Fike FCP-75 User manual

A
P/N LS10147-003FK-E:A • ECN 151526
Document LS10147-003FK-E
3/17/2021 Rev:
Addressable Fire Alarm Control Panel
FCP-75
Instruction Manual

2FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control panel (FACP) with remote
notification capability—can provide early warning of a developing fire.
Such a system, however, does not assure protection against property
damage or loss of life resulting from a fire.
An emergency communication system—typically made up of an
automatic fire alarm system (as described above) and a life safety
communication system that may include an autonomous control unit
(ACU), local operating console (LOC), voice communication, and
other various interoperable communication methods—can broadcast
a mass notification message. Such a system, however, does not
assure protection against property damage or loss of life resulting
from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors be
located throughout a protected premises following the
recommendations of the current edition of the National Fire Protection
Association Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the recommendations
contained in the Guide for Proper Use of System Smoke Detectors,
which is made available at no charge to all installing dealers. This
document can be found at http://www.systemsensor.com/appguides/.
A study by the Federal Emergency ManagementAgency (an agency
of the United States government) indicated thatsmoke detectors may
not go off in as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not guarantee
warning or protection against fire. A fire alarm system may not
provide timely or adequate warning, or simply may not function, for a
variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the
detectors such as in chimneys, in or behind walls, on roofs, or on the
other side of closed doors.Smoke detectors alsomay not sense a fire
on another level or floor of a building. A second-floor detector, for
example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not
reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chimneys,
even wet or humid areas may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the
ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets,
such as air conditioning vents.
• Smoke particles may be drawn into air returns before reaching the
detector.
The amount of “smoke” present may be insufficient to alarm smoke
detectors. Smoke detectors are designed to alarm at various levels of
smoke density. If such density levels are not created by a developing
fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing chambers
tend to detect smoldering fires better than flaming fires, which have
little visible smoke. Detectors that have ionizing-type sensing
chambers tend to detect fast-flaming fires better than smoldering
fires. Because fires develop in different ways and are often
unpredictable in their growth, neither type of detector is necessarily
best and a given type of detector may not provide adequate warning
of a fire.
Smoke detectors cannot be expected to provide adequate warning of
fires caused by arson, children playing with matches (especially in
bedrooms), smoking in bed, and violent explosions (caused by
escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only
when heat on their sensors increases at a predetermined rate or
reaches a predetermined level. Rate-of-rise heat detectors may be
subject to reduced sensitivity over time. For this reason, the rate-of-
rise feature of each detector should be tested at least once per year
by a qualified fire protection specialist. Heat detectors are designed to
protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room
as the control panel and in rooms used by the system for the
connection of alarm transmission wiring, communications, signaling,
and/or power. If detectors are not so located, a developing fire may
damage the alarm system, compromising its ability to report a fire.
Audible warning devices such as bells, horns, strobes, speakers
and displays may not alert people if these devices are located on the
other side of closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert people with a
disability or those who have recently consumed drugs, alcohol, or
medication. Please note that:
• An emergency communication system may take priority over a fire
alarm system in the event of a life safety emergency.
• Voice messaging systems must be designed to meet intelligibility
requirements as defined by NFPA, local codes, andAuthorities
Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dissemi-
nated on any local displays.
• Strobes can, under certain circumstances, cause seizures in peo-
ple with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a
fire alarm signal, do not respond to or comprehend the meaning of
the signal.Audible devices, such as horns and bells, can have dif-
ferent tonal patterns and frequencies. It is the property owner's
responsibility to conduct fire drills and other training exercises to
make people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause
temporary or permanent hearing loss.
A life safety system will not operate without any electrical power. If
AC power fails, the system will operate from standby batteries only for
a specified time and only if the batteries have been properly
maintained and replaced regularly.
Equipment used in the system may not be technically compatible
with the control panel. It is essential to use only equipment listed for
service with your control panel.
Alarm Signaling Communications:
•IP connections rely on available bandwidth, which could be lim-
ited if the network is shared by multiple users or if ISP policies
impose restrictions on the amount of data transmitted. Service
packages must be carefully chosen to ensure that alarm signals
will always have available bandwidth. Outages by the ISP for
maintenance and upgrades may also inhibit alarm signals. For
added protection, a backup cellular connection is recommended.
•Cellular connections rely on a strong signal. Signal strength can
be adversely affected by the network coverage of the cellular car-
rier, objects and structural barriers at the installation location. Uti-
lize a cellular carrier that has reliable network coverage where the
alarm system is installed. For added protection, utilize an external
antenna to boost the signal.
•Telephone lines needed to transmit alarm signals from a premise
to a central monitoring station may be out of service or temporarily
disabled. For added protection against telephone line failure,
backup alarm signaling connections are recommended.
The most common cause of life safety system malfunction is
inadequate maintenance. To keep the entire life safety system in
excellent working order, ongoing maintenance is required per the
manufacturer's recommendations, and UL and NFPA standards.At a
minimum, the requirements of NFPA 72 shall be followed.
Environments with large amounts of dust, dirt, or high air velocity
require more frequent maintenance.A maintenance agreement
should be arranged through the local manufacturer's representative.
Maintenance should be scheduled as required by National and/or
local fire codes and should be performed by authorized professional
life safety system installers only. Adequate written records of all
inspections should be kept. Limit-F-2020

FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be con-
nected to the fire alarm control panel. Disconnect all sources of
power before servicing. Control unit and associated equipment may
be damaged by removing and/or inserting cards, modules, or inter-
connecting cables while the unit is energized. Do not attempt to
install, service, or operate this unit until manuals are read and under-
stood.
CAUTION - System Re-acceptance Test after Software Changes:
To ensure proper system operation, this product must be tested in
accordance with NFPA 72 after any programming operation or
change in site-specific software. Re-acceptance testing is required
after any change, addition or deletion of system components, or after
any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions
known to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected, at
least 10% of initiating devices that are not directly affected by the
change, up to a maximum of 50 devices, must also be tested and
proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-
120º F and at a relative humidity 93% ± 2% RH (non-condensing) at
32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's
standby batteries and the electronic components may be adversely
affected by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and its peripherals be installed in
an environment with a normal room temperature of 15-27º C/60-80º
F.
Verify that wire sizes are adequate for all initiating and indicating
device loops. Most devices cannot tolerate more than a 10% I.R.
drop from the specified device voltage.
Like all solid state electronic devices, this system may operate
erratically or can be damaged when subjected to lightning induced
transients.Although no system is completely immune from lightning
transients and interference, proper grounding will reduce susceptibil-
ity. Overhead or outside aerial wiring is not recommended, due to an
increased susceptibility to nearby lightning strikes. Consult with the
Technical Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting
circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, ream-
ing, or punching of the enclosure. When possible, make all cable
entries from the sides or rear. Before making modifications, verify
that they will not interfere with battery, transformer, or printed circuit
board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening
may damage threads, resulting in reduced terminal contact pressure
and difficulty with screw terminal removal.
This system contains static-sensitive components. Always
ground yourself with a proper wrist strap before handling any circuits
so that static charges are removed from the body. Use static sup-
pressive packaging to protect electronic assemblies removed from
the unit.
Units with a touchscreen display should be cleaned with a dry,
clean, lint free/microfiber cloth. If additional cleaning is required,
apply a small amount of Isopropyl alcohol to the cloth and wipe
clean. Do not use detergents, solvents, or water for cleaning. Do not
spray liquid directly onto the display.
Follow the instructions in the installation, operating, and program-
ming manuals.These instructions must be followed to avoid damage
to the control panel and associated equipment. FACP operation and
reliability depend upon proper installation.
Precau-D2-11-2017
FCC Warning
WARNING: This equipment generates, uses, and can radi-
ate radio frequency energy and if not installed and used in
accordance with the instruction manual may cause interfer-
ence to radio communications. It has been tested and found
to comply with the limits for classA computing devices pur-
suant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against such
interference when devices are operated in a commercial
environment. Operation of this equipment in a residential
area is likely to cause interference, in which case the user
will be required to correct the interference at his or her own
expense.
Canadian Requirements
This digital apparatus does not exceed the ClassA limits for
radiation noise emissions from digital apparatus set out in
the Radio Interference Regulations of the Canadian Depart-
ment of Communications.
Le present appareil numerique n'emet pas de bruits radio-
electriques depassant les limites applicables aux appareils
numeriques de la classeAprescrites dans le Reglement sur
le brouillage radioelectrique edicte par le ministere des
Communications du Canada.
eVance®, Flexput®, Honeywell®, JumpStart®, and SWIFT® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered
trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered trademark of The Mozilla Foundation.
©2021. All rights reserved. Unauthorized use of this document is strictly prohibited.

4FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent
upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly
recommend that you download the most current version of software for each product prior to commissioning any system. Contact
Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online
Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
or call (800)979-3453, x21 in US or (816)229-3405 international
This symbol (shown left) on the product(s) and / or accompanying documents means that used electrical and electronic products
should not be mixed with general household waste. For proper treatment, recovery and recycling, contact your local authorities or
dealer and ask for the correct method of disposal.
Electrical and electronic equipment contains materials, parts and substances, which can be dangerous to the environment and harmful
to human health if the waste of electrical and electronic equipment (WEEE) is not disposed of correctly.

FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021 5
Table of Contents
Section 1: Introduction ................................................................................................................................................... 10
1.1: Overview of Basic System...............................................................................................................................................................................10
1.1.1: Hardware Features................................................................................................................................................................................10
1.1.2: Network System Hardware Features ....................................................................................................................................................10
1.1.3: Software Features .................................................................................................................................................................................10
1.2: About this Manual............................................................................................................................................................................................10
1.2.1: Terms Used in this Manual...................................................................................................................................................................10
1.3: Compatible Products........................................................................................................................................................................................11
Section 2: Agency Listings, Approvals, and Requirements........................................................................................ 12
2.1: Federal Communications Commission (FCC).................................................................................................................................................12
2.2: Underwriters Laboratories (UL)......................................................................................................................................................................13
2.2.1: Requirements for All Installations........................................................................................................................................................13
Restricted Options: .................................................................................................................................................................................13
2.2.2: Requirements for Central Station Fire Alarm Systems ........................................................................................................................13
2.2.3: Requirements for Local Protected Fire Alarm Systems .......................................................................................................................13
2.2.4: Requirements for Remote Station Protected Fire Alarm Systems........................................................................................................13
2.2.5: Requirements for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, NFPA 720..................................13
2.2.6: NFPA Requirements.............................................................................................................................................................................14
Section 3: Before You Begin Installing ......................................................................................................................... 15
3.1: Inventory..........................................................................................................................................................................................................15
3.2: Environmental Specifications..........................................................................................................................................................................15
3.3: Software Downloads........................................................................................................................................................................................15
3.4: Electrical Specifications ..................................................................................................................................................................................15
3.5: Wiring Specifications.......................................................................................................................................................................................16
3.6: Board Assembly Diagram................................................................................................................................................................................17
3.7: Calculating Current Draw and Standby Battery ..............................................................................................................................................17
3.7.1: Current Draw Worksheet Requirements...............................................................................................................................................17
3.7.2: Current Draw Worksheet for Fike IDP SLC Devices ..........................................................................................................................18
Maximum Battery Standby Load............................................................................................................................................................20
Section 4: Control Panel Installation............................................................................................................................. 21
4.1: Mounting the Control Panel Cabinet...............................................................................................................................................................21
4.1.1: Preventing Water Damage....................................................................................................................................................................21
4.1.2: Removing the FCP-75 Assembly from the Housing............................................................................................................................21
4.2: AC Power Connection .....................................................................................................................................................................................21
4.3: Battery Power ..................................................................................................................................................................................................22
4.3.1: Battery Accessory Cabinet ...................................................................................................................................................................23
Installing the RBB Accessory Cabinet and Batteries .............................................................................................................................23
4.4: SBUS Wiring ...................................................................................................................................................................................................24
4.4.1: Calculating Wiring distance for SBUS modules ..................................................................................................................................24
4.4.2: Wiring Configurations..........................................................................................................................................................................26
4.5: FIK-RA100 Remote Annunciator Installation.................................................................................................................................................26
4.5.1: Mounting the FIK-RA100 ....................................................................................................................................................................27
Flush Mounting.......................................................................................................................................................................................27
Surface Mounting ...................................................................................................................................................................................29
4.5.2: FIK-RA100 Connection to the Panel....................................................................................................................................................30
4.6: FIK-RA1000R Remote Annunciator Installation............................................................................................................................................30
4.6.1: Mounting the FIK-RA1000R................................................................................................................................................................31
Flush Mounting.......................................................................................................................................................................................31
Surface Mounting ...................................................................................................................................................................................32
4.7: FIK-RA2000 Remote Annunciator Installation...............................................................................................................................................33
4.7.1: Mounting the FIK-RA2000 ..................................................................................................................................................................33
Flush Mounting.......................................................................................................................................................................................33
Surface Mounting ...................................................................................................................................................................................35
4.7.2: FIK-RA2000 Connection to the Panel..................................................................................................................................................36
4.8: FIK-5824 Serial/Parallel Printer Interface Module Installation ......................................................................................................................36
4.8.1: Selecting FIK-5824 Options.................................................................................................................................................................37
4.9: FIK-5880 LED Driver Module........................................................................................................................................................................37
4.9.1: FIK-5880 Board Layout .......................................................................................................................................................................38
4.9.2: FACP Connection.................................................................................................................................................................................38

6FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021
Table of Contents
4.9.3: LED Wiring..........................................................................................................................................................................................38
4.9.4: Dry Contact Wiring ..............................................................................................................................................................................39
4.10: FIK-5865-3 / FIK-5865-4 LED Annunciator Installation .............................................................................................................................40
4.10.1: FACP Connection...............................................................................................................................................................................41
4.10.2: FIK-5865 Mounting............................................................................................................................................................................41
4.11: Configuring Modules.....................................................................................................................................................................................42
4.11.1: Assigning Module IDs........................................................................................................................................................................42
4.12: Telephone Connection ...................................................................................................................................................................................43
4.13: Notification Appliance/Auxiliary Power Circuits .........................................................................................................................................43
4.13.1: Conventional Notification Appliance.................................................................................................................................................43
Class B Notification Wiring ...................................................................................................................................................................43
Class A Notification Wiring ...................................................................................................................................................................44
4.13.2: Auxiliary Power Installation...............................................................................................................................................................44
Door Holder Power.................................................................................................................................................................................44
Constant Power.......................................................................................................................................................................................45
Resettable Power.....................................................................................................................................................................................45
Sounder Sync Power...............................................................................................................................................................................45
4.14: On-Board Relays (Conventional) ..................................................................................................................................................................45
4.14.1: Common Trouble Relay .....................................................................................................................................................................45
4.14.2: Programmable Relays.........................................................................................................................................................................45
4.15: Remote Station Applications .........................................................................................................................................................................46
4.15.1: Keltron Model 3158 Installation.........................................................................................................................................................46
4.15.2: City Box Connection Using the 5220 Module ...................................................................................................................................46
4.15.3: NFPA 72 Polarity Reversal ................................................................................................................................................................47
Using the 5220 Module...........................................................................................................................................................................47
4.15.4: Using a MR-201/T Control Relay From Air Products .......................................................................................................................48
4.15.5: Transmitter Activated by Dry Contacts..............................................................................................................................................50
Section 5: Networking Common Communicator List .................................................................................................. 51
5.1: Network System Hardware Features ...............................................................................................................................................................51
5.1.1: Networked Panels.................................................................................................................................................................................51
5.1.2: Wiring Options to Connect Networked Panels.....................................................................................................................................51
5.2: Direct Connect Wiring Option.........................................................................................................................................................................51
5.3: FIK-NIC Wiring Options.................................................................................................................................................................................51
5.3.1: Fiber Loop Modules .............................................................................................................................................................................52
FIK-NIC-KIT Mounting Kit...................................................................................................................................................................53
5.3.2: FIK-NIC Installation.............................................................................................................................................................................53
Unshielded Twisted Pair Wiring between Multiple Panels....................................................................................................................54
Fiber Optic Multi-Mode Wiring between Multiple Panels.....................................................................................................................55
Fiber Optic and Twisted Pair Wiring between Multiple Panels .............................................................................................................57
5.4: Setting the Panel ID for each Panel Network ..................................................................................................................................................58
Section 6: Network Management................................................................................................................................... 59
6.1: Network Diagnostics .......................................................................................................................................................................................59
6.1.1: Ping Panel.............................................................................................................................................................................................59
6.1.2: Data Network Status.............................................................................................................................................................................59
6.2: Network Programming ....................................................................................................................................................................................59
6.2.1: Learn Network......................................................................................................................................................................................59
6.2.2: Edit Network Names.............................................................................................................................................................................59
6.2.3: Edit Panel ID.........................................................................................................................................................................................59
6.2.4: Computer Access..................................................................................................................................................................................60
6.2.5: Access Codes........................................................................................................................................................................................60
Edit Name ...............................................................................................................................................................................................61
Edit Access Code....................................................................................................................................................................................61
Panel Functions.......................................................................................................................................................................................61
6.2.6: Communicator Options.........................................................................................................................................................................61
Communicator Assignments...................................................................................................................................................................61
Communicator Miscellaneous ................................................................................................................................................................61
Receiver Configuration...........................................................................................................................................................................61
Communicator Reporting Table .............................................................................................................................................................62
6.3: Sync Network Options.....................................................................................................................................................................................62
6.4: Network Management Quick Reference .........................................................................................................................................................63

FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021 7
Table of Contents
Section 7: Fike IDP and SWIFT SLC Device Installation.............................................................................................. 65
7.1: List of Fike IDP SLC Devices.........................................................................................................................................................................65
7.2: SWIFT Wireless SLC Devices ........................................................................................................................................................................65
7.3: Maximum Number of Devices ........................................................................................................................................................................65
7.4: Wiring Requirements for SLC Devices...........................................................................................................................................................66
7.4.1: Wire Sizing for Internal SLC................................................................................................................................................................66
7.4.2: Wiring Requirements for IDP Modules................................................................................................................................................66
7.4.3: Wiring SLC in Class A Configuration..................................................................................................................................................67
7.5: Addressing IDP SLC Devices..........................................................................................................................................................................68
7.6: Wiring the FIK-W-WGI...................................................................................................................................................................................68
7.6.1: SLC Connections..................................................................................................................................................................................68
Section 8: Programming Overview................................................................................................................................ 69
8.1: JumpStart AutoProgramming ..........................................................................................................................................................................69
8.1.1: Input Points...........................................................................................................................................................................................69
8.1.2: Output Points ........................................................................................................................................................................................69
8.1.3: Running JumpStart AutoProgramming ................................................................................................................................................69
8.2: Mapping Overview ..........................................................................................................................................................................................70
8.2.1: Input Point Mapping.............................................................................................................................................................................70
8.2.2: Output Circuit Mapping........................................................................................................................................................................72
8.2.3: Event Mapping.....................................................................................................................................................................................72
8.2.4: Mapping LED Points............................................................................................................................................................................75
8.3: Programming Using the HFSS Programming Tool .........................................................................................................................................75
8.4: Programming Using an Annunciator ...............................................................................................................................................................75
8.4.1: Entering / Exiting the Program Menu..................................................................................................................................................76
8.4.2: Moving through the Menus ..................................................................................................................................................................76
8.4.3: Selecting Options and Entering Data....................................................................................................................................................76
8.5: Programming Menu Quick Reference.............................................................................................................................................................77
Section 9: Programming................................................................................................................................................. 84
9.1: UL 864 Programming Requirements...............................................................................................................................................................84
9.2: Modules ...........................................................................................................................................................................................................84
9.2.1: Edit Modules.........................................................................................................................................................................................84
Editing Module ID..................................................................................................................................................................................84
Naming Modules.....................................................................................................................................................................................84
Changing Module Options......................................................................................................................................................................85
9.2.2: Adding a Module..................................................................................................................................................................................85
9.2.3: Deleting a Module ................................................................................................................................................................................85
9.2.4: View Module List.................................................................................................................................................................................85
9.3: Zone.................................................................................................................................................................................................................85
9.3.1: Edit Zone ..............................................................................................................................................................................................85
Edit Zone Name......................................................................................................................................................................................86
Edit Zone Properties ...............................................................................................................................................................................86
Zone Accessory Options.........................................................................................................................................................................87
9.3.2: View Zone Points .................................................................................................................................................................................87
9.4: Group...............................................................................................................................................................................................................88
9.4.1: Edit Group ............................................................................................................................................................................................88
Edit Group Name....................................................................................................................................................................................88
Edit Group Properties .............................................................................................................................................................................88
9.4.2: View Group Points ...............................................................................................................................................................................88
9.4.3: Edit OPG Template...............................................................................................................................................................................89
9.5: Point.................................................................................................................................................................................................................89
9.5.1: Point Programming For SLC................................................................................................................................................................89
9.5.2: Point Programming for the Internal or External Power Module ..........................................................................................................91
9.5.3: Point Programming For FIK-5880 and FIK-5865 Modules.................................................................................................................92
9.6: System Options................................................................................................................................................................................................93
9.6.1: Communication Options.......................................................................................................................................................................93
Auto Test Time.......................................................................................................................................................................................93
Phone Lines.............................................................................................................................................................................................93
Edit Ethernet ...........................................................................................................................................................................................94
AlarmNet Timers....................................................................................................................................................................................95
Phone Line Gains....................................................................................................................................................................................95
9.6.2: Daytime/Nighttime Sensitivity.............................................................................................................................................................95

8FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021
Table of Contents
9.6.3: Holiday Days ........................................................................................................................................................................................96
9.6.4: Time Options ........................................................................................................................................................................................96
Water Flow Delay...................................................................................................................................................................................96
Alarm Verify...........................................................................................................................................................................................97
AC Report Delay ....................................................................................................................................................................................97
AC Line Frequency.................................................................................................................................................................................97
Clock Display Format (AM/PM or Military) .........................................................................................................................................97
Auto-Resound (4 or 24 hours)................................................................................................................................................................97
9.6.5: Miscellaneous Options..........................................................................................................................................................................97
Strobes Active when Silenced ................................................................................................................................................................98
Auto Display Events...............................................................................................................................................................................98
9.6.6: Daylight Saving Options.......................................................................................................................................................................98
Automatic Daylight Saving Adjustment.................................................................................................................................................98
Daylight Saving Time Start and End......................................................................................................................................................98
9.6.7: Edit Banner...........................................................................................................................................................................................98
9.6.8: SLC Family...........................................................................................................................................................................................99
9.7: JumpStart Autoprogramming...........................................................................................................................................................................99
9.8: Restore Defaults...............................................................................................................................................................................................99
Section 10: System Operation...................................................................................................................................... 100
10.1: User and Installer Default Codes:................................................................................................................................................................100
10.2: Annunciator Description..............................................................................................................................................................................100
10.2.1: LCD Display.....................................................................................................................................................................................100
10.2.2: Banner...............................................................................................................................................................................................100
10.2.3: Single Key Acknowledge .................................................................................................................................................................100
10.3: Menu System ...............................................................................................................................................................................................101
10.3.1: Main Menu Overview.......................................................................................................................................................................101
10.3.2: Using the Menus...............................................................................................................................................................................101
10.4: Basic Operation ...........................................................................................................................................................................................101
10.4.1: Setting Time and Date ......................................................................................................................................................................101
10.4.2: Disable / Enable a Point....................................................................................................................................................................101
Disable / Enable NACs by Template....................................................................................................................................................101
Disable / Enable NACs by Group.........................................................................................................................................................101
Disable / Enable Zone Points................................................................................................................................................................101
Disable / Enable Point...........................................................................................................................................................................101
Inhibit Output Group ............................................................................................................................................................................101
10.4.3: View Event History ..........................................................................................................................................................................102
To clear the event history......................................................................................................................................................................102
10.4.4: Conduct a Fire Drill..........................................................................................................................................................................102
10.4.5: Conduct an Indicator Test.................................................................................................................................................................102
10.4.6: Conduct a Walk Test ........................................................................................................................................................................102
10.4.7: Conduct a Communicator Test.........................................................................................................................................................102
10.4.8: Manual AlarmNet Registration.........................................................................................................................................................103
10.4.9: Silence Alarms or Troubles ..............................................................................................................................................................103
10.4.10: Reset alarms....................................................................................................................................................................................103
Reset Communicator............................................................................................................................................................................103
10.4.11: Check Detector Sensitivity Through Point Status..........................................................................................................................103
10.4.12: View Status of a Point ....................................................................................................................................................................104
10.4.13: View Alarms, Supervisories or Troubles........................................................................................................................................104
10.4.14: View System Information...............................................................................................................................................................104
10.5: Operation Mode Behavior ...........................................................................................................................................................................105
10.6: Operation Mode Behavior ...........................................................................................................................................................................106
10.6.1: Multi-Site Annunciator and Multi-Site User Access........................................................................................................................108
10.7: Releasing Operations...................................................................................................................................................................................108
10.7.1: Single Interlock Zone Releasing.......................................................................................................................................................109
10.7.2: Double Interlock Zone Releasing .....................................................................................................................................................110
10.8: Smoke Alarm Verification ...........................................................................................................................................................................110
10.9: Function Keys.............................................................................................................................................................................................111
10.9.1: Recording an F-Key Macro ..............................................................................................................................................................111
10.9.2: Aborting an F-Key Macro Recording Session..................................................................................................................................111
10.9.3: Erasing an F-Key Macro...................................................................................................................................................................111
10.9.4: Using a Recorded F-Key Macro.......................................................................................................................................................111

FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021 9
Table of Contents
10.9.5: F-Key Status Event...........................................................................................................................................................................111
10.9.6: F-Key Map Inhibit............................................................................................................................................................................111
Section 11: Reporting ................................................................................................................................................... 112
11.1: Receivers Compatible with the Control Panel.............................................................................................................................................112
11.2: SIA / FCP-75 Panels PI Modifier Reporting: ..............................................................................................................................................119
11.3: SIA– FCP-75 Panel Communicator:............................................................................................................................................................120
Section 12: Testing and Troubleshooting................................................................................................................... 122
12.1: Troubleshooting...........................................................................................................................................................................................122
Table 12.1: Common Problems.............................................................................................................................................................................122
12.1.1: Periodic Testing And Maintenance ..................................................................................................................................................122
12.1.2: Event History....................................................................................................................................................................................123
12.2: Built-in Troubleshooting and Testing Tools ................................................................................................................................................123
12.2.1: SLC Device Locater .........................................................................................................................................................................123
12.2.2: SLC Multi Locater............................................................................................................................................................................123
12.2.3: I/O Point Control ..............................................................................................................................................................................124
12.3: Earth Fault Resistance .................................................................................................................................................................................124
Section 13: Installation Records.................................................................................................................................. 125
13.1: IDP SLC Device Point Record ....................................................................................................................................................................125
Appendix A: Compatible Devices ................................................................................................................................ 127
A.1: Notification Appliances ................................................................................................................................................................................127
A.2: Four Wire Smoke Detectors/Devices (UL Listed)........................................................................................................................................136
A.3: Door Holders (UL Listed).............................................................................................................................................................................137
A.4: Relays (UL Listed)........................................................................................................................................................................................137
A.5: Compatible 520Hz Signaling Speakers ........................................................................................................................................................138
A.6: Compatible 520Hz Low Frequency Bases....................................................................................................................................................138
Appendix B: Editing Text Using the Built-In Programmer......................................................................................... 139
B.1: Characters Used for Editing Text..................................................................................................................................................................139
B.2: Example Name Edit ......................................................................................................................................................................................139
Appendix C: Expanded Receiver/Panel Relationship................................................................................................ 140
Appendix D: Cadence Patterns.................................................................................................................................... 141
Appendix E: Panel Security.......................................................................................................................................... 142
Model FCP-75 Basic Operating Instructions............................................................................................................... 143

10 FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021
Section 1: Introduction
The FCP-75 Fire Alarm Control / Communicator is an Addressable Fire Alarm Control System that meets the requirements of UL 864.
1.1 Overview of Basic System
1.1.1 Hardware Features
• The FCP-75 has one built in signaling line circuit (SLC) that supports 75 IDP detectors and 75 IDP modules.
• The FCP-75 is capable of outputting 2.5A of output power during an alarm activation through 2 sets of terminals for the notification
appliance circuits or an auxiliary application. Each circuit is power-limited per UL 864 and can source up to 2.5A during an alarm
activation. The constant auxiliary power load must not exceed 1A for normal standby.
• Built-in dual phone line, digital alarm communicator/transmitter (DACT), or IP technologies.
• Reports events to central station by point or by zone.
• UL Listed for pre-action and deluge releasing systems.
• Two general purpose Form C programmable relays.
• One Form C Trouble Relay.
• Basic system operation can be performed from the on-board, or any remote annunciator.
• Up to 20 user profiles can be programmed, each having custom Access Code, and Main Menu items.
• Can be used with any combination of up to 8 Model FIK-RA100, FIK-RA1000R, or FIK-RA2000 Remote LCD Annunciators (sold
separately).
• Can be used with Model FIK-5865-3, FIK-5865-4, and FIK-5880 in any combination for a total of eight devices on one control panel.
See Figure 4.29 and Figure 4.32 for additional information on these models.
• Printing of event log available through the Model FIK-5824 serial/parallel printer interface module.
• 125 software zones, 125 Output Groups.
• Add four Notification/Auxiliary power circuits with each FIK-5496 NAC Expander. See note below.
1.1.2 Network System Hardware Features
• The default network setup can contain up to 32- FCP-75 panels connected.
• Network support for up to 32 Sites.
• Each building is referred to as a “site”.
• Panels can be interconnected using CLASS B or CLASS A topology.
• Use the FIK-NIC Network Interface Card to create a network. Copper wire or fiber optic cable panel connectivity can be used within
the same networked system.
• The network architecture provides true peer to peer capability allowing network survivability for all hardware that remains operational
in the event of partial system failure.
1.1.3 Software Features
• Advanced smoke detector features:
– Automatic drift compensation
– Maintenance alert region
– Point status meets calibrated smoke test requirements for NFPA 72
• “JumpStart” feature for easy programming
• Non-volatile event history stores 1000 events
• A choice of output patterns available for notification outputs, including Temp 4 along with ANSI 3.41 temporal signal
• Built-in synchronization appliance support forAMSECO, Gentex®, Wheelock®, or System Sensor ®
1.2 About this Manual
This manual is intended to be a complete reference for all installation and operation tasks for the FCP-75. Please let us know if the manual
does not meet your needs in any way. We value your feedback!
1.2.1 Terms Used in this Manual
The following terminology is used with the FCP-75 system:
NOTE: Total output power for both circuits must not exceed 2.5A in alarm condition, and total output power for both circuits must not exceed
1.0A for all other activation conditions (i.e. Supervisory, Trouble, etc.).
NOTE: The system can support a maximum of eight intelligent power modules, either the FIK-RPS1000 or FIK-5496, in any combination.
Term Description
SLC Signaling Line Circuit
Module The term module is used for all hardware devices except for SLC addressable devices and notification
appliances. This includes the FCP-75 panel itself.
Input Point An addressable sensing device, such as a smoke or heat detector or a contact monitor device.
Input Zone A protected area made up of input points.
Table 1.1 Manual Terminology

Compatible Products Introduction
FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021 11
1.3 Compatible Products
The chart below lists the products available for use with the FCP-75.
Output Point (or Output Circuit) Anotification point or circuit for notification appliances. Relay circuits and auxiliary power circuits are also
considered output points.
Group (or “Output Group”) Agroup of output points. Operating characteristics are common to all output points in the group.
Output (or “Cadence”) Pattern The pattern that the output will use, for example, Constant, March Code, ANSI 3.41. Applies to zones
and special system events. See Appendix D for additional information.
Mapping Mapping is the process of specifying which outputs are activated when certain events occur in the
system. Figure 8.2 explains mapping in detail.
Network System Consist of any combination of 32 panels of these model numbers: FCP-75, FCP-300, FCP-300ECS,
FCP-2100 or FCP-2100ECS.
SWIFT Smart Wireless Integrated Fire Technology
Term Description
Table 1.1 Manual Terminology (Continued)
Type of Device Model Description
Fike IDP Addressable SLC
Devices See Section 7.1 for a list of compatible devices.
SWIFT Wireless SLC Devices See Section 7.2 for a list of compatible devices
Other Modules FIK-5824 Serial/Parallel
Printer Interface Module Allows a printer to be attached for the on-site event logging. Maximum of four FIK-5824s per
control panel.
FIK-RPS1000 Power
Supply Provides additional power, six Flexput circuits, and two Form C relays. Max 8 per system. See
FIK-RPS1000 Installation Manual (PN LS10259-001FK-E) for more information.
FIK-5496 NAC Expander Provides 4 additional Notification Appliance Circuits/Auxiliary power. (Up to 8 per FCP-75
system).
FIK-RA100 and
FIK-RA1000R LCD
Annunciator
4 x20 Remote LCD annunciator. can be used in any combination, up to a total of 8 devices on
one panel.
FIK-RA2000 LCD
Annunciator 4 x 40 Remote LCD annunciator can be used in any combination, up to a total of 8 devices on
one panel.
FIK-5865-3 and
FIK-5865-4 LED
Annunciator
LED annunciator can display up to 30 LEDs (15 red and 15 yellow). FIK-5865-4 has key
switches for silence and reset, and a system trouble LED. FIK-5865-3, FIK-5865-4, and FIK-
5880 can be used in any combination, up to a total of eight devices on one panel.
RA-100TR Trim Ring Trim ring kit for surface mounting the FIK-RA2000/FIK-RA1000R annunciators.
FIK-5880 LED Driver
Module Driver for up to 40 LEDs. Interfaces with customized annunciator boards. In addition the FIK-
5880 has eight generic switch input points.
FIK-5883 General
Purpose Relay Module Provides 10 Form C relays. Designed to be driven by the FIK-5880. Up to four, FIK-5883s can
be used with each FIK-5880 module.
FIK-NIC Network Interface Card
FIK-FML Fiber-Optic Multi Mode
FIK-FSL Fiber-Optic Single Mode
Wireless FIK-W-WGI Wireless Gateway
FIK-W-PHOTO Wireless Photoelectric Smoke Detector with 4" base
FIK-W-ACCLIMATE Wireless Multi criteria photoelectric smoke detector with thermal (135°F) with 4" base
FIK-W-HEAT-ROR Wireless heat, ROR/ 135° fixed with 4" base
FIK-W-HEAT Wireless Heat, 135° fixed with 4" base
FIK-W-MONITOR Wireless Addressable Monitor module
FIK-W-RELAY Wireless Addressable Relay module
B210W 6" wireless base
Misc. HFSS Programming Tool For communication and panel programming with a Windows-based computer. Enables remote
viewing of detector status and event history.
7860 Telephone Cord RJ31X cord for connecting phone line to the FCP-75.
7628 UL Listed End-of-line resistor
Table 1.2 FCP-75 Compatible Products

12 FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021
Section 2: Agency Listings, Approvals, and Requirements
Install and maintain in accordance with NFPA 72. Detector spacing shall be in accordance to NFPA 72. End-of -line relays and resistors shall
be placed within the electrical box located and the end of the initiating circuit. Testing and maintenance should be performed according to
NFPA 72.
2.1 Federal Communications Commission (FCC)
The following information must be provided to the telephone company before the FCP-75 can be connected to the phone lines:
1. This device may not be directly connected to coin telephone or party line services.
2. This device cannot be adjusted or repaired in the field. In case of trouble with the device, notify the installing company or return to:
Fike Corporation
704 SW 10th Street
Blue Springs, MO 61015
1+816-229-3405
3. If the FCP-75 causes harm to the telephone network, the telephone company will notify the user in advance that temporary
discontinuance of service may be required. If advance notice is not practical, the telephone company will notify the user as soon as
possible. Users have the right to file complaints, if necessary, with the Federal Communications Commission.
4. The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the
equipment. If this happens, the telephone company will provide advance notice to allow you to make the necessary modifications to
maintain uninterrupted service.
1. This equipment complies with Part 68 of the FCC rules and the requirements adopted by theACTA. On the wiring diagram of this
equipment is a label that contains, among other information, a product identifier in the format US: HS9AL10A2100. If requested,
this number must be provided to the telephone company.
2. See manual for phone jack information.
3. A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable
FCC Part 68 rules and requirements adopted by the ACTA. A compliant telephone cord and modular plug is provided with this
product. It is designed to be connected to a compatible modular jack that is also compliant. See installation instructions for details.
4. The REN (ringer equivalence number) provided on this installation sheet is used to determine the number of devices that may be
connected to the public switched telephone network. This number must not exceed 5.0. Since this product has an REN of 1.0A, the
number of devices is limited. The REN number is embedded in the FCC registration number as 10A.
5. If this equipment FCP-75 causes harm to the telephone network, the telephone company will notify you in advance that temporary
discontinuance of service may be required. But if advance notice isn't practical, the telephone company will notify the customer as
soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
6. The telephone company may make changes in its facilities, equipment, operations or procedures that could affect the operation of
the equipment. If this happens the telephone company will provide advance notice in order for you to make necessary
modifications to maintain uninterrupted service.
7. If trouble is experienced with the FCP-75, for repair or warranty information, please contact technical support at (800)979-3453
or www.fike.com. If the equipment is causing harm to the telephone network, the telephone company may request that you
disconnect the FCP-75 until the problem has been resolved.
8. See warranty in back of this manual for repair and replacement information.
9. Connection to party line service is subject to state tariffs. Contact the state public utility commission, public service commission or
corporation commission for information.
10. If your home has specially wired alarm equipment connected to the telephone line, ensure the installation of this FCP-75 does not
disable your alarm equipment. If you have questions about what will disable alarm equipment, consult your telephone company or
qualified installer.
Electrical Safety Advisory:
Parties responsible for equipment requiringAC power should consider including an advisory notice in their customer information suggesting
the customer use a surge arrestor. Telephone companies report that electrical surges, typically lightning transients, are very destructive to
customer terminal equipment connected to AC power sources. This has been identified as a major nationwide problem.
A Manufacturer: Fike
B Model Number: FCP-75
C FCC registration number: US: HS9AL10A2100
Ringer equivalence: 1.0A
D Type of jack: RJ31X
E Facility Interface Codes: Loop Start: 02LS2
F Service Order Code: 9.0F
!
WARNING: FCC RULES PART 15
THIS DEVICE HAS BEEN VERIFIED TO COMPLY WITH FCC RULES PART 15. OPERATION IS SUBJECT TO THE
FOLLOWING CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE RADIO INTERFERENCE, AND (2) THIS DEVICE MUST
ACCEPTANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.

FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021 13
Underwriters Laboratories (UL) Agency Listings, Approvals, and Requirements
2.2 Underwriters Laboratories (UL)
2.2.1 Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for addi-
tional requirements. The following subsections list specific requirements for each type of installation (for example, Central Station Fire
Alarm systems, Local Protected Fire Alarm systems, and so on). See Section 10.7 for information on releasing operation.
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use the addressable smoke detectors specified in Section 7 of this manual.
3. Use UL listed notification appliances compatible with the FCP-75 from those specified in the Appendix at the back of this manual.
4. A full system checkout must be performed any time the panel is programmed.
Restricted Options:
• The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 - 30 hours. For UL certified installations this
number must be set from 1 to 3 hours.
• The system allows the use of non-latching spot type smoke detectors.This feature may not be used in commercial applications whereby
a general alarm is sounded. It is intended for elevator recall, door holding applications, and hotel/motel room applications.
• The system allows the Alarm Verification time to be set from 60 to 250 seconds. For UL certified installations the setting must be a
maximum of 60 seconds.
• The systems allows the Auto-resound time to be set to 4 or 24 hours. For ULcertified installations that are utilizing SWIFT devices, the
value must be set to 4 hours.
• Call forwarding shall not be used.
• When two count is used detector spacing shall be cut in half, you shall not use the alarm verification feature, and no delay shall be used.
• P.A.S (positive alarm sequence) feature shall be used only with automatic detectors.
2.2.2 Requirements for Central Station Fire Alarm Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the FCP-75 shall automatically initiate and complete a test signal
transmission sequence to its associated receiver at least once every 6 hrs. The AC Loss Hours option must be set from 1-3 hours.
3. If using wired Ethernet, you must program the corresponding account/subscriber ID and a test time so that the FACP shall automatically
initiate a test signal transmission sequence to its associated receiver at least once every 6 hrs.
2.2.3 Requirements for Local Protected Fire Alarm Systems
At least one UL listed supervised notification appliance must be used.
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems
1. Do not exceed the current load restrictions shown in Section 3.7.
2. The AC Loss Hours option must be set from 1-3 hours.
2.2.5 Requirements for the Installation of Carbon Monoxide (CO) Detection and Warning
Equipment, NFPA 720
When using carbon monoxide detection the system must be monitored by a Supervising Station.
!
CAUTION: INSTALLATION AND TEST
TO ENSURE PROPER OPERATION, THIS EQUIPMENT MUST BE INSTALLED ACCORDING TO THE ENCLOSED
INSTALLATION INSTRUCTIONS. TO VERIFY THAT THE EQUIPMENT IS OPERATING PROPERLYAND CAN
SUCCESSFULLY REPORTAN ALARM, THIS EQUIPMENT MUST BE TESTED IMMEDIATELY AFTER INSTALLATION,
AND PERIODICALLY THEREAFTER, ACCORDING TO THE ENCLOSED TEST INSTRUCTIONS.
!
CAUTION: LINE IN USE
IN ORDER FOR “ALARM DIALING EQUIPMENT” TO BE ABLE TO SEIZE THE PHONE LINE TO REPORTAN ALARM OR
OTHER EVENT WHEN OTHER CUSTOMER EQUIPMENT (TELEPHONE,ANSWERING SYSTEM, COMPUTER MODEM,
ETC.) CONNECTED TO THE SAME LINE IS IN USE, “ALARM DIALING EQUIPMENT” MUST BE CONNECTED TO A
PROPERLY INSTALLED RJ31X JACK. THE RJ31X JACK MUST BE CONNECTED IN SERIES WITH, AND AHEAD OF, ALL
OTHER EQUIPMENTATTACHED TO THE SAME PHONE LINE. SERIES INSTALLATION OF AN RJ31X JACK IS DEPICTED
IN THE FIGURE BELOW. IF YOU HAVE ANY QUESTIONS CONCERNING THESE INSTRUCTIONS, CONSULT YOUR
TELEPHONE COMPANY OR A QUALIFIED INSTALLER ABOUT INSTALLING THE NECESSARY JACKAND ALARM
DIALING EQUIPMENT.

14 FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021
Agency Listings, Approvals, and Requirements Underwriters Laboratories (UL)
2.2.6 NFPA Requirements
The following is the minimum configuration to meet the NFPA requirements.
Model/Module Description Local Releasing Remote
Station Auxiliary Central
Station Emergency
Signaling
0067000 Main board YYYYYY
FIK-5496 NAC expander O Y O O O O
5220 Direct connect module NNNYNO
FIK-NIC NetworkcardOOOOOO
FIK-FML/ -FSL Fiber module OOOOOO
Y = YES, N = NO, O = OPTIONAL
Table 2.1 NFPA Requirements for FCP-75

FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021 15
Section 3: Before You Begin Installing
This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly, espe-
cially if you are installing an FCP-75 panel for the first time.
3.1 Inventory
When the FCP-75 shipment is received, check that all the parts have been included in the shipment. The shipment consists of one of each of
the following:
• main circuit board with display
• backbox with door
• plastic bag containing two keys, screws, cables, and ten 4.7K ohm end-of-line resistors
• manual
3.2 Environmental Specifications
It is important to protect the FCP-75 control panel from water. To prevent water damage, the following precautions should be FOLLOWED
when installing the units:
• Intended for indoor use in dry locations only.
• Do not mount directly on exterior walls, especially masonry walls (condensation).
• Do not mount directly on exterior walls below grade (condensation).
• Protect from plumbing leaks.
• Protect from splash caused by sprinkler system inspection ports.
• Do not mount in areas with humidity-generating equipment (such as dryers, production machinery).
When selecting a location to mount the FCP-75 control panel, the unit should be mounted where it will NOT be exposed to temperatures out-
side the range of 0°C-49°C (32°F-120°F) or humidity outside the range of 10%-93% at 30°C (86°F) noncondensing.
3.3 Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades
to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that
you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any
questions about software and the appropriate version for a specific application. The HFSS Programming Tool is available at wwwfike.com.
3.4 Electrical Specifications
Table 3.1 list the terminal block on the FCP-75 as well as a description of the each individual terminal and their respective electrical rating.
For location of the terminals refer to Figure 3.2. See also Section 4 for installation.
Terminal No. Label Description Rating
Group Individual Voltage Current
Terminal Block 3 TELCO 1 RING Phone Line 1 Telco Ring
TIP Phone Line 1 Telco Tip
PHONE 1 RING Phone Line 1 Phone Ring
TIP Phone Line 1 Phone Tip
TELCO 2 RING Phone Line 2 Telco Ring
TIP Phone Line 2 Telco Tip
PHONE 2 RING Phone Line 2 Phone Ring
TIP Phone Line 2 Phone Tip
Terminal Block 2 RELAY 1 NO Normally open relay contact 27.4 VDC 2.5 A, resistive
COM Common terminal
NC Normally closed relay contact
RELAY 2 NO Normally open relay contact 27.4 VDC 2.5 A, resistive
COM Common terminal
NC Normally closed relay contact
TROUBLE NO Normally open relay contact 27.4 VDC 2.5 A, resistive
COM Common terminal
NC Normally closed relay contact
SLC IN – Used for Class A installations 32 VDC 100 mA
+
Table 3.1 Terminal Descriptions and Electrical Specifications

16 FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021
Before You Begin Installing Wiring Specifications
3.5 Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or cause false alarms. To
avoid induced noise, follow these guidelines:
• Isolate input wiring from high current output and power wiring. Do not pull one multi-conductor cable for the entire panel. Instead,
separate the wiring as follows:
• Do not pull wires from different groups through the same conduit. If you must run them together, do so for as short a distance as
possible or use shielded cable. Connect the shield to earth ground at the panel. You must route high and low voltages separately.
• Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it could induce noise into the
sensitive microelectronics or pick up unwanted RF noise from the high speed circuits. See Figure 3.1 for an example.
• High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be reduced by running the wire
through ferrite shield beads or by wrapping it around a ferrite toroid.
Figure 3.1 Wire Routing Example
Terminal Block 2 SLC OUT – SLC terminals 32 VDC 100 mA
+
SLC PROG – Used for programming SLC Detectors 32 VDC 100 mA
+
SBUS – SBUS Power 27.4 VDC 0.5 A
+
A SBUS Communication 5 VDC 100 mA
B
NAC1* – Notification Appliance Circuit/Auxiliary
power 27.4 VDC 1 Amp NAC or Aux power
+
NAC2* – Notification Appliance Circuit/Auxiliary
power 27.4 VDC 1 Amp NAC or Aux power
+
P7 Data Network Used for FIK-NIC 24 VDC 21 mA
Note: Regulated NAC application. When programmed for releasing, NAC are Special Application.
Terminal No. Label Description Rating
Group Individual Voltage Current
Table 3.1 Terminal Descriptions and Electrical Specifications (Continued)
High voltage AC power Terminals
SLC loops
Audio input/output Phone line circuits
Notification circuits NAC1 through NAC2
SBUS
Relay circuits Table 3.2 Wiring Specifications
Relay
NAC / Aux Power
Outputs
SBUS
Phone
SLC IN/OUT
AC Power
Input
Devices
Lines
Outputs
Battery Battery
1/4” spacing must
be maintained
between each of
these circuit types;
as well as between
power-limited and
non-power-limited
circuits.

Board Assembly Diagram Before You Begin Installing
FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021 17
3.6 Board Assembly Diagram
Figure 3.2 Model FCP-75 Assembly
Figure 3.2 shows the circuit boards, and annunciator. If you should need to remove the control board for repair, remove the three mounting
screws which hold the control board in the cabinet. Then lift the control board out of the cabinet.
3.7 Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery needs if you are using IDP addressable devices (Table 3.3).
3.7.1 Current Draw Worksheet Requirements
The following steps must be taken when determining FCP-75 current draw and standby battery requirements.
1. For the FCP-75, the worst case current draw is listed for the panel, addressable devices, and all SBUS expanders. Fill in the number of
addressable devices that will be used in the system and compute the current draw requirements for alarm and standby. Record this
information in the Current Calculation Worksheet at Line A.
2. Add up the current draw for all auxiliary devices and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. For notification appliance circuits and auxiliary devices not mentioned in the manual, refer to the device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the panel itself, does not exceed 2.5A. This is the maximum
alarm current for the FCP-75 control panel.
If the current is above 2.5Ayou will need to use a notification power expander(s) such as the FIK-5496 NAC Expander, to distribute the
power loads so that the FCP-75 or the power expanders do not exceed their power rating. Refer to the current draw worksheets provided
with the FIK-5496 manual so you do not exceed their power requirements.
6. Complete the remaining instructions in the Current Calculation Worksheet for determining battery size requirements.
On-board
Annunciator
NAC/Aux
Power Circuits
Phone Lines SLC In/Out,
SLC Programming
AC Power
Input
SBUS
Connections
Battery
Connector
Program
Port
Form C
Trouble Relay
120 VAC,
60 Hz, 1.5A

18 FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021
Before You Begin Installing Calculating Current Draw and Standby Battery
3.7.2 Current Draw Worksheet for Fike IDP SLC Devices
Use Table 3.3 to determine current requirements during alarm/battery standby operation when SLC devices are installed. You can install up
to 75 IDP detectors and 75 IDP modules1.
Device # of Devices Current per Device Standby
Current Alarm Current
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from battery) 1 Standby: 165 mA 165 mA
Alarm: 310 mA 310 mA
Addressable SLC Detectors
FIK-2351 SLC Standby: 200µA mA
Alarm: 4.5mA mA
FIK-2351R SLC Standby: 200µA mA
Alarm: 4.5mA mA
FIK-2351T SLC Standby: 200µA mA
Alarm: 4.5mA mA
FIK-5351 SLC Standby: 200µA mA
Alarm: 4.5mA mA
FIK-5351R SLC Standby: 200µA mA
Alarm: 4.5mA mA
FIK-5351H SLC Standby: 200µA mA
Alarm: 4.5mA mA
DNR5(non-Relay) None, included with FIK-2351R 6
DNR6(with Relay) None, included with FIK-2351R & FIK-M500R7
Addressable SLC Modules
FIK-M500M Standby/Alarm 0.375 mA mA mA
FIK-M501M mA mA
FIK-PULL-SA/FIK-PULL-DA
FIK-M500DM Standby/Alarm: 0.75mA mA mA
FIK-IM-10 Standby/Alarm: 3.5mA mA mA
FIK-M500S SLC Standby: 0.375mA
Alarm: 0.375mA mA mA
Aux Pwr Standby: 1.7mA mA
Alarm: 7mA mA
FIK-SC-6 SLC Standby: 2.25mA
Alarm: 2.25mA mA mA
Aux Pwr Standby: 8mA mA
Alarm: 20mA mA
FIK-M500R Standby/Alarm: .255mA mA mA
FIK-CR-6 Standby/Alarm: 1.45mA mA mA
FIK-M500MR-2 Standby: 1.3mA mA
Alarm: 24mA mA
FIK-M502M Aux Pwr Standby: 12mA mA mA
Alarm: 90mA mA mA
SLC Standby/Alarm: .27mA mA mA
FIK-CZ-6 Aux Pwr Standby: 50mA mA mA
Alarm: 270mA mA mA
SLC Standby/Alarm: 2mA mA mA
SLC Accessories
B200S-WH / -IV Intelligent sounder base Aux Pwr Standby: .5mA mA
Alarm: (high vol) 35mA mA
SLC Standby .3mA mA
B200S-LF-WH / -IV Low Frequency sounder base Aux Pwr Standby .55mA mA
Alarm (high vol) 140mA mA
SLC Standby .30mA mA
B224RB-WH / -IV Relay Base Standby/Alarm: .5mA mA mA
SLC Isolator Devices
FIK-M500X (100 max.) Standby/Alarm: .45mA mA mA
Color Guide: -IV = Ivory color, -BL = Black, -WH = White, -WHITE-White
Table 3.3 Current Calculation Worksheet for Fike IDP Devices

Calculating Current Draw and Standby Battery Before You Begin Installing
FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021 19
1. Total does not include isolator devices or accessory bases.
2. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during
that time. However, during normal operation, door holders draw current and must be included in the 2.5Atotal alarm current (1.0A
for all other conditions) that can be drawn from the panel.
3. Use next size battery with capacity greater than required.
4. The FIK-2351R is sold separately from the DNR. Current draw for the DNR + FIK-2351R is calculated by increasing the “Number
of Devices” column for each FIK-2351R used with a DNR.
5. The DNR housing does not include a Relay circuit board. If a relay is needed, be sure to add one to the FIK-M500R & FIK-2351R
“Number of Devices” column for each DNR used for correct current calculations.
6. The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
Accessories Modules
FIK-RA2000 Remote LCD Annunciator (8 max.) Standby: 25 mA mA
Alarm: 50 mA mA
FIK-RA100 Remote LCD Annunciator Standby: 20 mA mA
Alarm: 25 mA mA
FIK-RA1000R Remote LCD Annunciator Standby: 20 mA mA
Alarm: 25 mA mA
FIK-5824 Serial / Parallel Module (4 max.) Standby/Alarm: 45mA mA mA
FIK-5496 NAC Expander (8 max.) Standby/Alarm: 10 mA mA mA
FIK-RPS1000 Power Supply Standby/Alarm: 10 mA mA mA
FIK-5865-4 LED Annunciator
(with reset and silence switches) (8 max.) Standby: 35 mA mA
Alarm: 145 mA mA
FIK-5865-3 LED Annunciator Standby: 35 mA mA
Alarm: 145 mA mA
FIK-5880 LED I/O Module Standby: 35 mA mA
Alarm: 200 mA mA
FIK-5883 Relay Interface (32 max.) Standby: 0 mA mA
Alarm: 220 mA
(22 mA per relay) mA
FIK-NIC Network Interface Card (1 Max.) Standby/Alarm: 21 mA mA mA
FIK-FML Fiber Optic Multi Mode (1 Max.) Standby/Alarm: 53 mA mA mA
FIK-FSL Fiber Optic Single Mode (1 Max.) Standby/Alarm: 79 mA mA mA
Wireless Modules
FIK-W-WGI Wireless Gateway Max current using external supply 40 mA mA mA
Max current SLC Power 24 mA mA mA
Total System Current
Auxiliary Devices2Refer to devices manual for current rating.
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Auxiliary Devices Current
Notification Appliance Circuits Refer to device manual for current rating.
Alarm: mA mA
Alarm: mA mA
Alarm: mA mA
Notification Appliances Current mA
Total current ratings of all devices in system (line A + line B + C) mA mA
Total current ratings converted to amperes (line D x.001): A A
Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5): H
Multiply lines E and F. Total standby AH AH
Alarm sounding period in hours. (For example, 5 minutes =.0833 hours) H
Multiply lines E and H. Total alarm AH AH
Add lines G and I. 3AH
Multiply by the Derating Factor x 1.25
Total ampere hours required AH
Device # of Devices Current per Device Standby
Current Alarm Current
Table 3.3 Current Calculation Worksheet for Fike IDP Devices (Continued)

20 FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021
Before You Begin Installing Calculating Current Draw and Standby Battery
Maximum Battery Standby Load
The table below shows the maximum battery standby load for the FCP-75 based on 24 and 60 hours of standby. The standby load calcula-
tions of line D in the Current Draw Calculation Worksheet (Table 3.4) must be less than the number shown in the table below for the battery
size used and standby hours required.
Rechargeable Battery Size Max. Load 24hrs Standby,
5 minutes Alarm *Max. Load for 60hrs Standby,
5 minutes Alarm
7AH 221mA 85mA
18AH 675mA 250mA
33AH 1.1A 450mA
Table 3.4 Maximum Battery Standby Load
NOTE: *Required for NFPA 72 Auxiliary Protected FireAlarm systems for Fire Alarm Service (City Box) and Remote Station Protected Fire
Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter (DACT).
!
WARNING: BATTERIES
FIKE DOES NOT SUPPORT THE USE OF BATTERIES SMALLER THAN THOSE LISTED IN TABLE ABOVE. USING A
BATTERY TOO SMALL FOR THE CONFIGURATION COULD OVERLOAD THE BATTERY, RESULTING IN THE BATTERY
HAVING LESS THAN THE REQUIRED 24 HOURS STANDBY POWER. USE THE CURRENT CALCULATION WORKSHEET
TO CALCULATE THE CORRECT BATTERYAMPERES/HOUR RATING NEEDED FOR THE SYSTEM CONFIGURATION.
Other manuals for FCP-75
1
Table of contents
Other Fike Control Panel manuals

Fike
Fike FCP-75 User manual

Fike
Fike FIK-RA100BD Technical manual

Fike
Fike TWINFLEXpro User manual

Fike
Fike TWINFLEXpro User manual

Fike
Fike SITA200plus User manual

Fike
Fike FCP-2100 User manual

Fike
Fike FIK-RA2000 Technical manual

Fike
Fike CIE-A-200 User manual

Fike
Fike FIK-5496 User manual

Fike
Fike FCP-300 User manual