Table 1.2 FCP-75 Compatible Products

FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022 11
Related Documentation Introduction
1.4 Related Documentation
Refer to the following documents for more information.
Wireless FIK-W-WGI Wireless Gateway
FIK-W-PHOTO Wireless Photoelectric Smoke Detector
FIK-W-ACCLIMATE Wireless Multi-criteria Smoke Detector
FIK-W-HEAT-ROR Wireless ROR Heat Detector
FIK-W-HEAT Wireless Fixed Heat (135°F) Detector
FIK-W-MONITOR Wireless Addressable Monitor Module
FIK-W-RELAY Wireless Addressable Relay Module
B210W 6" wireless base
Miscellaneous HFSS Programming
Tool For communication and panel programming with a Windows-based computer. Enables
remote viewing of detector status and event history.
7860 Telephone Cord RJ31X cord for connecting phone line to the FCP-75.
7628 UL Listed End-of-line resistor
Type of Device Model Description
Table 1.2 FCP-75 Compatible Products (Continued)
Title Document Number
SLC Wiring Manual LS10179-000FK-E
Device Compatibility Document LS10167-005FK-E
FIK-5824 Printer Interface Module Install Sheet LS10254-002FK-E
FIK-RPS1000 Power Supply Manual LS10259-001FK-E
FIK-5496 NAC Expander Manual LS10253-001FK-E
FIK-RA100 Annunciator Install Sheet LS10260-001FK-E
FIK-RA1000R LCD Annunciator Install Sheet LS10258-001FK-E
FIK-RA2000 LCD Annunciator LS10261-001FK-E
FIK-5865-3 and FIK-5865-4 LED Annunciator LS10255-001FK-E
FIK-5880 LED Driver Module LS10256-001FK-E
FIK-5883 General Purpose Relay Module LS10257-001FK-E
FIK-NIC LS10172-002FK-E
FIK-FML/FSL LS10178-002FK-E
MRD-1 Releasing Disconnect LS10231-000GE-E
Table 1.3 Related Documentation

12 FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022
Section 2: Agency Listings, Approvals, and Requirements
Install and maintain this panel in accordance with NFPA72. Detector spacing shall be done in accordance to NFPA 72. End-of -line relays
and resistors shall be placed within the electrical box located at the end of the initiating circuit. Testing and maintenance should be performed
in compliance with NFPA72.
2.1 Federal Communications Commission (FCC)
The following information must be provided to the Telephone Company before the FCP-75can be connected to the phone lines:
1. This device may not be directly connected to the coin telephone or party line services.
2. This device cannot be adjusted or repaired in the field. In case of trouble with the device, notify the installing company or return to:
Fike Corporation
704 SW 10th Street
Blue Springs, MO 61015
1+816-229-3405
3. If the FCP-75 causes harm to the telephone network, the Telephone Company will notify the user in advance that temporary
discontinuance of service may be required. If advance notice is not practical, the Telephone Company will notify the user as soon as
possible. Users have the right to file complaints, if necessary, with the Federal Communications Commission.
4. The Telephone Company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the
equipment. If this happens, the Telephone Company will provide advance notice to allow you to make the necessary modifications to
maintain uninterrupted service.
5. This equipment complies with Part 68 of the FCC rules and the requirements adopted by theACTA. On the wiring diagram of this
equipment is a label that contains, among other information, a product identifier in the format US: HS9AL10A2100. If requested, this
number must be provided to the Telephone Company.
6. See the manual for phone jack information.
7. A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC
Part 68 rules and requirements adopted by the ACTA. A compliant telephone cord and modular plug is provided with this product. It is
designed to be connected to a compatible modular jack that is also compliant. See installation instructions for details.
8. The REN (Ringer Equivalence Number) provided on this installation sheet is used to determine the number of devices that may be
connected to the public switched telephone network. This number must not exceed 5.0. Since this product has an REN of 1.0A, the
number of devices is limited. The REN number is embedded in the FCC registration number as 10A.
9. If this equipment FCP-75 causes harm to the telephone network, the Telephone Company will notify you in advance that temporary
discontinuance of service may be required. But if advance notice isn't practical, the Telephone Company will notify the customer as
soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
10. The Telephone Company may make changes in its facilities, equipment, operations or procedures that could affect the operation of the
equipment. If this happens the Telephone Company will provide advance notice in order for you to make necessary modifications to
maintain uninterrupted service.
11. If trouble is experienced with the FCP-75, for repair or warranty information, please contact Technical Support at (800)979-3453 or
www.fike.com. If the equipment is causing harm to the telephone network, the Telephone Company may request that you disconnect the
FCP-75 until the problem has been resolved.
12. See the Manufacturer’s Warranty for repair and replacement information.
13. Connection to party line service is subject to state tariffs. Contact the state public utility commission, public service commission or
corporation commission for information.
14. If your facility has specially wired alarm equipment connected to the telephone line, ensure the installation of this FCP-75 does not
disable your alarm equipment. If you have questions about what will disable alarm equipment, consult your Telephone Company or
qualified installer.
2.1.1 Electrical Safety Advisory
Parties responsible for equipment requiring AC power should consider including an advisory notice in their customer information, suggest-
ing the customer use a surge arrestor. Telephone Companies report that electrical surges, typically lightning transients, are very destructive to
customer terminal equipment connected to AC power sources. This has been identified as a major nationwide problem.
Manufacturer: Fike
Model Number: -75FCP-75
FCC registration number: US: HS9AL10A2100
Ringer equivalence: 1.0A
Type of jack: RJ31X
Facility Interface Codes: Loop Start: 02LS2
Service Order Code: 9.0F
!
WARNING: FCC RULES PART 15
THIS DEVICE HAS BEEN VERIFIED TO COMPLY WITH FCC RULES PART 15. OPERATION IS SUBJECT TO THE
FOLLOWING CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE RADIO INTERFERENCE,AND (2) THIS DEVICE MUST
ACCEPTANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.

FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022 13
Underwriters Laboratories (UL) Agency Listings, Approvals, and Requirements
2.2 Underwriters Laboratories (UL)
2.2.1 Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for addi-
tional requirements. The following subsections list specific requirements for each type of installation (for example, Central Station Fire
Alarm Systems, Local Protected Fire Alarm Systems, and so on). See Section 9.6 for information on releasing operation.
1. All field wiring must be installed in accordance with the NFPA 70 National Electric Code.
2. Use addressable smoke detectors specified in the SLC Wiring Manual, P/N: LS10179-000FK-E.
3. Use UL listed notification appliances compatible with the FCP-75 from those specified in the Device Compatibility Document, P/N:
LS10167-005FK-E.
4. A full System checkout must be performed any time the panel is programmed.
Restricted Options
• The loss ofAC signal is defaulted to 3 hours. However, the System allows settings from 0 - 30 hours. For UL-certified installations, this
number must be set from 1 to 3 hours.
• The system allows the use of non-latching spot type smoke detectors.This feature may not be used in commercial applications whereby
a general alarm is sounded. It is intended for elevator recall, door holding applications, and hotel/motel room applications.
• The system allows the Alarm Verification time to be set from 60 to 250 seconds. For UL-certified installations, the setting must be a
maximum of 60 seconds.
• The system allows the Auto-resound time to be set to 4 or 24 hours. For UL certified installations that are using SWIFT devices, the
value must be set to 4 hours.
• Call forwarding shall not be used.
• When two-count is used, detector spacing shall be cut in half, you shall not use the alarm verification feature, and no delay shall be
used.
• P.A.S (Positive Alarm Sequence) feature shall be used only with automatic detectors.
2.2.2 UL 864 9th and 10th Edition
• Per the UL Continuing Certification Program, UL 864 9th edition fire alarm control equipment will retain certification after the rollout
of UL 10th edition (12/2/2018).
• Installations of UL 864 10th Edition certified equipment are permitted to use UL864 9th Edition certified equipment when approved by
the local Authority Having Jurisdiction (AHJ).
For product compliance, refer to the UL/ULC listing cards located on the UL online certification directory. https://iq.ulprospector.com
2.2.3 Requirements for Central Station Fire Alarm Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the FCP-75 shall automatically initiate and complete a test signal
transmission sequence to its associated receiver at least once every 6-hours, using two phones or one phone line with Ethernet backup.
The AC Loss Hours option must be set from 1-3 hours.
3. If you use wired Ethernet or cellular, you must program the correspondingAccount/Subscriber ID and a test time so that the FACP shall
automatically initiate a test signal transmission sequence to its associated receiver at least once every 6-hours.
The automatic 6-hour test signal transmission only applies if secondary communication paths are used. If no secondary communication
paths are used, the FACP shall automatically initiate a test signal transmission sequence to its associated receiver at least once every 60
minutes.
2.2.4 Requirements for Local Protected Fire Alarm Systems
At least one UL listed supervised notification appliance must be used.
2.2.5 Requirements for Remote Station Protected Fire Alarm Systems
1. Do not exceed the current load restrictions shown in Section 3.5.
2. The AC Loss Hours option must be set from 1-3 hours.
!
CAUTION: INSTALLATION AND TEST
TO ENSURE PROPER OPERATION, THIS EQUIPMENT MUST BE INSTALLED ACCORDING TO THE ENCLOSED
INSTALLATION INSTRUCTIONS. TO VERIFY THAT THE EQUIPMENT IS OPERATING PROPERLYAND CAN
SUCCESSFULLY REPORTAN ALARM, THIS EQUIPMENT MUST BE TESTED IMMEDIATELY AFTER INSTALLATION,
AND PERIODICALLY THEREAFTER, ACCORDING TO THE ENCLOSED TEST INSTRUCTIONS.
!
CAUTION: LINE IN USE
IN ORDER FOR “ALARM DIALING EQUIPMENT” TO BE ABLE TO SEIZE THE PHONE LINE TO REPORTAN ALARM OR
OTHER EVENT WHEN OTHER CUSTOMER EQUIPMENT (TELEPHONE,ANSWERING SYSTEM, COMPUTER MODEM,
ETC.) CONNECTED TO THE SAME LINE IS IN USE, “ALARM DIALING EQUIPMENT” MUST BE CONNECTED TO A
PROPERLY INSTALLED RJ31X JACK. THE RJ31X JACK MUST BE CONNECTED IN SERIES WITH, AND AHEAD OF,ALL
OTHER EQUIPMENTATTACHED TO THE SAME PHONE LINE. SERIES INSTALLATION OF AN RJ31X JACK IS DEPICTED
IN THE FIGURE BELOW. IF YOU HAVE ANY QUESTIONS CONCERNING THESE INSTRUCTIONS, CONSULT YOUR
TELEPHONE COMPANY OR A QUALIFIED INSTALLER ABOUT INSTALLING THE NECESSARY JACK AND ALARM
DIALING EQUIPMENT.

14 FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022
Agency Listings, Approvals, and Requirements Underwriters Laboratories (UL)
2.2.6 Requirements for the Installation of Carbon Monoxide (CO) Detection and Warning
Equipment, NFPA 720
When using carbon monoxide detection the system must be monitored by a Supervising Station with emergency response, both aspects meet-
ing the Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, NFPA 720.
2.2.7 NFPA Requirements
The following is the minimum configuration necessary to comply with the NFPA requirements.
Model/Module Description Local Releasing Remote
Station Auxiliary Central
Station Emergency
Signaling
FCP-75 Control Unit Y Y Y Y Y Y
5220 Direct Connect Module N N N Y N O
FIK-5496 NAC Expander O Y* O O O O
FIK-5865-3/-4 LED Annunciator O O O O O O
FIK-5880 LED I/O Module O O O O O O
FIK-RPS1000 IntelligentPowerModule O Y* O O O O
FIK-RA100 LCD Annunciator O O O O O O
FIK-RA1000R LCD Annunciator O O O O O O
FIK-RA2000R LCD Annunciator O O O O O O
FIKNIC Network card O O O O O O
FIK-FML/ -FSL Fiber modules O O O O O O
Y = YES, N = NO, O = OPTIONAL
Note: Y * = You must include the FIK-RPS1000 or FIK-5496 for releasing purposes.
Table 2.1 NFPA Requirement for Minimum System Configuration for FCP-75-75

FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022 15
Section 3: Prerequisites for Installation
This section of the Manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly,
especially if you are installing an FCP-75 panel for the first time.
3.1 Inventory
When the FCP-75 shipment is received, check that all the parts have been included in the shipment. The shipment consists of one of each of
the following:
• main circuit board with the display
• backbox with door
• plastic bag containing two keys, screws, cables, and ten 4.7K ohm end-of-line resistors
• manual
3.2 Environmental Specifications
It is important to protect the FCP-75 control panel from water. To prevent water damage, the following precautions should be FOLLOWED
when you install the units:
• Intended for indoor use in dry locations only.
• Do not mount the panel directly on exterior walls, especially masonry walls (condensation).
• Do not mount the panel directly on exterior walls below grade (condensation).
• Protect the panel from plumbing leaks.
• Protect the panel from splash caused by Sprinkler System inspection ports.
• Do not mount the panel in areas with humidity-generating equipment (such as dryers, production machinery).
When you select a location to mount the FCP-75 control panel, the unit should be mounted where it will NOT be exposed to temperatures
outside the range of 32°F-120°F (0°C-49°C) or humidity outside the range of 10%-93% at 86°F (30°C) non-condensing.
3.3 Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades
to the embedded software in our products. To ensure that you install and program the latest features, we strongly recommend that you down-
load the most current version of software for each product prior to commissioning any System. Contact Technical Support with any ques-
tions about software and the appropriate version for a specific application. The HFSS Software Suite is available at www.fike.com.
3.4 Electrical Specifications
Table 3.1 lists the terminal block on the FCP-75 as well as a description of each individual terminal and their respective electrical rating. For
the location of the terminals, refer to Figure 4.3. See also Section 4 for installation information.
Terminal No. Label Description Rating
Group Individual Voltage Current
Terminal Block 3 TELCO 1 RING Phone Line 1 Telco Ring
TIP Phone Line 1 Telco Tip
PHONE 1 RING Phone Line 1 Phone Ring
TIP Phone Line 1 Phone Tip
TELCO 2 RING Phone Line 2 Telco Ring
TIP Phone Line 2 Telco Tip
PHONE 2 RING Phone Line 2 Phone Ring
TIP Phone Line 2 Phone Tip
Terminal Block 2 RELAY 1 NO Normally open relay contact 27.4 VDC 2.5 A, resistive
COM Common terminal
NC Normally closed relay contact
RELAY 2 NO Normally open relay contact 27.4 VDC 2.5 A, resistive
COM Common terminal
NC Normally closed relay contact
TROUBLE NO Normally open relay contact 27.4 VDC 2.5 A, resistive
COM Common terminal
NC Normally closed relay contact
SLC IN – Used for Class A installations 32 VDC 100 mA
+
SLC OUT –SLC terminals 32 VDC 100 mA
+
SLC PROG – Used for programming SLC Detectors 32 VDC 100 mA
+Table 3.1 Terminal Descriptions and Electrical Specifications

16 FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022
Prerequisites for Installation Calculating Current Draw and Standby Battery
3.5 Calculating Current Draw and Standby Battery
This section contains instructions and tables for calculating current draws and standby battery needs.
3.5.1 Worksheet Requirements
The following steps must be taken when determining FCP-75 current draw and standby battery requirements.
Filling in the Current Draw Worksheet, Table 3.2
1. For the FCP-75, the worst case current draw is listed for the panel, addressable devices, and SLC expanders. Fill in the number of
addressable devices and expanders that will be used in the system and compute the current draw requirements for alarm and standby.
2. Add up the current draw for all auxiliary devices and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. For notification appliances and auxiliary devices not mentioned in the manual, refer to the device manual for the current ratings.
5. Make sure that the total alarm current calculated, including current for the panel itself, does not exceed 2.5 A. This is the maximum
alarm current allowable.
If the current is above 2.5A, you will need to use a notification power expander(s) such as, the FIK-5496 NAC Expander. Use the
expander(s) to distribute the power loads, so that the FCP-75 or the power expanders do not exceed their power rating.
Refer to the Current Draw Worksheets provided with the FIK-5496 Manual to identify the ratings that do not exceed their power
requirements.
6. Complete the remaining instructions in the table for determining battery size requirements.
3.5.2 Current Draw Worksheet for SLC Devices
Use Table 3.2 to determine the current requirements during the alarm/battery standby operation when Fike SLC devices are installed. You
can install up to 75 detectors and 75 modules.
Terminal Block 2 SBUS – SBUS Power 27.4 VDC 0.5 A
+
A SBUS Communication 5 VDC 100 mA
B
NAC11– Notification Appliance Circuit/Auxiliary power 27.4 VDC 1 Amp NAC or Aux power
+
NAC21– Notification Appliance Circuit/Auxiliary power 27.4 VDC 1 Amp NAC or Aux power
+
P7 Data Network Used for FIK-NIC 24 VDC 21 mA
1 Regulated NAC application. When programmed for Releasing, the NACs are Special Application.
Terminal No. Label Description Rating
Group Individual Voltage Current
Table 3.1 Terminal Descriptions and Electrical Specifications (Continued)
Device # of Devices Current per Device Standby
Current Alarm Current
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel
(Current draw from battery) 1 Standby 165 mA 165 mA
Alarm: 310 mA 310 mA1
Addressable SLC Detectors
FIK-2351
Standby: 0.2 mA
Alarm: 4.5 mA2
mA mA
FIK-2351T mA mA
FIK-2351R mA mA
FIK-5351 mA mA
FIK-5351H mA mA
FIK-5351R mA mA
OSI-RI-FIK SLC Standby/Alarm: 20 mA mA mA
Aux. Pwr Standby: 22 mA mA
Alarm: 20 mA mA
DNR/DNRW3(non-relay) None, included with FIK-2351R
DNR3(with relay) None, included with FIK-2351R & FIK-M500R
FIK-FC351 SLC Standby: 0.20 mA mA
Alarm: 4.5 mA mA
Table 3.2 Current Draw Worksheet for IDP SLC Devices

FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022 17
Calculating Current Draw and Standby Battery Prerequisites for Installation
FIK-2351TIR SLC Standby: 0.20 mA mA
Alarm: 4.5 mA mA
Addressable SLC Modules
FIK-M500M Standby/Alarm 0.375 mA mA mA
FIK-M501M Standby/Alarm 0.375 mA mA mA
FIK-PULL-SA/FIK-PULL-DA Standby/Alarm 0.3 mA mA mA
FIK-M500DM Standby/Alarm: 0.75 mA mA mA
FIK-IM-10 Standby/Alarm: 3.5 mA mA mA
FIK-M500S SLC Standby 0.375 mA mA
Alarm: 0.375 mA mA
Aux Pwr Standby 1.7 mA mA
Alarm: 6.5mA mA
FIK-SC-6 SLC Standby 2.65 mA mA
Alarm: 35 mA mA
Aux Pwr Standby 8 mA mA
Alarm: 20 mA mA
FIK-M500R Standby/Alarm: 0.255 mA mA mA
FIK-CR-6 Standby: 1.9 mA mA
Alarm: 32 mA mA
FIK-M500MR-2 Standby: 1.3 mA mA
Alarm: 24 mA mA
FIK-M502M Aux Pwr Standby 12 mA mA
Alarm: 90 mA mA
SLC Standby: 0.27 mA mA
Alarm: 5.1 mA
FIK-CZ-6 Aux Pwr Standby 50 mA mA
Alarm: 70 mA mA
SLC Standby 2.3 mA mA
Alarm: 40 mA mA
SLC Accessories
B200S-W/-IV Intelligent Sounder
Base Aux Pwr Standby: 0.5 mA mA
Alarm: (high vol) 35 mA mA
SLC Standby 0.3 mA mA
B200S-LF-W/-IV Intelligent Low
Frequency Sounder Base Aux Pwr Standby 0.55 mA mA
Alarm (high vol) 140 mA mA
SLC Standby 0.30 mA mA
B224RB-W/-IV Relay Base Standby/Alarm: 0.17 mA mA mA
RTS151 Alarm: 10 mA mA
RTS151KEY Alarm: 12 mA mA
RA100Z Alarm: 10 mA mA
SLC Isolator Devices
FIK-M500X (Isolator Module) Standby: 0.45 mA mA mA
Isolation: 17 mA
ISO-6 (6 Fault Isolator Module) Standby: (per circuit) 0.45 mA mA
Isolation: (per circuit) 17 mA mA
Accessories Modules4
FIK-RA2000 Remote LCD
Annunciator Standby: 27 mA mA
Alarm: 53 mA mA
Device # of Devices Current per Device Standby
Current Alarm Current
Table 3.2 Current Draw Worksheet for IDP SLC Devices (Continued)

18 FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022
Prerequisites for Installation Calculating Current Draw and Standby Battery
FIK-RA1000R Remote LCD
Annunciator Standby: 58 mA mA
Alarm: 68 mA mA
FIK-RA100 Remote LCD Annunciator Standby: 59 mA mA
Alarm: 92 mA mA
FIK-5824 Serial/Parallel Module Standby/Alarm: 45 mA mA mA
FIK-5496 NAC Expander Standby/Alarm (SBUS): 10 mA mA mA
FIK-RPS1000 Power Supply Standby/Alarm (SBUS): 10 mA mA mA
FIK-5865-4 LED Annunciator
(with reset and silence switches) Standby: 35 mA mA
Alarm: 145 mA mA
FIK-5865-3 LED Annunciator Module Standby: 35 mA mA
Alarm: 145 mA mA
FIK-5880 LED I/O Module Standby: 35 mA mA
Alarm: 200 mA mA
FIK-5883 Relay Interface Standby: 0 mA mA
Alarm: (22 mA/relay) 220 mA mA
Network Cards
FIK-NIC Network Interface Card Standby/Alarm: 21 mA mA mA
FIK-FML Fiber Optic Multi Mode Standby/Alarm: 53 mA mA mA
FIK-FSL Fiber Optic Single Mode Standby/Alarm: 79 mA mA mA
Wireless Modules
FIK-W-WGI Wireless Gateway Max current using ext supply 40 mA mA mA
Max current SLC Power 24 mA mA mA
A Total System Current
Auxiliary Devices Refer to devices manual for current rating
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
B Auxiliary Devices Current5
Notification Devices Refer to device manual for current rating
Alarm: mA mA
Alarm: mA mA
Alarm: mA mA
C Notification Appliances Current mA
D Total current ratings of all devices in system (line A + line B + C) mA mA
E Total current ratings converted to amperes (line D x 0.001): A A
F Number of standby hours H
G Multiply lines E and F. Total standby AH AH
H Alarm sounding period in hours. (For example, 5 minutes = 0.0833 hours) H
I Multiply lines E and H. Total alarm AH AH
J Add lines G and I. AH
Multiply by the Derating Factor 1.25
Total ampere hours required6AH
1 The FACP can only support 5 devices with LEDs on. The current draw has been added to the panels alarm current.
2 Total does not include isolator devices or accessory bases.
3 The FIK-2351R is sold separately from the DNR. Current draw for the DNR + FIK-2351R is calculated by increasing the “Number of
Devices” column for each FIK-2351R used with a DNR.
4 Maximum SBUS address capacity is determined by the amount of SBUS bandwidth consumed by each SBUS module. Refer to
Section 4.6.2 for SBUS limitations.
5 If there are door holders in the system, there is no need to consider door holder current for alarm/battery standby, because power is
removed during that time. However, during normal operation, door holders draw current and must be included in the 1.8 A total current that
can be drawn from the panel.
6 Use next size battery with capacity greater than required.
Device # of Devices Current per Device Standby
Current Alarm Current
Table 3.2 Current Draw Worksheet for IDP SLC Devices (Continued)

FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022 19
Calculating Current Draw and Standby Battery Prerequisites for Installation
Maximum Battery Standby Load
Table 3.3 shows the maximum battery standby load for the FCP-75 based on 24 and 60 hours of standby. The standby load calculations of
line G in the Current Draw Calculation Worksheet (Table 3.2) must be less than the number shown in Table 3.3 for the battery size used and
standby hours required.
Rechargeable
Battery Size Max. Load for 24 hrs. Standby,
5 mins. Alarm
1Max. Load for 60 hrs. Standby,
5 mins. Alarm
1 Required for NFPA 72 Auxiliary Protected FireAlarm systems for Fire Alarm Service (City Box) and
Remote Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm
Communicator/Transmitter (DACT).
7 AH 270 mA 105 mA
12 AH 475 mA 190 mA
17 AH 685 mA 270 mA
33 AH 1370 mA 540 mA
Table 3.3 Maximum Battery Standby Load

20 FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022
Section 4: Control Panel Installation
4.1 Mounting the Control Panel Cabinet
Read the Environmental Specifications in Section 3.2 before mounting the FCP-75 panel.
The FCP-75 cabinet base dimensions are: 12.531” W x 14.875” H.
The FCP-75 panel should be located within a secured area, where it is accessible to the main drop wiring runs and where it can be easily
tested and serviced. End-users responsible for maintaining the panel should be able to hear alarms and troubles. When you select a location,
keep in mind that the panel itself is the main source of alarm and trouble annunciation.
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting on concrete, especially when moisture is
expected, attach a piece of ¾” plywood to the concrete surface and then attach the FCP-75 to the plywood.Also mount any other desired
components to the plywood.
DO NOT flush-mount the FCP-75 cabinet in a wall designated as a fire break.
1. Mark and pre-drill hole in the wall for the top keyhole mounting bolt using the dimensions illustrated below.
2. Install top fasteners in the wall with the screw head protruding.
3. Place backbox over the top screws, level and secure.
4. Mark and drill the left and right lower mounting holes.
5. Install remaining fasteners and tighten.
4.1.1 Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits that are installed to enter the
top of the cabinet are most likely to cause water problems. Installers should take reasonable precautions to prevent water from entering the
cabinet. Water damage is not covered under Warranty.
4.1.2 Removing the FCP-75 Assembly from the Housing
If it should ever be necessary to remove the control panel assembly from the cabinet for repair, do so by removing the screws that hold the
control panel in to the cabinet. Do not attempt to disassemble the circuit boards.
4.1.3 Dead Front Installation and Removal
This section provides instructions to install and or remove the optional dead front for the control panel cabinet.
Installing the Dead Front
Follow these steps to properly install the dead front panel into the control panel cabinet.
1. Remove the top two screws which secure the annunciator to the board. Leave the bottom two screws installed. See Figure 4.2 for
annunciator screw location.
2. Set the dead front into the cabinet.
!
CAUTION: DISCONNECT POWER
TOAVOID THE RISK OF ELECTRICAL SHOCKAND DAMAGE TO THE UNIT, POWER SHOULD BE OFFAT THE
CONTROL PANEL WHILE INSTALLING OR SERVICING.
11.25”
Figure 4.1 FCP-75 Cabinet
lower mounting holes
Other manuals for FCP-75
1
Table of contents
Other Fike Control Panel manuals

Fike
Fike TWINFLEXpro User manual

Fike
Fike CIE-A-200 User manual

Fike
Fike FCP-75 User manual

Fike
Fike Twinflex pro2 User manual

Fike
Fike FIK-5496 User manual

Fike
Fike GB2426367 User manual

Fike
Fike TWINFLEXpro User manual

Fike
Fike Quadnet User manual

Fike
Fike FIK-RA2000 Technical manual

Fike
Fike FCP-2100ECS User manual