Fike FCP-2100ECS User manual

B
P/N LS10143-002FK-E:B • ECN 00003636
Document LS10143-002FK-E
6/20/2022
Addressable Fire Alarm Control Panel
FCP-2100/FCP-2100ECS
Manual

2FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control panel (FACP) with remote
notification capability—can provide early warning of a developing fire.
Such a system, however, does not assure protection against property
damage or loss of life resulting from a fire.
An emergency communication system—typically made up of an
automatic fire alarm system (as described above) and a life safety
communication system that may include an autonomous control unit
(ACU), local operating console (LOC), voice communication, and
other various interoperable communication methods—can broadcast
a mass notification message. Such a system, however, does not
assure protection against property damage or loss of life resulting
from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors be
located throughout a protected premises following the
recommendations of the current edition of the National Fire Protection
Association Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the recommendations
contained in the Guide for Proper Use of System Smoke Detectors,
which is made available at no charge to all installing dealers. This
document can be found at http://www.systemsensor.com/appguides/.
A study by the Federal Emergency ManagementAgency (an agency
of the United States government) indicated that smoke detectors may
not go off in as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not guarantee
warning or protection against fire. A fire alarm system may not
provide timely or adequate warning, or simply may not function, for a
variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the
detectors such as in chimneys, in or behind walls, on roofs, or on the
other side of closed doors. Smoke detectors also may not sense a fire
on another level or floor of a building.A second-floor detector, for
example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not
reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chimneys,
even wet or humid areas may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the
ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets,
such as air conditioning vents.
• Smoke particles may be drawn into air returns before reaching the
detector.
The amount of “smoke” present may be insufficient to alarm smoke
detectors. Smoke detectors are designed to alarm at various levels of
smoke density. If such density levels are not created by a developing
fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing chambers
tend to detect smoldering fires better than flaming fires, which have
little visible smoke. Detectors that have ionizing-type sensing
chambers tend to detect fast-flaming fires better than smoldering
fires. Because fires develop in different ways and are often
unpredictable in their growth, neither type of detector is necessarily
best and a given type of detector may not provide adequate warning
of a fire.
Smoke detectors cannot be expected to provide adequate warning of
fires caused by arson, children playing with matches (especially in
bedrooms), smoking in bed, and violent explosions (caused by
escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only
when heat on their sensors increases at a predetermined rate or
reaches a predetermined level. Rate-of-rise heat detectors may be
subject to reduced sensitivity over time. For this reason, the rate-of-
rise feature of each detector should be tested at least once per year
by a qualifiedfire protection specialist. Heat detectors are designed to
protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room
as the control panel and in rooms used by the system for the
connection of alarm transmission wiring, communications, signaling,
and/or power. If detectors are not so located, a developing fire may
damage the alarm system, compromising its ability to report a fire.
Audible warning devices such as bells, horns, strobes, speakers
and displays may not alert people if these devices are located on the
other side of closed or partly open doors or are located on another
floor of a building.Any warning device may fail to alert people with a
disability or those who have recently consumed drugs, alcohol, or
medication. Please note that:
• An emergency communication system may take priority over a fire
alarm system in the event of a life safety emergency.
• Voice messaging systems must be designed to meet intelligibility
requirements as defined by NFPA, local codes, and Authorities
Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dissemi-
nated on any local displays.
• Strobes can, under certain circumstances, cause seizures in peo-
ple with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a
fire alarm signal, do not respond to or comprehend the meaning of
the signal.Audible devices, such as horns and bells, can have dif-
ferent tonal patterns and frequencies. It is the property owner's
responsibility to conduct fire drills and other training exercises to
make people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause
temporary or permanent hearing loss.
A life safety system will not operate without any electrical power. If
AC power fails, the system will operate fromstandbybatteriesonly for
a specified time and only if the batteries have been properly
maintained and replaced regularly.
Equipment used in the system may not be technically compatible
with the control panel. It is essential to use only equipment listed for
service with your control panel.
Alarm Signaling Communications:
•IP connections rely on available bandwidth, which could be lim-
ited if the network is shared by multiple users or if ISP policies
impose restrictions on the amount of data transmitted. Service
packages must be carefully chosen to ensure that alarm signals
will always have available bandwidth. Outages by the ISP for
maintenance and upgrades may also inhibit alarm signals. For
added protection, a backup cellular connection is recommended.
•Cellular connections rely on a strong signal. Signal strength can
be adversely affected by the network coverage of the cellular car-
rier, objects and structural barriers at the installation location. Uti-
lize a cellular carrier that has reliable network coverage where the
alarm system is installed. For added protection, utilize an external
antenna to boost the signal.
•Telephone lines needed to transmit alarm signals from a premise
to a central monitoring station may be out of service or temporarily
disabled. For added protection against telephone line failure,
backup alarm signaling connections are recommended.
The most common cause of life safety system malfunction is
inadequate maintenance. To keep the entire life safety system in
excellent working order, ongoing maintenance is required per the
manufacturer's recommendations, and UL and NFPA standards. At a
minimum, the requirements of NFPA 72 shall be followed.
Environments with large amounts of dust, dirt, or high air velocity
require more frequent maintenance. A maintenance agreement
should be arranged through the local manufacturer's representative.
Maintenance should be scheduled as required by National and/or
local fire codes and should be performed by authorized professional
life safety system installers only.Adequate written records of all
inspections should be kept. Limit-F-2020

FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be con-
nected to the fire alarm control panel. Disconnect all sources of
power before servicing. Control unit and associated equipment may
be damaged by removing and/or inserting cards, modules, or inter-
connecting cables while the unit is energized. Do not attempt to
install, service, or operate this unit until manuals are read and under-
stood.
CAUTION - System Re-acceptance Test after Software Changes:
To ensure proper system operation, this product must be tested in
accordance with NFPA 72 after any programming operation or
change in site-specific software. Re-acceptance testing is required
after any change, addition or deletion of system components, or after
any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions
known to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected, at least
10% of initiating devices that are not directly affected by the change,
up to a maximum of 50 devices, must also be tested and proper sys-
tem operation verified.
This system meets NFPArequirements for operation at 0-49º C/32-
120º F and at a relative humidity 93% ± 2% RH (non-condensing) at
32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's
standby batteries and the electronic components may be adversely
affected by extreme temperature ranges and humidity. Therefore, it is
recommended that this system and its peripherals be installed in an
environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indicating
device loops. Most devices cannot tolerate more than a10% I.R. drop
from the specified device voltage.
Like all solid state electronic devices, this system may operate
erratically or can be damaged when subjected to lightning induced
transients. Although no system is completely immune from lightning
transients and interference, proper grounding will reduce susceptibil-
ity. Overhead or outside aerial wiring is not recommended, due to an
increased susceptibility to nearby lightning strikes. Consult with the
Technical Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting
circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, ream-
ing, or punching of the enclosure. When possible, make all cable
entries from the sides or rear. Before making modifications, verify that
they will not interfere with battery, transformer, or printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening
may damage threads, resulting in reduced terminal contact pressure
and difficulty with screw terminal removal.
This system contains static-sensitive components. Always
ground yourself with a proper wrist strap before handling any circuits
so that static charges are removed from the body. Use static suppres-
sive packaging to protect electronic assemblies removed from the
unit.
Units with a touchscreen display should be cleaned with a dry,
clean, lint free/microfiber cloth. If additional cleaning is required,
apply a small amount of Isopropyl alcohol to the cloth and wipe
clean. Do not use detergents, solvents, or water for cleaning. Do not
spray liquid directly onto the display.
Follow the instructions in the installation, operating, and program-
ming manuals. These instructions must be followed to avoid damage
to the control panel and associated equipment. FACP operation and
reliability depend upon proper installation.
Precau-D2-11-2017
FCC Warning
WARNING: This equipment generates, uses, and can radi-
ate radio frequency energy and if not installed and used in
accordance with the instruction manual may cause interfer-
ence to radio communications. It has been tested and found
to comply with the limits for classA computing devices pur-
suant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against such
interference when devices are operated in a commercial
environment. Operation of this equipment in a residential
area is likely to cause interference, in which case the user
will be required to correct the interference at his or her own
expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for
radiation noise emissions from digital apparatus set out in
the Radio Interference Regulations of the Canadian Depart-
ment of Communications.
Le present appareil numerique n'emet pas de bruits radio-
electriques depassant les limites applicables aux appareils
numeriques de la classeAprescrites dans le Reglement sur
le brouillage radioelectrique edicte par le ministere des
Communications du Canada.
Flexput®, Honeywell®, JumpStart®, and SWIFT® are registered trademarks of Honeywell International Inc.Microsoft® and Windows® are registered trademarks of the
Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered trademark of The Mozilla Foundation.
©2022. All rights reserved. Unauthorized use of this document is strictly prohibited.

4FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent
upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly
recommend that you download the most current version of software for each product prior to commissioning any system. Contact
Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online
Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
or call (800)979-3453, x21 in US or (816)229-3405 international
This symbol (shown left) on the product(s) and / or accompanying documents means that used electrical and electronic products
should not be mixed with general household waste. For proper treatment, recovery and recycling, contact your local authorities or
dealer and ask for the correct method of disposal.
Electrical and electronic equipment contains materials, parts and substances, which can be dangerous to the environment and harmful
to human health if the waste of electrical and electronic equipment (WEEE) is not disposed of correctly.

FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022 5
Table of Contents
Section 1: Introduction ................................................................................................................................................... 10
1.1: Basic System Overview...................................................................................................................................................................................10
1.1.1: Hardware Features................................................................................................................................................................................10
1.1.2: Network System Hardware Features ....................................................................................................................................................10
1.1.3: Software Features .................................................................................................................................................................................10
1.1.4: FCP-2100ECS Features........................................................................................................................................................................11
1.2: Terms Used in this Manual..............................................................................................................................................................................11
1.3: Compatible Products........................................................................................................................................................................................12
1.4: Related Documentation ...................................................................................................................................................................................13
Section 2: Agency Listings, Approvals, and Requirements........................................................................................ 14
2.1: Federal Communications Commission (FCC).................................................................................................................................................14
2.2: Underwriters Laboratories (UL)......................................................................................................................................................................15
2.2.1: Requirements for All Installations........................................................................................................................................................15
2.2.2: UL 864 9th and 10th Edition ................................................................................................................................................................15
2.2.3: Requirements for Central Station Fire Alarm Systems ........................................................................................................................15
2.2.4: Requirements for Local Protected Fire Alarm Systems .......................................................................................................................15
2.2.5: Requirements for Remote Station Protected Fire Alarm Systems........................................................................................................15
2.2.6: Requirements for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, NFPA 720..................................15
2.2.7: NFPA Requirements.............................................................................................................................................................................16
Section 3: Before You Begin Installation ...................................................................................................................... 18
3.1: Inventory..........................................................................................................................................................................................................18
3.2: Environmental Specifications..........................................................................................................................................................................18
3.3: Software Downloads........................................................................................................................................................................................18
3.4: Electrical Specifications ..................................................................................................................................................................................18
3.5: Calculating Current Draw and Standby Battery ..............................................................................................................................................20
3.5.1: Current Draw Worksheet Requirements...............................................................................................................................................20
3.5.2: Current Draw Worksheet for Fike SLC Devices..................................................................................................................................20
3.5.3: Maximum Battery Standby Load..........................................................................................................................................................24
Section 4: Control Panel Installation............................................................................................................................. 25
4.1: Mounting the Control Panel Cabinet...............................................................................................................................................................25
4.1.1: Preventing Water Damage....................................................................................................................................................................25
4.1.2: Removing the FCP-2100 Assembly from the Housing........................................................................................................................25
4.1.3: Ethernet Connection .............................................................................................................................................................................25
4.2: Board Assembly Diagram................................................................................................................................................................................26
4.3: Wiring Specifications.......................................................................................................................................................................................27
4.4: AC Power Connection .....................................................................................................................................................................................28
4.5: Battery Power ..................................................................................................................................................................................................29
4.5.1: Battery Accessory Cabinets..................................................................................................................................................................29
4.6: SBUS Wiring ...................................................................................................................................................................................................31
4.6.1: Calculating Wiring Distance for SBUS Modules.................................................................................................................................31
4.6.2: Wiring Configurations..........................................................................................................................................................................33
4.7: FIK-RA100 Remote Annunciator Installation.................................................................................................................................................33
4.7.1: Mounting the FIK-RA100 ....................................................................................................................................................................34
4.7.2: FIK-RA100 Connection to the Panel....................................................................................................................................................36
4.8: FIK-RA1000R Remote Annunciator Installation............................................................................................................................................36
4.8.1: Mounting the FIK-RA1000R................................................................................................................................................................36
4.9: FIK-RA2000 Remote Annunciator Installation...............................................................................................................................................39
4.9.1: Mounting the FIK-RA2000 ..................................................................................................................................................................40
4.9.2: FIK-RA2000 Connection to the Panel..................................................................................................................................................41
4.10: Temporary Programming Display .................................................................................................................................................................41
4.11: FIK-6815 Installation.....................................................................................................................................................................................41
4.11.1: FIK-6815 Connection to the Panel .....................................................................................................................................................42
4.12: FIK-5824 Serial/Parallel Interface Module Installation ................................................................................................................................42
4.12.1: Selecting FIK-5824 Options...............................................................................................................................................................43
4.13: FIK-5880 LED I/O Module...........................................................................................................................................................................43
4.13.1: FIK-5880 Board Layout .....................................................................................................................................................................44
4.13.2: FACP Connection...............................................................................................................................................................................44
4.13.3: LED Wiring ........................................................................................................................................................................................44
4.13.4: Dry Contact Wiring ............................................................................................................................................................................45

6FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022
Table of Contents
4.14: FIK-5865-3 / FIK-5865-4 LED Annunciator Installation .............................................................................................................................45
4.14.1: FACP Connection...............................................................................................................................................................................46
4.14.2: FIK-5865 Mounting............................................................................................................................................................................47
4.15: Configuring SBUS Modules..........................................................................................................................................................................47
4.15.1: Assigning SBUS Module IDs.............................................................................................................................................................47
4.15.2: SBUS Bandwidth Considerations.......................................................................................................................................................48
4.16: Telephone Connection ...................................................................................................................................................................................48
4.17: Flexput I/O Circuits.......................................................................................................................................................................................49
4.17.1: Conventional Notification Appliance.................................................................................................................................................49
4.17.2: Conventional Input Switch Circuits....................................................................................................................................................50
4.17.3: Installing 2-Wire Smoke Detectors ....................................................................................................................................................51
4.17.4: Installing 4-Wire Smoke Detectors ....................................................................................................................................................52
4.17.5: Auxiliary Power Installation...............................................................................................................................................................53
4.18: Onboard Relays (Conventional) ....................................................................................................................................................................54
4.18.1: Trouble Relay .....................................................................................................................................................................................54
4.18.2: Programmable Relays.........................................................................................................................................................................54
4.19: Remote Station Applications .........................................................................................................................................................................54
4.19.1: Keltron Model 3158 Installation.........................................................................................................................................................54
4.19.2: City Box Connection Using the 5220 Module ...................................................................................................................................55
4.19.3: Using the Addressable Relay Module for City Box Connection........................................................................................................56
4.19.4: NFPA 72 Polarity Reversal ................................................................................................................................................................56
4.19.5: Transmitter Activated by Dry Contacts..............................................................................................................................................57
Section 5: Networking..................................................................................................................................................... 58
5.1: Network System Hardware Features ...............................................................................................................................................................58
5.1.1: Networked Sites....................................................................................................................................................................................58
5.1.2: Wiring Options to Connect Networked Panels.....................................................................................................................................58
5.2: Model RFCP-2100...........................................................................................................................................................................................58
5.3: Network Wiring ...............................................................................................................................................................................................58
5.4: FIK-NIC Wiring Options.................................................................................................................................................................................59
5.4.1: Fiber Loop Modules .............................................................................................................................................................................59
5.4.2: FIK-NIC Installation.............................................................................................................................................................................60
5.4.3: FIK-NIC Remote Mounting .................................................................................................................................................................61
5.4.4: Wiring...................................................................................................................................................................................................61
5.5: Setting the Network ID for Each Panel ...........................................................................................................................................................63
Section 6: Network Management................................................................................................................................... 64
6.1: Network Diagnostics .......................................................................................................................................................................................64
6.1.1: Ping Panel.............................................................................................................................................................................................64
6.1.2: Data Network Status.............................................................................................................................................................................64
6.1.3: Voice Network Status...........................................................................................................................................................................64
6.2: Network Programming ....................................................................................................................................................................................64
6.2.1: Learn Network......................................................................................................................................................................................64
6.2.2: Edit Network Names.............................................................................................................................................................................64
6.2.3: Edit Panel ID.........................................................................................................................................................................................65
6.2.4: Computer Access..................................................................................................................................................................................65
6.2.5: Access Codes........................................................................................................................................................................................65
6.2.6: Communicator Options.........................................................................................................................................................................65
6.3: Voice Options...................................................................................................................................................................................................67
6.3.1: Edit Timers ...........................................................................................................................................................................................67
6.3.2: Edit Voice Commands..........................................................................................................................................................................67
6.4: Sync Network Options.....................................................................................................................................................................................68
6.5: Network Management Quick Reference .........................................................................................................................................................69
Section 7: Programming Overview................................................................................................................................ 71
7.1: JumpStart Auto-Programming.........................................................................................................................................................................71
7.1.1: Input Points...........................................................................................................................................................................................71
7.1.2: Output Points ........................................................................................................................................................................................71
7.1.3: Running JumpStart Auto-Programming...............................................................................................................................................71
7.2: Mapping Overview ..........................................................................................................................................................................................72
7.2.1: Input Point Mapping.............................................................................................................................................................................73
7.2.2: Output Circuit Mapping........................................................................................................................................................................73
7.2.3: Event Mapping.....................................................................................................................................................................................74

FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022 7
Table of Contents
7.2.4: Mapping LED Points............................................................................................................................................................................76
7.2.5: Mapping LED Points for a Networked System....................................................................................................................................76
7.3: Programming Using the HFSS Software Suite................................................................................................................................................76
7.4: Programming Using an Annunciator ...............................................................................................................................................................77
7.4.1: Entering / Exiting Panel Programming.................................................................................................................................................77
7.5: Programming Menu Quick Reference.............................................................................................................................................................78
Section 8: Programming................................................................................................................................................. 88
8.1: UL 864 / UL 2572 Programming Requirements..............................................................................................................................................88
8.2: Modules ...........................................................................................................................................................................................................88
8.2.1: Edit Modules.........................................................................................................................................................................................88
8.2.2: Adding a Module..................................................................................................................................................................................89
8.2.3: Deleting a Module ................................................................................................................................................................................89
8.2.4: View Module List.................................................................................................................................................................................89
8.3: Zone.................................................................................................................................................................................................................90
8.3.1: Edit Zone ..............................................................................................................................................................................................90
8.3.2: View Zone Points .................................................................................................................................................................................92
8.4: Group...............................................................................................................................................................................................................92
8.4.1: Edit Group ............................................................................................................................................................................................92
8.4.2: View Group Points ...............................................................................................................................................................................93
8.4.3: Edit OPG Template...............................................................................................................................................................................93
8.5: Point.................................................................................................................................................................................................................94
8.5.1: Point Programming For FIK-6815 Module..........................................................................................................................................94
8.5.2: Point Programming For Internal or External Power Module (FIK-RPS1000).....................................................................................97
8.5.3: Point Programming for FIK-5880/FIK-5865 Modules.........................................................................................................................98
8.5.4: Point Programming for the FIK-5496...................................................................................................................................................99
8.5.5: Point Programming for ECS Amplifiers...............................................................................................................................................99
8.5.6: Point Programming for FIK-NVCM and FIK-RVM............................................................................................................................99
8.6: System Options..............................................................................................................................................................................................101
8.6.1: Communication Options.....................................................................................................................................................................101
8.6.2: Daytime/Nighttime Sensitivity...........................................................................................................................................................104
8.6.3: Holiday Days ......................................................................................................................................................................................104
8.6.4: Time Options ......................................................................................................................................................................................104
8.6.5: Miscellaneous Options........................................................................................................................................................................105
8.6.6: Daylight Saving Options.....................................................................................................................................................................106
8.6.7: Edit Banner.........................................................................................................................................................................................106
8.6.8: SLC Family.........................................................................................................................................................................................106
8.6.9: JumpStart Auto-Programming............................................................................................................................................................106
8.7: Restore Defaults.............................................................................................................................................................................................107
8.8: Voice Options.................................................................................................................................................................................................107
8.8.1: VCM Maintenance..............................................................................................................................................................................107
8.8.2: Voice Settings.....................................................................................................................................................................................107
Section 9: System Operation........................................................................................................................................ 108
9.1: Annunciator Description................................................................................................................................................................................108
9.1.1: LCD Display.......................................................................................................................................................................................108
9.1.2: Banner.................................................................................................................................................................................................108
9.2: Menu System ................................................................................................................................................................................................109
9.2.1: Panel Login Menu...............................................................................................................................................................................109
9.2.2: Main Menu Overview.........................................................................................................................................................................110
9.2.3: Using the Menus.................................................................................................................................................................................111
9.3: Basic Operation .............................................................................................................................................................................................111
9.3.1: Setting Time and Date ........................................................................................................................................................................111
9.3.2: Disable / Enable a Point......................................................................................................................................................................111
9.3.3: View Event History ............................................................................................................................................................................111
9.3.4: Conduct a Fire Drill............................................................................................................................................................................112
9.3.5: Conduct an Indicator Test...................................................................................................................................................................112
9.3.6: Conduct a Walk Test ..........................................................................................................................................................................112
9.3.7: Conduct a Communicator Test...........................................................................................................................................................112
9.3.8: Manual AlarmNet Registration...........................................................................................................................................................112
9.3.9: Silence Alarms or Troubles................................................................................................................................................................113
9.3.10: Reset Alarms.....................................................................................................................................................................................113
9.3.11: Check Detector Sensitivity Through Point Status...........................................................................................................................113

8FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022
Table of Contents
9.3.12: View Status of a Point ......................................................................................................................................................................114
9.3.13: View Alarms or Troubles .................................................................................................................................................................114
9.3.14: System Information .........................................................................................................................................................................114
9.4: Event Priority.................................................................................................................................................................................................115
9.4.1: System Control ...................................................................................................................................................................................115
9.4.2: System Override .................................................................................................................................................................................115
9.4.3: Event Priority......................................................................................................................................................................................115
9.4.4: Priority Rules......................................................................................................................................................................................116
9.4.5: Other Priority Considerations.............................................................................................................................................................116
9.5: Operation Mode Behavior .............................................................................................................................................................................116
9.5.1: Multi-Site Annunciator and Multi-Site User Access..........................................................................................................................119
9.6: Releasing Operations.....................................................................................................................................................................................119
9.6.1: Single Interlock Zone Releasing.........................................................................................................................................................120
9.6.2: Double Interlock Zone Releasing.......................................................................................................................................................120
9.7: Smoke Alarm Verification .............................................................................................................................................................................121
9.8: Function Keys...............................................................................................................................................................................................121
9.8.1: Recording an F-Key Macro ................................................................................................................................................................121
9.8.2: Aborting an F-Key Macro Recording Session....................................................................................................................................121
9.8.3: Erasing an F-Key Macro.....................................................................................................................................................................121
9.8.4: Using a Recorded F-Key Macro.........................................................................................................................................................122
9.8.5: F-Key Status Event.............................................................................................................................................................................122
9.8.6: F-Key Map Inhibit..............................................................................................................................................................................122
Section 10: Emergency Communication System Operation..................................................................................... 123
10.1: Overview......................................................................................................................................................................................................123
10.2: LOC Functionality.......................................................................................................................................................................................123
10.2.1: Keys and LEDs.................................................................................................................................................................................123
10.2.2: Gaining ECS Control........................................................................................................................................................................124
10.2.3: Manual ECS......................................................................................................................................................................................125
10.2.4: Fire Page Mode.................................................................................................................................................................................125
10.2.5: Message Mode..................................................................................................................................................................................125
10.2.6: Custom ECS Event ...........................................................................................................................................................................126
10.2.7: Passing ECS Control.........................................................................................................................................................................126
10.2.8: Exit ECS Control Menu....................................................................................................................................................................126
10.2.9: Relinquish ECS Control ...................................................................................................................................................................127
10.2.10: ECS Reset .......................................................................................................................................................................................127
10.3: ECS Super User ...........................................................................................................................................................................................127
10.4: ECS Point Functionality ..............................................................................................................................................................................127
10.4.1: ECS Point Activations......................................................................................................................................................................127
10.4.2: FIK-NVCM and FIK-RVM Points...................................................................................................................................................127
10.5: Amplifier Programming...............................................................................................................................................................................127
10.5.1: Adding an Amplifier.........................................................................................................................................................................127
10.5.2: Editing an Amplifier.........................................................................................................................................................................128
10.6: LOC Programming ......................................................................................................................................................................................128
10.6.1: Adding an LOC.................................................................................................................................................................................128
10.6.2: Editing an LOC.................................................................................................................................................................................128
10.7: Using the Microphone .................................................................................................................................................................................129
10.7.1: Microphone Functionality ................................................................................................................................................................129
10.7.2: Custom ECS Event ...........................................................................................................................................................................129
10.7.3: Fire Page...........................................................................................................................................................................................129
10.7.4: Emergency Page ...............................................................................................................................................................................129
10.7.5: Paging ...............................................................................................................................................................................................129
10.8: Recording Custom Messages.......................................................................................................................................................................130
10.8.1: Recording Messages 1-15 Using Aux Audio Input..........................................................................................................................130
10.8.2: Recording Messages 1-15 Using the Microphone............................................................................................................................131
10.8.3: Erasing User Message.......................................................................................................................................................................132
10.8.4: Using HFSS Voice Message Load Software....................................................................................................................................132
10.9: Network Paging ...........................................................................................................................................................................................133
10.9.1: Priority..............................................................................................................................................................................................133
10.9.2: Configuration....................................................................................................................................................................................133
Section 11: Reporting ................................................................................................................................................... 134
11.1: Receivers Compatible with the Control Panel.............................................................................................................................................134

FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022 9
Table of Contents
11.2: SIA - Panel PI Modifier Reporting ..............................................................................................................................................................143
11.3: SIA – Panel Communicator .........................................................................................................................................................................144
Section 12: Testing and Troubleshooting................................................................................................................... 145
12.1: Troubleshooting...........................................................................................................................................................................................145
12.1.1: Common Problems ...........................................................................................................................................................................145
12.2: Periodic Testing and Maintenance...............................................................................................................................................................145
12.3: Event History...............................................................................................................................................................................................146
12.4: Built-in Troubleshooting and Testing Tools ................................................................................................................................................146
12.4.1: SLC Device Locater .........................................................................................................................................................................146
12.4.2: SLC Multiple Device Locater...........................................................................................................................................................146
12.4.3: I/O Point Control ..............................................................................................................................................................................147
12.4.4: Earth Fault Resistance ......................................................................................................................................................................147
Section 13: Installation Records.................................................................................................................................. 149
13.1: Detector and Module Point Record .............................................................................................................................................................149
13.2: Additional SLC Devices ..............................................................................................................................................................................151
13.3: Conventional Output Point Record..............................................................................................................................................................152
Appendix A: Editing Text Using the Built-In Programmer......................................................................................... 153
A.1: Characters Used for Editing Text..................................................................................................................................................................153
A.2: Example Name Edit......................................................................................................................................................................................153
Appendix B: Expanded Receiver/Panel Relationship................................................................................................ 154
Appendix C: Cadence Patterns.................................................................................................................................... 155
Appendix D: Panel Security.......................................................................................................................................... 156
Model FCP-2100 Basic Operating Instructions........................................................................................................... 157
Model FCP-2100ECS Basic Operating Instructions................................................................................................... 159
Keypad and LED Indicators.......................................................................................................................................... 161
ECS Control ................................................................................................................................................................... 163

10 FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022
Section 1: Introduction
The FCP-2100, FCP-2100HV, FCP-2100ECS, and FCP-2100ECSHV are analog addressable fire alarm control panels (FACP), that meets
the requirements of UL 864. The FCP-2100ECS and FCP-2100ECSHVanalog addressable fire control system combined with an Emergency
Communication System that meet the requirements for Mass Notification as described in UL 864 and UL 2572.
The RFCP-2100 is the same as the FCP-2100 without the display. The RFCP-2100 is used in a networked system where there is at least one
FCP-2100 in the system. When using the RFCP-2100 as a standalone local unit, one LCD annunciator must be connected and the annuncia-
tor must be wired in conduit within 20’of the RFCP-2100.
1.1 Basic System Overview
The FCP-2100 base system is packaged as an assembled stack of 3 circuit boards mounted to an aluminum housing.
1.1.1 Hardware Features
• The basic FCP-2100 panel contains one built-in signaling line circuit (SLC), which supports up to 159 sensors and 159 modules.
Additional SLC loops can be added to increase overall point capacity.
• Additional FIK-6815 SLC expanders supports 159 sensors and 159 modules for a maximum of 2,100 points per FCP-2100 control
panel.
• 9.0A of output power is available through 8 sets of terminals for notification and auxiliary applications. Each circuit is power limited
per UL 864 and can source up to 3.0A (total output power must not exceed 9.0A). The constant auxiliary power load must not exceed
6.0A for normal standby.
• Built-in dual phone line, digital alarm communicator/transmitter (DACT), or IP technologies
• Reports events to central station by point or by zone
• UL-Listed for pre-action and deluge releasing systems
• Dedicated Form C trouble relay and two general purpose Form C programmable relays
• Can be used with up to 31 FIK-RA2000, FIK-RA1000R, or FIK-RA100 remote annunciators in any combination
• Supports the FIK-5865-3, FIK-5865-4, and FIK-5880 LED annunciators1. See Section 4.13 and Section 4.14 for additional information
on these models.
• Printing of event log available through the FIK-58241serial/parallel printer interface module
• Supports conventional 2-wire & 4-wire detectors using the 8 Flexput circuits or SLC zone modules
• Add four notification/auxiliary power circuits with each FIK-5496 Intelligent Power Module
• Add six Flexput circuits with each FIK-RPS1000 Remote Power Supply
1. The system supports a maximum of 63 SBUS devices in any combination.
1.1.2 Network System Hardware Features
• The default network setup can contain up to 32- FCP-2100 panels connected.
• Network support for up to 32 sites
• Each building is referred to as a “site”.
• Panels can be interconnected using CLASS B or CLASS A topology.
• Use the FIK-NIC network card to network panels together. Copper wire or fiber-optic cable panel connectivity can be used within the
same networked system.
• The network architecture provides true peer to peer capability allowing network survivability for all hardware that remains operational
in the event of partial system failure.
1.1.3 Software Features
• 999 software zones, 999 output groups
• Advanced analog smoke detector features:
– Three sensitivity settings (high, medium, low)
– Automatic drift compensation
– Maintenance alert region
– Point status meets calibrated smoke test requirements for NFPA 72
– Automatic day/night sensitivity adjustment
• “JumpStart AutoProgramming” feature for easy programming
• Non-volatile event history stores 1000 events per panel
• A choice of output patterns available for notification outputs, includingANSI 3.41 temporal signal
• Built-in synchronization appliance support for AMSECO®, Gentex®, System Sensor®, and Wheelock®
NOTE: All references to the FCP-2100 within this manual are applicable to the FCP-2100, FCP-2100HV, FCP-2100ECS, FCP-2100ECSHV,
RFCP-2100, and RFCP-2100HV unless otherwise indicated.

FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022 11
Terms Used in this Manual Introduction
1.1.4 FCP-2100ECS Features
• 15 recordable, one-minute messages that can be mapped to eight ECS buttons
• ECS messages can be selected as priority over fire
• Support of up to 15 FIK-LOC2100 Local Operator Consoles
• Programmable trigger inputs from an external source, such as a Monaco system, to either the FIK-NVCM, FIK-RVM, FIK-5880, any
SLC input module, or Flexput module
• Support for up to 16 SBUS addressable amplifiers using a combination of FIK-50W, FIK-125W, FIK-INT50W, or FIK-DUAL50W for
a maximum of 2,000 watts per system and up to 128 mappable speaker circuits
• Support for dual channel and backup audio using the FIK-DUAL50W amplifier and FIK-50WBU back-up amplifier
• Single enclosure for both Fire and Emergency Control System components
• Support for one FIK-NVCM
• Onboard supervised microphone
1.2 Terms Used in this Manual
The following terminology is used with the above mentioned control panels:
Term Description
SLC Signaling line circuit
Module The term module is used for all hardware devices except for SLC addressable devices and notification appliances.
This includes the FCP-2100 panel itself and the built-in power supply. It also refers to any (optional) FIK-6815 SLC
expansion modules.
Input Point An addressable sensing device, such as a smoke or heat detector or a contact monitor device
Input Zone A protected area made up of input points
Output Point (or “Output Circuit”) A notification point or circuit for notification appliances. Relay circuits and auxiliary power circuits are also
considered output points
Group (“Output Group” or OPG) A group of output points. Operating characteristics are common to all output points in a group.
Output (or “Cadence”) Pattern The pattern that the output will use, for example, Constant, March Code, ANSI 3.41. Applies to zones and special
system events. See Appendix B for additional information.
Mapping Mapping is the process of specifying which outputs are activated when certain events occur in the system.
Section 7.2 explains mapping in detail.
Networking Up to 32 panels can be networked.
Network System Consist of any combination of 32 panels of these model numbers: FCP-75, FCP-300, FCP-300ECS,FCP-2100,
FCP-2100ECS, and RFCP-2100
ECS Emergency Communication System
SWIFT Smart Wireless Integrated Fire Technology

12 FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022
Introduction Compatible Products
1.3 Compatible Products
Table 1.1 lists the products available for use with the FCP-2100.
Type of Device Model Description
Addressable SLC Devices Refer to the Device Compatibility Document and SLC Wiring Manual for a list of compatible devices.
SWIFT Wireless SLC Devices Refer to the SWIFT Wireless Manual for a list of compatible devices.
Other Modules FIK-5824 Serial/Parallel
Printer Interface Module Allows a printer to be attached for the system for on-site logging. Four maximum
per system.
FIK-6815 SLC EXPANDER Each FIK-6815 supports up to 159 sensors and 159 modules. The maximum point
count for Fike IDP devices is limited to 2,100 per panel. The FIK-6815 supports
System Sensor devices only.
RFCP-2100 Remote Fire
Panel without display Same operation as FCP-2100 without display
FIK-RPS1000 Intelligent
Power Module Provides additional power, six Flexput circuits, and two Form C relays.
FIK-5496 NAC Expander Provides four additional Notification Appliance Circuits/Auxiliary power.
FIK-RA2000 LCD Alarm
Annunciator 4x40 LCD annunciator. Same operation, similar appearance as onboard
annunciator.Any combination of supported annunciators for a max of 63.
FIK-RA1000R LCD Alarm
Annunciator 4x20 LCD annunciator. Any combination of supported annunciators for a max of
31.
FIK-RA100 LCD Alarm
Annunciator 4x20 LCD annunciator. Any combination of supported annunciators for a max of
31.
5860TR Trim Ring Kits for
FIK-RA1000R Trim ring kit for surface mounting the 5860 annunciator.
FIK-5865-3and FIK-5865-4
LED Annunciators LED annunciator can display up to 30 LEDs (15 red and 15 yellow). FIK-5865-4
has key switches for silence and reset, and a system trouble LED.
FIK-5880 LED I/O Module Driver for up to 40 LEDs. Interfaces with customized annunciator boards. In
addition, the FIK-5880 has eight generic switch input points.
FIK-5883 General Purpose
Relay Module Provides 10 Form C relays. Designed to be driven by the FIK-5880. Up to four FIK-
5883s can be used with each FIK-5880 module.
Audio Devices
(for FCP-2100ECS only) FIK-SW24 24 Switch expander Refer to the FikeECS Series
Installation Manual PN
LS10262-001FK-E for more
info on these accessories.
FIK-NVCM Network Voice Control Module
FIK-50W 50 watt audio amplifier
FIK-125W 125 watt audio amplifier
FIK-INT50W 50 watt internal amplifier
FIK-DUAL50W Dual Channel amplifier
FIK-50WBU Backup daughter card
FIK-CE4 Provides 4 additional audio circuits for the FIK-
50W or the FIK-125W
FIK-RVM Remote Voice Microphone
FIK-LOC2100 Local Operating Console
Networking FIK-NIC Network Interface Card Refer to LS10172-002FK-E
FIK-FML Fiber-Optic Multi Mode, Receiver Refer to LS10178-002FK-E
FIK-FSL Fiber-Optic Single Mode, Transmitter
Wireless FIK-W-WGI Wireless Gateway Refer to the SWIFT wireless
Installation Manual P/N
LS10036-000FK-E for more
information on these
accessories.
FIK-W--PHOTO Wireless Photoelectric Smoke Detector
FIK-W-ACCLIMATE Wireless Multi criteria photoelectric smoke
detector with thermal (135°F)
FIK-W-HEAT-ROR Wireless Heat Rate of Rise Heat Detector
FIK-W-HEAT Wireless 135° fixed Heat Detector
FIK-W-MONITOR Wireless Addressable Monitor module
FIK-W-RELAY Wireless Addressable Relay module
B210W 6" wireless base
Table 1.1 FCP-2100 Compatible Products

FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022 13
Related Documentation Introduction
1.4 Related Documentation
Refer to the following documents for more information.
Miscellaneous 7860 Telephone Cord RJ31X cord for connecting phone line to the FCP-2100
HFSS Software Suite For communication and panel programming with a Windows-based computer.
Enables remote viewing of detector status and event history.
RBB Remote Battery Box for mounting backup batteries up to 35AH that are too large to
fit into the main control panel cabinet. Dimensions: 16" W x 10" H x 6" D (40.64 cm
W x 25.4 cm H x 15.24 cm D)
RBB Remote Battery Box for mounting backup batteries that are too large to fit into the
main control panel cabinet. Dimensions: 16" W x 10" H x 6" D
(40.64 cm W x 25.4 cm H x 15.24 cm D).
Type of Device Model Description
Table 1.1 FCP-2100 Compatible Products (Continued)
Title Document Number
SLC Wiring Manual LS10179-000FK-E
Device Compatibility Document LS10167-005FK-E
FIK-5824 Printer Interface Module Install Sheet LS10254-002FK-E
FIK-RPS1000 Power Supply Manual LS10259-001FK-E
FIK-5496 NAC Expander Manual LS10253-001FK-E
FIK-RA100 Annunciator Install Sheet LS10260-001FK-E
FIK-RA1000R LCD Annunciator Install Sheet LS10258-001FK-E
FIK-RA2000 LCD Annunciator LS10261-001FK-E
FIK-5865-3 and FIK-5865-4 LED Annunciator LS10255-001FK-E
FIK-5880 LED Driver Module LS10256-001FK-E
FIK-5883 General Purpose Relay Module LS10257-001FK-E
Fike ECS Series Manual LS10262-001FK-E
FIK-RVM Install Sheet LS10311-001FK-E
FIK-SW24 Install Sheet LS10264-001FK-E
FIK-CE4 Install Sheet LS10263-001FK-E
FIK-INT50W Install Sheet LS10119-002FK-E
FIK-RPU Install Sheet LS10152-002FK-E
FIK-NVCM Install Sheet LS10169-002FK-E
FIK-LOC Install Sheet LS10187-002FK-E
FIK-LOC2100 Install Sheet LS10188-002FK-E
FIK-EMG Install Sheet LS10191-002FK-E
FIK-NIC Install Sheet LS10172-002FK-E
FIK-FML/FSL Install Sheet LS10178-002FK-E
MRD-1 Releasing Disconnect LS10231-000GE-E
Table 1.2 Related Documentation

14 FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022
Section 2: Agency Listings, Approvals, and Requirements
2.1 Federal Communications Commission (FCC)
The following information must be provided to the telephone company before the FCP-2100 can be connected to the phone lines:
This equipment complies with Part 68 of the FCC rules and the requirements adopted by ACTA. On the inside cover of this equipment is a
label that contains, among other information, a product identifier. If requested, this information must be provided to the telephone company.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68
rules and requirements adopted by the ACTA. A compliant telephone cord (not provided) and modular jack must be utilized with this prod-
uct. It is designed to be used with a modular jack that is also compliant.
The REN (ringer equivalence number) provided on this installation sheet is used to determine the number of devices that may be connected
to the public switched telephone network. This number must not exceed 5.0. Since this product has an REN of 1.0A, the number of devices
is limited. The REN number is embedded in the FCC registration number as 10A.
If the FCP-2100 causes harm to the telephone network, the telephone company will notify you in advance that the temporarily discontinu-
ance of service may be required. But if advance notice is not practical, the telephone company will notify the customer as soon as possible.
Also, you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations or procedures that could affect the operation of the equip-
ment. If this happens the telephone company will provide advance notice in order for you to make necessary modifications to maintain unin-
terrupted service.
If trouble is experienced with the FCP-2100, for repair or warranty information, contactFike at (800)979-3453 or www.fike.com. If the
equipment is causing harm to the telephone network, the telephone company may request that you disconnect the FCP-2100 until the prob-
lem has been resolved.
This product cannot be adjusted or repaired in the field. It must be returned to the factory for service.
This equipment is not designed for use with party line service. Connection to party line service is subject to state tariffs.You may contact the
state public utility commission, public service commission or corporation commission for information.
Since the FCP-2100 is a commercial fire alarm panel, it must be connected upstream of all other equipment utilizing the phone lines. If you
have questions about the installation, contact your telephone company or a qualified installer.
Manufacturer: Fike
Model Number: FCP-2100/ECS
FCC registration number: US: HS9AL10A2100
Ringer equivalence: 1.0A
Type of jack: RJ31X
Facility Interface Codes: Loop Start: 02LS2
Service Order Code: 9.0F
!
WARNING: FCC PART 15
THIS DEVICE HAS BEEN VERIFIED TO COMPLY WITH FCC RULES PART 15. OPERATION IS SUBJECT TO THE
FOLLOWING CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE RADIO INTERFERENCE,AND (2) THIS DEVICE MUST
ACCEPTANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
!
CAUTION: INSTALLATION AND TEST
TO ENSURE PROPER OPERATION, THIS EQUIPMENT MUST BE INSTALLED ACCORDING TO THE ENCLOSED
INSTALLATION INSTRUCTIONS. TO VERIFY THAT THE EQUIPMENT IS OPERATING PROPERLY AND CAN
SUCCESSFULLY REPORTAN ALARM, THIS EQUIPMENT MUST BE TESTED IMMEDIATELY AFTER INSTALLATION,
AND PERIODICALLY THEREAFTER, ACCORDING TO THE ENCLOSED TEST INSTRUCTIONS.
!
CAUTION: LINE IN USE
IN ORDER FOR “ALARM DIALING EQUIPMENT” TO BE ABLE TO SEIZE THE PHONE LINE TO REPORTAN ALARM OR
OTHER EVENT WHEN OTHER CUSTOMER EQUIPMENT (TELEPHONE, ANSWERING SYSTEM, COMPUTER MODEM,
ETC.) CONNECTED TO THE SAME LINE IS IN USE, “ALARM DIALING EQUIPMENT” MUST BE CONNECTED TOA
PROPERLY INSTALLED RJ31X JACK. THE RJ31X JACK MUST BE CONNECTED IN SERIES WITH, AND AHEAD OF, ALL
OTHER EQUIPMENTATTACHED TO THE SAME PHONE LINE. SERIES INSTALLATION OF AN RJ31X JACK IS DEPICTED
IN THE FIGURE BELOW. IF YOU HAVE ANY QUESTIONS CONCERNING THESE INSTRUCTIONS, CONSULT YOUR
TELEPHONE COMPANY OR A QUALIFIED INSTALLER ABOUT INSTALLING THE NECESSARY JACKAND ALARM
DIALING EQUIPMENT.

FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022 15
Underwriters Laboratories (UL) Agency Listings, Approvals, and Requirements
2.2 Underwriters Laboratories (UL)
2.2.1 Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for addi-
tional requirements. The following subsections list specific requirements for each type of installation (for example, Central Station Fire
Alarm systems, Local Protected Fire Alarm systems, and so on). See Section 9.6 for information on releasing operation.
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use the addressable smoke detectors specified in the SLC Wiring Manual and/or conventional detectors listed in the Device
Compatibility Document.
3. Use UL listed notification appliances compatible with the FCP-2100 from those specified in the Device Compatibility Document.
4. Afull system checkout must be performed any time the panel is programmed.
Restricted Options:
• The loss of AC signal is defaulted to 3 hours, but the system still allows settings from 0 - 30 hours. For UL certified installations, this
number must be set from 1 to 3 hours.
• The system allows the use of non-latching, spot type smoke detectors. This feature may not be used in commercial applications
whereby a general alarm is sounded. It is intended for elevator recall, door holding applications, and hotel/motel room applications.
• The system allows the Alarm Verification confirmation time to be set from 60 to 250 seconds. For UL certified installations the setting
must be a minimum of 60 seconds.
• The systems allows the Auto-resound time to be set to 24 or 4 hours. For ULcertified installations that are utilizing SWIFT devices, the
value must be set to 4 hours.
• Call forwarding shall not be used.
• When two count is used: detector spacing shall be cut in half, you shall not use the alarm verification feature, and no delay shall be used.
• P.A.S. (positive alarm sequence) feature shall be used only with automatic detectors.
2.2.2 UL 864 9th and 10th Edition
• Per the UL Continuing Certification Program, UL864 9th edition fire alarm control equipment will retain certification after the roll-out
of UL 10th edition (12/2/2018).
• Installations of UL 864 10th Edition certified equipment are permitted to use UL864 9th Edition certified equipment when approved by
the local Authority Having Jurisdiction (AHJ).
For product compliance, refer to the UL/ULC listing cards located on the UL online certification directory. https://iq.ulprospector.com
2.2.3 Requirements for Central Station Fire Alarm Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the FCP-2100 shall automatically initiate and complete a test signal
transmission sequence to its associated receiver at least once every 6 hours, using two phones or one phone line with Ethernet backup.
3. The AC Loss Hours option must be set from 1-3 hours.
4. If using wired Ethernet, you must program the corresponding account/subscriber ID and a test time so that the FACP shall automatically
initiate a test signal transmission sequence to its associated receiver at least once every 6 hours.
2.2.4 Requirements for Local Protected Fire Alarm Systems
At least one UL listed supervised notification appliance must be used.
2.2.5 Requirements for Remote Station Protected Fire Alarm Systems
Minimum system requirements are one Fike addressable initiating device and either a 5220, Keltron 3158, or the built-in Digital Alarm
Communicator Transmitter (DACT).
1. Do not exceed the current draw load restrictions shown in Section 3.5.
2. The AC Loss Hours option must be set from 1-3 hours.
2.2.6 Requirements for the Installation of Carbon Monoxide (CO) Detection and Warning
Equipment, NFPA 720
When using carbon monoxide detection the system must be monitored by a Supervising Station with emergency response, both aspects meet-
ing the Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, NFPA 720.

16 FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022
Agency Listings, Approvals, and Requirements Underwriters Laboratories (UL)
2.2.7 NFPA Requirements
The following is the minimum configuration to meet NFPA requirements.
Model/Module Description Local Releasing Auxiliary Remote
Station Central
Station
FCP-2100 Control Unit YYYYY
FIK-6861BIA annunciator YYYYY
RFCP-2100 Remote unit O O O O O
FIK-6815 SLC Expander OOOOO
FIK-5824 Serial card OOOOO
5220 Rev Polarity Module O O Y Y O
FIK-NIC NetworkcardOOOOO
FIK-FML Fiber module OOOOO
FIK-FSL Fiber module OOOOO
Y = YES, N = NO, O = OPTIONAL
Table 2.1 NFPA Requirements for FCP-2100, FCP-2100HV, RFCP-2100, or RFCP-2100HV

FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022 17
Underwriters Laboratories (UL) Agency Listings, Approvals, and Requirements
Model/Module Description Local Releasing Auxiliary Remote
Station Central
Station
Mass
Notification
(In-Building) Emergency EVAC
FCP-2100ECS Control Unit Y Y Y Y Y Y Y Y
FIK-6861BIA Annunciator Y Y Y Y Y Y Y Y
FIK-EMG LED / switch card Y Y Y Y Y Y Y Y
5220 Direct Conn
Module OO Y YO N O N
FIK-5496 Indicating Circuit
Expander OO O OO O O O
FIK-5824 Serial/Parallel
Interface OO O OO O O O
FIK-5865-3, FIK-
5865-4 Remote
Annunciator OO O OO O O O
FIK-5880 Remote
Annunciator OO O OO O O O
FIK-5883 Relay Module O O O O O N O N
FIK-6815 SLC expander O O O O O O O O
FIK-NIC Network card O O O O O O O O
FIK-NVCM Network Voice
Control Mod OO O OO O O O
FIK-FML, FIK-FSL Network Fiber Mod O O O O O O O O
FIK-M500R Control Mod O O Y O O N O N
FIK-RPS1000 Power Expander O O O O O O O O
RBB Accessory cabinet O O O O O O O O
FIK-DUAL50W Amplifier N N N N N Y1OY
1
FIK-50W Amplifier N N N N N Y1OY
1
FIK-125W Amplifier N N N N N Y1OY
1
FIK-SW24 Switch
Annunciator NN N NN Y O Y
FIK-RVM Remote Voice
Module NN N NN Y O Y
FIK-INT50W Amplifier N N N N N Y O Y
Y = YES, N = NO, O = OPTIONAL
1. At least one of the following amplifiers is required for MNS operation as well as EVAC: FIK-DUAL50W, FIK-50W, FIK-125W or FIK-INT50W.
Table 2.2 NFPA Requirements for FCP-2100ECS

18 FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022
Section 3: Before You Begin Installation
This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly, espe-
cially if you are installing a FCP-2100 panel for the first time.
3.1 Inventory
When the FCP-2100shipment is received, check that all the parts have been included in the shipment. The shipment consist of one of each of
the following:
• main circuit board with display
• backbox with door.
• plastic bag containing two keys, screws, cables, and ten 4.7K ohm end-of-line resistors
• manual
3.2 Environmental Specifications
It is important to protect the FCP-2100 control panel from water. To prevent water damage, the following precautions should be followed
when installing the units:
• Intended for indoor use in dry locations only
• Do not mount directly on exterior walls, especially masonry walls (condensation)
• Do not mount directly on exterior walls below grade (condensation)
• Protect from plumbing leaks
• Protect from splash caused by sprinkler system inspection ports
• Do not mount in areas with humidity-generating equipment (such as dryers, production machinery)
When selecting a location to mount the FCP-2100 control panel, the unit should be mounted where it will NOT be exposed to: temperatures
outside the range of 0°C- 49°C (32°F-120°F) or humidity exceeding 93% non-condensing.
3.3 Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades
to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that
you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any
questions about software and the appropriate version for a specific application. Software updates can be found at www.fike.com.
3.4 Electrical Specifications
Table 3.1 lists the terminal block on the FCP-2100 as well as a description of each individual terminal and their respective electrical rating.
Terminal Label Description Rating Earth Ground
Faults
Voltage Current
B AC input (hot) 120 VAC, 60 Hz
240 VAC, 50/60 Hz 5A for the FCP-2100
4.5A for the FCP-2100ECS
2.8A for the FCP-2100HV/ECSHV
N/A
G Earth ground N/A N/A N/A
W AC input (neutral) 120 VAC, 60 Hz
240 VAC, 50/60 Hz 5A for the FCP-2100
4.5A for the FCP-2100ECS
2.8A for the FCP-2100HV/ECSHV
N/A
X1I/O 1 Flexput Circuits 24 VDC 3.0 A notification and auxiliary
power circuits 0Ω
O100 mA for initiation circuits
X1I/O 2 Flexput Circuits 24 VDC 3.0 A notification and auxiliary
power circuits 0Ω
O100 mA for initiation circuits
X1I/O 3 Flexput Circuits 24 VDC 3.0 A notification and auxiliary
power circuits 0Ω
O100 mA for initiation circuits
X1I/O 4 Flexput Circuits 24 VDC 3.0 A notification and auxiliary
power circuits 0Ω
O100 mA for initiation circuits
X1I/O 5 Flexput Circuits 24 VDC 3.0 A notification and auxiliary
power circuits 0Ω
O100 mA for initiation circuits
Table 3.1 Terminal Descriptions and Electrical Specifications

FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022 19
Electrical Specifications Before You Begin Installation
X1I/O 6 Flexput Circuits 24 VDC 3.0 A notification and auxiliary
power circuits 0Ω
O100 mA for initiation circuits
X1I/O 7 Flexput Circuits 24 VDC 3.0 A notification and auxiliary
power circuits 0Ω
O100 mA for initiation circuits
X1I/O 8 Flexput Circuits 24 VDC 3.0 A notification and auxiliary
power circuits 0Ω
O100 mA for initiation circuits
B SBUS1 OUT SBUS communication 5 VDC 100 mA 0Ω
A
+ SBUS power 24 VDC 1.0A
-
B SBUS1 IN Used for Class Ainstallations 0Ω
A
+
-
B SBUS2 OUT SBUS communication 5 VDC 100 mA 0Ω
A
+ SBUS power 24 VDC 1.0A
-
B SBUS2 IN Used for Class Ainstallations 0Ω
A
+
-
N.C. RELAY 1 General Purpose Relay 1 24 VDC 2.5A, resistive N/A
C
N.O.
N.C. RELAY 2 General Purpose Relay 2 24 VDC 2.5A, resistive N/A
C
N.O.
N.C. TROUBLE Trouble Relay 24 VDC 2.5 A, resistive N/A
C
N.O.
S- SLC OUT SLC terminals 32 VDC 150 mA 0Ω
S+
S- SLC PGM SLC Programming 32 VDC 150 mA 0Ω
S+
S- SLC IN Used for Class Ainstallations 0Ω
S+
Ring Phone Line 1 Telco Ring N/A 0Ω
Tip Phone Line 1 Telco Tip
Ring Phone Line 1 Premises Ring
Tip Phone Line 1 Premises Tip
Ring Phone Line 2 Telco Ring N/A 0Ω
Tip Phone Line 2 Telco Tip
Ring Phone Line 2 Premises Ring
Tip Phone Line 2 Premises Tip
Terminal Label Description Rating Earth Ground
Faults
Voltage Current
Table 3.1 Terminal Descriptions and Electrical Specifications

20 FCP-2100/ECS Manual — P/N LS10143-002FK-E:B 6/20/2022
Before You Begin Installation Calculating Current Draw and Standby Battery
3.5 Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery needs for your installation.
3.5.1 Current Draw Worksheet Requirements
The following steps must be taken when determining FCP-2100 current draw and standby battery requirements.
1. For the FCP-2100, the worst case current draw is listed for the panel, addressable devices, and SLC expanders. Fill in the number of
addressable devices and expanders that will be used in the system and compute the current draw requirements for alarm and standby.
Record this information in the current draw worksheet on LineA.
2. Add up the current draw for all auxiliary devices and record in the table on Line B.
3. Add up the current draw for all notification appliance loads and record in the table on Line C.
4. For notification appliances and auxiliary devices not mentioned in the manual, refer to the device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the panel itself, does not exceed 9.0A. This is the maximum
alarm current for the FCP-2100 control panel. If the current is above 9.0 A you will need to use a notification power expander(s) such as
the FIK-5496 or the FIK-RPS1000 intelligent power expander, to distribute the power loads so that the FCP-2100 or the power
expanders do not exceed their power ratings. Refer to the current draw worksheets provided with the FIK-5496 or the FIK-RPS1000
manuals so you do not exceed their power ratings.
6. Alternatively, you may network additional FCP-2100 panels to get additional power.
7. Complete the remaining instructions in the appropriate current draw worksheet for determining battery size requirements.
3.5.2 Current Draw Worksheet for Fike SLC Devices
Use Table 3.2 to determine current requirements during alarm/battery standby operation when SLC devices are installed. You can install up
to 159 sensors per loop (2100 points max per panel) and 159 modules per loop (2,100 points max per panel). Copy this section if additional
space is required.
+ Battery Battery Connection 24 VDC 1.12 A N/A
–
P7 Data
Network Used for FIK-NIC 24 VDC 21 mA 0Ω
P8 Voice
Network Used For FIK-NVCM 24 VDC 59 mA 0Ω
1 Regulated for NAC circuits, special application when used for releasing or auxiliary power circuits
Terminal Label Description Rating Earth Ground
Faults
Voltage Current
Table 3.1 Terminal Descriptions and Electrical Specifications
Device # of Devices Current per Device Standby
Current Alarm Current
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel
(Current draw from battery) 1 Standby 230 mA 230 mA
Alarm: 415 mA 415 mA1
Addressable SLC Detectors
FIK-2351
Standby: 0.2 mA
Alarm: 4.5 mA2
mA mA
FIK-2351T mA mA
FIK-2351R mA mA
FIK-5351 mA mA
FIK-5351H mA mA
FIK-5351R mA mA
OSI-RI-FIK SLC Standby/Alarm: 20 mA mA mA
Aux. Pwr Standby: 22 mA mA
Alarm: 20 mA mA
DNR/DNRW3(non-relay) None, included with FIK-2351R
DNR3(with relay) None, included with FIK-2351R & FIK-M500R
FIK-FC351 SLC Standby: 0.20 mA mA
Alarm: 4.5 mA mA
Table 3.2 Current Draw Worksheet for IDP SLC Devices
This manual suits for next models
1
Table of contents
Other Fike Control Panel manuals

Fike
Fike Twinflex pro2 User manual

Fike
Fike TWINFLEXpro User manual

Fike
Fike FCP-75 User manual

Fike
Fike CIE-A-200 User manual

Fike
Fike FIK-5496 User manual

Fike
Fike TWINFLEX SRP 100-0001 User manual

Fike
Fike FCP-300 User manual

Fike
Fike TWINFLEXpro User manual

Fike
Fike SITA200plus User manual

Fike
Fike FIK-RA100BD Technical manual
Popular Control Panel manuals by other brands

Garmin
Garmin GMA 345 pilot's guide

Harvia
Harvia Xenio RGBW CX002RGBW Instructions for installation and use

Compool
Compool Cp3830 Installation & operating instructions

GE
GE Entelli-Switch 250 Operation and maintenance manual

ICP DAS USA
ICP DAS USA TPD-432F-H quick start

Siemens
Siemens SIMATIC HMI OP3 Equipment manual