Fike 55-042 User manual

D500-74-00 1 I56-2463-008
INSTALLATION AND MAINTENANCE INSTRUCTIONS
55-042 Supervised Control Module
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to the
appropriate control panel installation manual for detailed system information.
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
Control Module, Model 55-042, is used to switch an external power supply
or audio amplifier to notification appliances. In addition to switching the ex-
ternal power, the device will monitor the wiring (while external power is not
switched to the auxiliary devices) to the auxiliary device for open and short
circuits via an end of line resistor. This module is capable of Class A or Class
B operation.
The control module will also have the capability to monitor the external
power input for loss of power (DC voltage supplies only). This feature can
be disabled through device configuration programming. If the external power
is switched to the auxiliary devices and there is a loss of the DC supply, the
control module has the capability of running an algorithm in which the device
will switch back to monitor mode and check the line for short circuits. If no
short exists, the device will reapply the external power. This algorithm can
be enabled when using a DC external supply that is guaranteed to be above
9 volts.
SPECIFICATIONS
Normal Operating Voltage: 15 to 30 VDC
Standby Current: 630 µA maximum average (continuous broadcasts)
Alarm Current: 2 mA (red LED on)
Maximum NAC Circuit Line Loss: 4 VDC
Power Supply Monitor
Maximum (Speakers): 70.7 Vrms, 50W
Maximum (NAC): Regulated 24 VDC
Trouble Range: 0 to 2 VDC
Maximum NAC Current Ratings: For Class B Wiring Systems, 3A; For Class A Wiring Systems, 2A
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10% to 93% RH Non-condensing
Dimensions: 4.675˝ H x 4.275˝ W x 1.4˝ D
Accessories: 39 kΩEnd of Line Resistor Part # A2263-00 (included); Wall cover plate (included); SMB500 Surface Mount Electrical Box;
A2143-60 Bypass capacitor; EA-CB Control Module Barrier
I56-2463-008
704 S. 10th Street
Blue Springs, MO 64015
Phone: 816.229.3405; Fax: 816.228.9277
R
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a listed compat-
ible control panel.
MOUNTING
The module mounts directly to 4-inch square electrical boxes. The box must
have a minimum depth of 21/8inches. Modules must be mounted with the ar-
row facing upward for proper operation of the IR programming tool. Surface
mounted electrical boxes (SMB500) are available from Fike.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams. Optional EA-CB may be required to separate power
limited and non power limited wiring in the electrical box.
2. For new installations use the enclosed 39 kΩEOL resistor. For retrofit ap-
plications where the existing 47 kΩcannot be easily replaced, it may be
left in place without loss of performance.
3. Set the address on the module per job drawings using the handheld IR
programmer.
4. Secure module to electrical box (supplied by installer).
NOTE: All references to power limited represent “Power Limited (Class 2)”.
All references to Class A also include Class X.
RELAY CONTACT RATINGS:
CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION
2 A 25 VAC PF = 0.35 Non-coded
3 A 30 VDC Resistive Non-coded
2 A 30 VDC Resistive Coded
0.46 A 30 VDC (L/R = 20ms) Non-coded
0.7 A 70.7 VAC PF = 0.35 Non-coded
0.9 A 125 VDC Resistive Non-coded
0.5 A 125 VAC PF = 0.75 Non-coded
0.3 A 125 VAC PF = 0.35 Non-coded

D500-74-00 2 I56-2463-008
TESTING
The following resistance values can be used to test the module after installation:
Short Circuit: <50Ω
Open Circuit: >1MΩ
Ground Fault: <50Ω
WARNING
All relay switch contacts are shipped in the standby state (open) state, but may
have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to com-
municate with the panel before connecting circuits controlled by the module.
TERMINAL DEFINITIONS
T1 (+) SLC in/out T9 (–) External Power Line in/out
T2 (–) SLC in/out T10 (+) External Power Line in/out
T3 (+) SLC in/out T11 (+) NAC A/B
T4 (–) SLC in/out T12 (–) NAC A/B
T7 (–) External Power Line in/out T13 (–) Class A
T8 (+) External Power Line in/out T14 (+) Class A
FIGURE 1. SUPERVISED CONTROL MODULE:
LED INDICATOR
IR RECEIVER
C0164-00

D500-74-00 3 I56-2463-008
FIGURE 2. TYPICAL CLASS B, STYLE Y NAC CONFIGURATION:
TO NEXT
DEVICE
FROM PANEL OR
PREVIOUS DEVICE
SIGNAL LINE CIRCUIT (SLC)
30 VDC MAX.
TWISTED P
AIR RECOMMENDED
(–)
(+)
(–)
(+)
EOL
RESIST
OR
UL LISTED
EOL RELAY
SHOWN
ENERGIZED
24 VDC COIL
A77-716B OR
EQUIVALENT
REQUIRED FOR PANELS
WITHOUT POWER SUPPLY
MONITORING
FROM TERMINALS
7 AND 8 OF LAST
CONTROL MODULE
ON BRANCH
MODULE POLARITIES ARE
SHOWN IN ALARM
14
13
12
11
10
9
8
7
24 VDC
POWER
SUPPLY
TO NEXT CONTROL MODULE
TERMINALS 10 (+) AND 9 (–)
OR END OF LINE RELAY
(IF REQUIRED)
–
+
1
2
3
4
–
+
24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER NFPA 70
LISTED FOR FIRE PROTECTION
WITH BATTERY BACK-UP
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
FIGURE 3. TYPICAL CLASS A, STYLE Z NAC CONFIGURATION:
TO NEXT
DEVICE
FROM PANEL OR
PREVIOUS DEVICE
SIGNAL LINE CIRCUIT (SLC)
30 VDC MAX.
TWISTED PAIR RECOMMENDED
(–)
(+)
(–)
(+)
EOL RESISTOR
IS INTERNAL
AT TERMINALS
13 & 14
UL LISTED
EOL RELAY
SHOWN
ENERGIZED
24 VDC COIL
A77-716B OR
EQUIVALENT
REQUIRED FOR PANELS
WITHOUT POWER SUPPLY
MONITORING
FROM TERMINALS
7 AND 8 OF LAST
CONTROL MODULE
ON BRANCH
MODULE POLARITIES ARE SHOWN IN ALARM 14
13
12
11
10
9
8
7
24 VDC
POWER
SUPPLY
TO NEXT CONTROL MODULE
TERMINALS 10 (+) AND 9 (–)
OR END OF LINE RELAY
(IF REQUIRED)
–
+
1
2
3
4–
+
24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER NFPA 70
LISTED FOR FIRE PROTECTION
WITH BATTERY BACK-UP
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
C0107-04
C0937-00

D500-74-00 4 I56-2463-008
©2013 Fike
FCC STATEMENT
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installa-
tion. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
FIGURE 4. TYPICAL CLASS B, STYLE Y AUDIO NAC CONFIGURATION:
TO NEXT
DEVICE
FROM PANEL OR
PREVIOUS DEVICE
SIGNAL LINE CIRCUIT (SLC)
30 VDC MAX.
TWISTED PAIR RECOMMENDED
EOL
RESIST
OR
SPEAKERS MUST BE LISTED FOR FIRE PROTECTION
14
13
12
11
10
9
8
7
AUDIO
AMPLIFIER
70.7 Vrms MAX.
AUDIO CIRCUIT MUST BE
TWISTED PAIR AS A MINIMUM
WHEN A 70.7 V AUDIO AMPLIFIER IS USED,
TERMINALS 1-4 ARE POWER LIMITED,
WHILE TERMINALS 7-14 ARE
NON-POWER LIMITED
–
+
1
2
3
4
–
+
ALL WIRING SHOWN IS SUPERVISED
(–)
(+)
TO NEXT CONTROL MODULE
LAST MODULE MUST
RETURN WIRES AUDIO AMP.
(–)
(+)
(–)
(+)
(–)
(+)
C0938-00
FIGURE 5. TYPICAL CLASS A, STYLE Z AUDIO NAC CONFIGURATION:
TO NEXT
DEVICE
FROM PANEL OR
PREVIOUS DEVICE
SIGNAL LINE CIRCUIT (SLC)
30 VDC MAX.
TWISTED PAIR RECOMMENDED
EOL
RESISTOR
IS INTERNAL
AT
TERMINALS
13 AND 14
SPEAKERS MUST BE LISTED FOR FIRE PROTECTION
14
13
12
11
10
9
8
7
AUDIO
AMPLIFIER
70.7 Vrms Max.
AUDIO CIRCUIT MUST BE
TWISTED PAIR AS A MINIMUM
WHEN A 70.7 V AUDIO AMPLIFIER
IS USED, TERMINALS 1-4 ARE
POWER LIMITED, WHILE TERMINALS
7-14 ARE NON-POWER LIMITED
–
+
1
2
3
4
–
+
ALL WIRING SHOWN IS SUPERVISED
(–)
(+)
TO NEXT CONTROL MODULE
LAST MODULE MUST
RETURN WIRES
(–)
(+)
(–)
(+)
REQUIRED
BYPASS CAPACITORS:
100µF 16V
NONPOLARIZED
<10µA LEAKAGE
A2143-60
(–)
(+)
C0393-00
Table of contents
Other Fike Control System manuals

Fike
Fike CyberCat 1016 Owner's manual

Fike
Fike CyberCat 1016 Manual

Fike
Fike FIK-PULL-SA User manual

Fike
Fike 10-071 User manual

Fike
Fike FIK-CZ-6 User manual

Fike
Fike Cheetah Xi User guide

Fike
Fike Epaco User manual

Fike
Fike Cheetah Xi User manual

Fike
Fike CyberCat 50 10-070 Manual

Fike
Fike 10-2539 Owner's manual
Popular Control System manuals by other brands

Landi Renzo
Landi Renzo A1 V05 Installation and adjustment manual

BM PRO
BM PRO JAYCOMMAND owner's manual

Spraying Systems
Spraying Systems TeeJet TECHNOLOGIES BoomPilot installation manual

BM PRO
BM PRO OdysseyControl owner's manual

Planet
Planet HDVR-1600 user manual

Mill-right
Mill-right CARVE KING 2 Assembly instructions