Fike CyberCat 1016 User manual

Installation Manual
P/N 06-326, Rev. 14
September 2015
10-064, CyberCat 1016
10-066, CyberCat 254
Addressable Fire Alarm Control System

DEVELOPED BY Fike
704 SW 10th Street
P.O. Box 610
Blue Springs, Missouri 64013 U.S.A.
Phone: (800) 979-FIKE (3453)
(816) 229-3405
Fax: (816) 229-0314
COPYRIGHT NOTICE Copyright 2015. All rights reserved.
Fike copyrights this manual and products it describes. You may not reproduce,
transmit, transcribe, or any part of this manual without express, written
permission from Fike.
This manual contains proprietary information intended for distribution to
authorized persons or companies for the sole purpose of conducting business
with Fike. If you distribute any information contained in this manual to
unauthorized persons, you have violated all distributor agreements and we may
take legal action.
TRADEMARKS Fikeis a registered trademark of Fike.
CyberCat®is a registered trademark of Fike.
QUALITY Fike has maintained ISO 9001 certification since 1996. Prior to shipment, we
thoroughly test our products and review our documentation to assure the highest
quality in all respects.
WARRANTY Fike provides a one-year limited manufacturer’s warranty on this product. All
warranty returns must be returned from an authorized Fike Distributor. Contact
Fike’s Marketing department for further warranty information.
Fike maintains a repair department that is available to repair and return existing
electronic components or exchange/purchase previously repaired inventory
component (advance replacement). All returns must be approved prior to return.
A Material Return Authorization (MRA) number must be indicated on the box of
the item being returned. Contact the appropriate Regional Sales Manager for
further information regarding product return procedures.
LIMITATIONS OF LIABILITY
Installation in accordance with this manual, applicable codes, and the
instructions of the Authority Having Jurisdiction is mandatory. Fike can not be
held liable for any incidental or consequential damages arising from the loss of
property or other damages or losses resulting from the use or misuse of Fike
products beyond the cost of repair or replacement of any defective components.
Fike reserves the right to make product improvements and change product
specifications at any time.
While every precaution has been taken during the preparation of this manual to
ensure the accuracy of its content, Fike assumes no responsibility for errors or
omissions.

TABLE OF CONTENTS
UL S2203 CyberCat 254/1016 Installation Manual i
FM P/N: 06-326 Rev 14, 09/2015
REVISION HISTORY
Document Title: CyberCat Addressable Fire Alarm System Installation Manual
Document Reorder Number: 06-326
Revision Section Date Reason for Change
0 All Sections 09/2004 Initial Release
1 All Sections 12/2004 Added CyberCat 254 and programming
menu’s
2 All Sections 05/2005
Added Networking, Isolator devices,
sounder bases
3 All Sections 08/2007 Upgraded Firmware to Version 3.0
4 Sections 2, 3, 6 and 8 03/2008 Added new peripherals
5 Sections 1, 3, 6 and 7 07/2008 Added Dual Monitor Module and
Conventional Zone Monitor Module
6 All Sections 10/2008
Creation of Product Manual and addition of
Smoke Control components
7 All Sections 04/2011 Separated manual into separate
Installation, Operation and Programming
Manuals
8 All Sections 06/2011 Changed document P/N from
06-326-1 to 06-326
9 Sections 1, 2, 3, Appendix A & C 12/2011 Added MNS updates
10 Sections 2.1.4, 3.7.6, 3.8,
Appendix A & C
04/2012 FAAST Detector Addition
11 Appendix A 06/2012 Updated battery calculations per UL 2572
12 All Sections 08/2014 Added FAAST XT
aspirating smoke detector
13 Appendix A 02/2015 Updated Appendix A battery calculation
14 All Sections 09/2015 Clarifications and General Updates

TABLE OF CONTENTS
ii CyberCat 254/1016 Installation Manual UL S2203
Rev 14, 09/2015 P/N: 06-326 FM
SECTION DESCRIPTION PAGE
1.0 Introduction ....................................................................................................................1-1
1.1 About This Manual...........................................................................................................1-1
1.2 Product Support...............................................................................................................1-1
1.3 Safety Information............................................................................................................1-1
1.4 Terms Used In This Manual.............................................................................................1-2
1.5 Related Documentation ...................................................................................................1-3
2.0 System Overview ...........................................................................................................2-1
2.1 System Description..........................................................................................................2-1
2.1.1 CyberCat Features...........................................................................................................2-2
2.1.2 Listings and Approvals.....................................................................................................2-3
2.1.3 Agency Standards and Compliance.................................................................................2-3
2.1.4 Minimum System Configurations.....................................................................................2-4
3.0 System Components .....................................................................................................3-1
3.1 Basic Equipment Packages .............................................................................................3-1
3.2 CyberCat Controller .........................................................................................................3-1
3.3 System Enclosures ..........................................................................................................3-8
3.3.1 Standard Enclosure..........................................................................................................3-9
3.3.1.1 Standard Enclosure with Solid Dead-front.....................................................................3-10
3.3.1.2 Standard Enclosure with Three Card Dead-front...........................................................3-10
3.3.2 Fire Command Center (FCC) Enclosures......................................................................3-11
3.3.2.1 FCC Enclosure with Nineteen Card Dead-front.............................................................3-11
3.3.2.2 FCC Enclosure with Twenty-Three Card Dead-front.....................................................3-12
3.3.2.3 FCC Enclosure with Option-2 Back-Box........................................................................3-13
3.3.3 FCC Enclosure with Twenty-Five Card Dead-front........................................................3-14
3.4 Optional Dead-Front Cover Plates.................................................................................3-15
3.5 Optional Circuit Modules................................................................................................3-16
3.5.1 DACT, 5 Zone with Serial Interface ...............................................................................3-16
3.5.1.1 DACT Programmer ........................................................................................................3-16
3.5.2 Supplemental Power Supply (SPS)...............................................................................3-16
3.5.3 Supplemental Loop Module (SLM) ................................................................................3-17
3.5.4 Relay Module (CRM4)....................................................................................................3-17
3.5.5 Reverse Polarity Module (RPM) ....................................................................................3-17
3.5.6 RS485 Network Module.................................................................................................3-17
3.5.7 Fiber Optic Network Module ..........................................................................................3-18
3.6 Peripheral Bus Devices..................................................................................................3-19
3.6.1 Fourteen Button Remote Display Unit ...........................................................................3-19
3.6.2 Ten Button Remote Display Unit....................................................................................3-19
3.6.3 Two Button Remote Display Unit...................................................................................3-20
3.6.4 Ethernet Module.............................................................................................................3-20
3.6.5 Multi-Interface Module (MIM).........................................................................................3-20
3.6.6 Intelligent Graphic Annunciator......................................................................................3-21
3.6.7 Firefighter’s Smoke Control Station (FSCS)..................................................................3-21
3.6.8 Twenty Zone Remote Annunciator ................................................................................3-22
3.6.9 Six Zone Smoke Control Switch Card............................................................................3-22
3.6.10 Input/Output Switch Card...............................................................................................3-22
3.6.11 Twenty Zone Annunciator Card (panel mount)..............................................................3-23
3.6.12 Audio Control Card.........................................................................................................3-23
3.6.13 Fire-Phone Card.............................................................................................................3-23
3.6.14 Supplemental Fire-Phone Card .....................................................................................3-24

TABLE OF CONTENTS
UL S2203 CyberCat 254/1016 Installation Manual iii
FM P/N: 06-326 Rev 14, 09/2015
SECTION DESCRIPTION PAGE
3.6.15 Amplifier Card................................................................................................................ 3-24
3.6.15.1 Class A Speaker Card................................................................................................... 3-24
3.6.16 Relay Control Assembly................................................................................................ 3-25
3.6.17 Relay Card..................................................................................................................... 3-25
3.6.18 Class A Peripheral Bus Card......................................................................................... 3-25
3.6.19 FCC Digital Paging Assembly....................................................................................... 3-26
3.6.20 Local Operating Console............................................................................................... 3-27
3.6.20.1 Audio Adjunct Panel...................................................................................................... 3-27
3.7 Intelligent Detectors....................................................................................................... 3-28
3.7.1 Photoelectric Smoke Detector....................................................................................... 3-28
3.7.2 Ionization Smoke Detector ............................................................................................ 3-28
3.7.3 Photo/Heat Combination Detector................................................................................. 3-29
3.7.4 Heat Detector ................................................................................................................ 3-29
3.7.5 Photoelectric Duct Detector........................................................................................... 3-30
3.7.5.1 Duct Detector Housing .................................................................................................. 3-30
3.7.6 FAAST Aspirating Smoke Detector............................................................................... 3-31
3.8 Detector Bases.............................................................................................................. 3-32
3.8.1 Four Inch Detector Base................................................................................................ 3-32
3.8.2 Six Inch Detector Base.................................................................................................. 3-32
3.8.3 Sounder Base................................................................................................................ 3-32
3.8.4 Relay Base .................................................................................................................... 3-32
3.9 Remote Testing and Notification Accessories............................................................... 3-33
3.9.1 Remote Annunciator...................................................................................................... 3-33
3.9.2 Remote Test Station...................................................................................................... 3-33
3.9.3 Remote Test Station with Key....................................................................................... 3-33
3.10 Addressable Modules.................................................................................................... 3-34
3.10.1 Mini Monitor Module ...................................................................................................... 3-34
3.10.2 Monitor Module.............................................................................................................. 3-34
3.10.3 Dual Monitor Module ..................................................................................................... 3-35
3.10.4 Addressable Pull Station ............................................................................................... 3-35
3.10.5 Conventional Zone Monitor Module .............................................................................. 3-35
3.10.6 Supervised Control Module........................................................................................... 3-36
3.10.6.1 Solenoid Protection Assembly....................................................................................... 3-36
3.10.6.2 Master-box Interface...................................................................................................... 3-36
3.10.7 Relay Module................................................................................................................. 3-37
3.11 Vesda High Level Interface ........................................................................................... 3-37
3.12 Programming and Configuration Equipment................................................................. 3-37
3.12.1 IR Remote Tool ............................................................................................................. 3-37
3.12.2 Hand Held Programmer................................................................................................. 3-38
3.12.3 C-Linx Software............................................................................................................. 3-38
3.12.4 Interface Cable .............................................................................................................. 3-38
3.12.5 Interface Converter........................................................................................................ 3-38
3.12.6 Interface Cable (USB to RS232) ................................................................................... 3-38
3.12.7 Interface Cable (USB) ................................................................................................... 3-38
3.13 Batteries and Battery Enclosures.................................................................................. 3-39
3.13.1 18 AH Battery Assembly................................................................................................ 3-39
3.13.2 Batteries......................................................................................................................... 3-39
3.13.3 Battery Enclosures ........................................................................................................ 3-39
3.13.3.1 33 AH Battery Enclosure............................................................................................... 3-39
3.13.3.2 75 AH Battery Enclosure............................................................................................... 3-39

TABLE OF CONTENTS
iv CyberCat 254/1016 Installation Manual UL S2203
Rev 14, 09/2015 P/N: 06-326 FM
SECTION DESCRIPTION PAGE
4.0 Installation ......................................................................................................................4-1
4.1 System Installation Sequence..........................................................................................4-1
4.2 Select the Enclosure Mounting Location..........................................................................4-1
4.3 Select the Enclosure Mounting Option.............................................................................4-2
4.4 Mount the Enclosure........................................................................................................4-2
4.4.1 Install the Dead-front Door...............................................................................................4-2
4.5 Wire Selection..................................................................................................................4-5
4.6 Circuit Class Designations...............................................................................................4-5
4.7 Pull Field Wiring Into the Enclosure.................................................................................4-5
4.8 Verify Field Wiring............................................................................................................4-6
4.9 Install the AC Power Transformer....................................................................................4-6
4.10 Connect AC Power to the Transformer............................................................................4-7
4.11 Install Optional Modules...................................................................................................4-9
4.12 Install the Controller.......................................................................................................4-10
4.13 Connect the AC Power to the Controller........................................................................4-13
4.14 Install Batteries...............................................................................................................4-14
4.14.1 Battery Cutoff .................................................................................................................4-14
4.15 Apply Power to the Panel...............................................................................................4-15
4.16 Connect Field Wiring......................................................................................................4-16
4.16.1 General Relay Wiring.....................................................................................................4-17
4.16.2 RS232 Wiring.................................................................................................................4-17
4.16.3 RS485 Peripheral Bus Wiring........................................................................................4-17
4.16.4 Auxiliary Power Wiring...................................................................................................4-18
4.16.5 SLC Wiring.....................................................................................................................4-19
4.16.5.1 Class B Wiring................................................................................................................4-19
4.16.5.2 Class A Wiring................................................................................................................4-20
4.16.5.3 Class X Wiring................................................................................................................4-20
4.16.5.4 Remote LED Wiring .......................................................................................................4-20
4.16.6 Notification Appliance Circuit Wiring..............................................................................4-21
4.17 Initial Power-Up with Field Wiring Connected................................................................4-22
4.18 Configure System...........................................................................................................4-22
4.19 Acceptance Test ............................................................................................................4-22
Appendix A Battery Calculation Form ............................................................................................. A-1
Appendix B System Operation Posting........................................................................................... B-1
Appendix C Compatible Components ............................................................................................. C-1
Appendix D Battery Cutoff................................................................................................................ D-1

TABLE OF CONTENTS
UL S2203 CyberCat 254/1016 Installation Manual v
FM P/N: 06-326 Rev 14, 09/2015
LIST OF EXHIBITS
EXHIBIT DESCRIPTION PAGE
1-1 Related Documentation................................................................................................... 1-3
1-2 Related Documentation – Continued .............................................................................. 1-4
2-1 Example CyberCat Block Diagram.................................................................................. 2-1
2-2 Minimum System Configurations..................................................................................... 2-4
3-1 System Ordering Formats ............................................................................................... 3-1
3-2 CyberCat System Controller with Display ....................................................................... 3-2
3-3 CyberCat Extended Display ............................................................................................ 3-2
3-4 CyberCat Controller Terminal Locations......................................................................... 3-3
3-5 CyberCat Controller Terminal Specifications .................................................................. 3-4
3-6 CyberCat Controller Terminal Specifications – Cont....................................................... 3-5
3-7 CyberCat Controller Terminal Specifications – Cont....................................................... 3-6
3-8 CyberCat Controller Terminal Specifications – Cont....................................................... 3-7
3-9 Enclosure Ordering Formats ........................................................................................... 3-8
3-10 Standard Enclosure with No Dead-front.......................................................................... 3-9
3-11 Standard Enclosure with Solid Dead-front .................................................................... 3-10
3-12 Standard Enclosure with Three Card Dead-front.......................................................... 3-10
3-13 FCC Enclosure with Nineteen Card Dead-front ............................................................ 3-11
3-14 FCC Enclosure with Twenty-Three Card Dead-front .................................................... 3-12
3-15 FCC Enclosure with Twenty-Five Card Dead-front....................................................... 3-14
3-16 Single Card Plate........................................................................................................... 3-15
3-17 Two Card Plate.............................................................................................................. 3-15
3-18 Three Card Plate........................................................................................................... 3-15
3-19 Four Card Plate ............................................................................................................. 3-15
3-20 Five Card Plate.............................................................................................................. 3-15
3-21 Fire-Phone Plate............................................................................................................ 3-15
3-22 DACT............................................................................................................................. 3-16
3-23 DACT Programmer........................................................................................................ 3-16
3-24 Supplemental Power Supply (SPS)............................................................................... 3-16
3-25 SLM ............................................................................................................................... 3-17
3-26 CRM4............................................................................................................................. 3-17
3-27 CRPM............................................................................................................................ 3-17
3-28 RS485 Network Module................................................................................................. 3-17
3-29 Fiber Optic Network Module.......................................................................................... 3-18
3-30 Fourteen Button Remote Display Unit........................................................................... 3-19
3-31 Ten Button Remote Display Unit................................................................................... 3-19
3-32 Tow Button Remote Display Unit .................................................................................. 3-20
3-33 Ethernet Module ............................................................................................................ 3-20
3-34 Multi-Interface Module................................................................................................... 3-20
3-35 Graphic Annunciator (Intelligent)................................................................................... 3-21
3-36 Firefighter’s Smoke Control Station (FSCS).................................................................. 3-21
3-37 Twenty Zone Remote Annunciator................................................................................ 3-22
3-38 Smoke Control Switch Card .......................................................................................... 3-22
3-39 I/O Switch Card ............................................................................................................. 3-22
3-40 Twenty Zone Annunciator Card..................................................................................... 3-23
3-41 Audio Control Card........................................................................................................ 3-23
3-42 Fire-Phone Card............................................................................................................ 3-23
3-43 Supplemental Fire-Phone Card..................................................................................... 3-24
3-44 Amplifier Card................................................................................................................ 3-24
3-45 Class A Speaker Card................................................................................................... 3-24
3-46 Relay Control Assembly................................................................................................ 3-25

TABLE OF CONTENTS
vi CyberCat 254/1016 Installation Manual UL S2203
Rev 14, 09/2015 P/N: 06-326 FM
EXHIBIT DESCRIPTION PAGE
3-47 HPM4 Relay Card..........................................................................................................3-25
3-48 Relay Card .....................................................................................................................3-25
3-49 Class A Peripheral Bus Card .........................................................................................3-25
3-50 FCC Digital Paging Card................................................................................................3-26
3-51 Local Operating Console ...............................................................................................3-27
3-52 LOC w/ RDU ..................................................................................................................3-27
3-53 Photo Detector...............................................................................................................3-28
3-54 Ion Detector....................................................................................................................3-28
3-55 Photo/Heat Detector.......................................................................................................3-29
3-56 Heat Detector.................................................................................................................3-29
3-57 Photo Duct Detector.......................................................................................................3-30
3-58 Duct Detector Housing...................................................................................................3-30
3-59 FAAST Detector.............................................................................................................3-31
3-60 4-Inch Base....................................................................................................................3-32
3-61 6-Inch Base....................................................................................................................3-32
3-62 Sounder Base ................................................................................................................3-32
3-63 Relay Base.....................................................................................................................3-32
3-64 Remote Annunciator ......................................................................................................3-33
3-65 Remote Test Station ......................................................................................................3-33
3-66 Remote Test Station with Key........................................................................................3-33
3-67 Mini Monitor Module.......................................................................................................3-34
3-68 Monitor Module ..............................................................................................................3-34
3-69 Dual Monitor Module......................................................................................................3-35
3-70 Pull Station.....................................................................................................................3-35
3-71 Conventional Zone Monitor Module...............................................................................3-35
3-72 Supervised Control Module............................................................................................3-36
3-73 Solenoid Protection Assembly.......................................................................................3-36
3-74 Master-box Interface......................................................................................................3-36
3-75 Relay Module .................................................................................................................3-37
3-76 VESDA HLI ....................................................................................................................3-37
3-77 IR Remote Tool..............................................................................................................3-37
3-78 Hand Held Programmer.................................................................................................3-38
3-79 DB9 – RJ11 Communication Cable...............................................................................3-38
3-80 USB – DB9 Communication Cable ................................................................................3-38
3-81 USB Communication Cable ...........................................................................................3-38
3-82 Sealed Batteries.............................................................................................................3-39
3-83 33 AH Battery Enclosure................................................................................................3-39
3-84 75 AH Battery Enclosure................................................................................................3-39
4-1 Standard Enclosure Dimensions......................................................................................4-3
4-2 FCC Enclosure Dimensions.............................................................................................4-4
4-3 Conductor Properties.......................................................................................................4-5
4-4 Standard Enclosure Transformer Mounting Locations ....................................................4-7
4-5 Fire Command Center Enclosure Transformer Mounting Locations ...............................4-7
4-6 Connect AC Power to Transformer..................................................................................4-8
4-7 Connect AC Power to Primary and Secondary Transformer...........................................4-8
4-8 Mounting Locations for Optional Modules .......................................................................4-9
4-9 Controller Mounting Location in Standard Enclosure ....................................................4-10
4-10 Controller Mounting Location in FCC Enclosure............................................................4-10
4-11 Mounting the Controller..................................................................................................4-11
4-12 Mounting the Extended Display.....................................................................................4-12

TABLE OF CONTENTS
UL S2203 CyberCat 254/1016 Installation Manual vii
FM P/N: 06-326 Rev 14, 09/2015
EXHIBIT DESCRIPTION PAGE
4-13 AC Power Connections ................................................................................................. 4-13
4-14 Battery Connections ...................................................................................................... 4-14
4-15 CyberCat Board Terminal Connections......................................................................... 4-16
4-16 P2 Relay Connections................................................................................................... 4-17
4-17 RS232 Wiring ................................................................................................................ 4-17
4-18 RS485 Peripheral Bus Wiring........................................................................................ 4-17
4-19 RS485 DACT Wiring...................................................................................................... 4-18
4-20 Auxiliary Power Wiring................................................................................................... 4-18
4-21 Class B SLC Wiring....................................................................................................... 4-19
4-22 Class A SLC Wiring....................................................................................................... 4-20
4-23 Detector Base Wiring..................................................................................................... 4-20
4-24 NAC Circuit Wiring – Class B........................................................................................ 4-21
4-25 NAC Circuit Wiring – Class A........................................................................................ 4-21
C-1 Compatible Components.................................................................................................C-1
D-1 Battery Cutoff Wiring Diagram.........................................................................................D-2

TABLE OF CONTENTS
viii CyberCat 254/1016 Installation Manual UL S2203
Rev 14, 09/2015 P/N: 06-326 FM
Reserved for future use.

1.0 INTRODUCTION
UL S2203 CyberCat 254/1016 Installation Manual 1-1
FM P/N: 06-326 Rev 14, 09/2015
1.1 ABOUT THIS MANUAL
This manual is intended for those individuals who are responsible for the installation of the Fike CyberCat
Addressable Control System. Others such as architects, engineers, sales and marketing personnel, etc. will
find the information useful as well. It also allows those parties responsible for verifying the system design to
determine if the design parameters have been met.
The first-time installer and/or user should thoroughly read and understand the instructions contained within
this manual before using this device. These instructions must be followed to avoid damage to the equipment
itself or adverse operating conditions caused by improper installation, operation, and servicing.
1.2 PRODUCT SUPPORT
If you have a question or encounter a problem not covered in this manual, you should first try to contact the
distributor that installed the protection system. Fike has a worldwide distribution network. Each distributor
sells, installs, and services Fike equipment. Look on the inside of the door, left side, there should be a sticker
with an indication of the distributor who sold the system. If you cannot locate the distributor, please call Fike
Customer Service for locating your nearest distributor, or go to our web-site at www.fike.com. If you are
unable to contact your installing distributor or you simply do not know who installed the system you can
contact Fike Product Support at (800) 979-FIKE (3453) Option 21, Monday through Friday, 8:00 AM to 4:30
PM CST.
1.3 SAFETY INFORMATION
Important safety admonishments are used throughout this manual to warn of possible hazards to persons or
equipment.
aWARNING
Warnings are used to indicate the presence
of a hazard which will or may cause
personal injury or death, or loss of service if
safety instructions are not followed or if the
hazard is not avoided.
I
Caution
Cautions are used to indicate the presence
of a hazard which will or may case damage
to the equipment if safety instructions are
not followed or if the hazard is not avoided.
Notes: Notes indicate the message is
important, but is not of a Warning or
Caution category. These notes can be of
great benefit to the user and should be
read.

1.0 INTRODUCTION
1-2 CyberCat 254/1016 Installation Manual UL S2203
Rev 14, 09/2015 P/N: 06-326 FM
1.4 TERMS USED IN THIS MANUAL
The following are various terms used in this manual with a brief description of each.
Ω
- Symbol for “ohm”. Unit of resistance.
AC Normal State - (“AC Normal” Green LED ON) The system is in the AC Normal state when
appropriate AC power is being applied to the system.
Alarm State - (“Alarm” Red LED ON, Piezo pulsing) The alarm occurs when an input circuit
configured for alarm operation has been activated. Activation typically initiated by a detector or
contact device. The alarm state is a latching event in the CyberCat. The operator will be required to
RESET the CyberCat in order for the panel to exit/clear the alarm state.
Class A – A circuit that includes a redundant path that ensures operational capability past a single
open.
Class X – A circuit that includes a redundant path that ensures operational capability past a single
open or short-circuit. Requires the use of isolator style devices on the signaling line circuit.
Class B – A circuit that does not include a redundant path and where the operational capability stops
at a single open.
Initiating Device - A system component that originates transmission of a change-of-state condition,
such as in a smoke detector, manual fire alarm box, or supervisory switch. This manual interchanges
the terms initiating device and input device.
Initiating Device Circuit A circuit to which automatic or manual initiating devices are connected
where the signal received does not identify the individual device operated. This manual interchanges
the terms initiating device circuit and input circuit.
Normal State - (“Trouble” Yellow LED OFF). The system is in the normal state when the power
supply and all circuits are configured properly, connected, and responding properly. The system
remains in normal state until a trouble condition occurs.
Notification Appliance - A fire alarm system component such as a bell, horn, speaker, light, or
textual display that provides audible, tactile, or visible output, or any combination thereof. The device
notifies building occupants of system status. This manual interchanges the terms notification and
audible appliance.
Notification Appliance Circuit - A circuit or path directly connected to a notification appliance(s).
This manual interchanges the terms notification appliance circuit and audible circuit.
Non-Power-Limited - A circuit designation given for wiring purposes. The amount of current flowing
through the circuit is unlimited vs. being limited, or power-limited. AC power and Battery wiring is
non-power-limited.
Power-Limited - A circuit designation given for wiring purposes. The amount of current flowing
through the circuit is limited (typically by fuse) vs. being unlimited, or non-power-limited. The
CyberCat addressable loops and output circuits are power-limited. The circuit has a maximum power
that flows through it or it current limits and opens the circuit.
Supervisory State - (“Supervisory” Yellow LED ON, Piezo Warble).The supervisory state occurs
upon activation of a supervisory input circuit. The supervisory state is non-latching and will follow the
status of the supervisory input contact.
Trouble State - (“Trouble” Yellow LED ON, Piezo Constant). The trouble state occurs upon any
detectable condition which could impair system operation including connection problems, ground
faults, hardware problems, power problems, or configuration problems. Certain trouble conditions are
latching; others allow the system to reset upon trouble condition removal. Depending upon the type
of trouble condition, the system may or may not remain operational. When the system is in trouble
state, it is not in the normal state.

1.0 INTRODUCTION
UL S2203 CyberCat 254/1016 Installation Manual 1-3
FM P/N: 06-326 Rev 14, 09/2015
1.5 RELATED DOCUMENTATION
To obtain a complete understanding of the specific features of the CyberCat or to become familiar with related
functions in general, refer to the documentation listed below. Please reference the most current version or
the version noted on the label located on the product.
Exhibit 1-1: Related Documentation
Document Title Part Number
DACT (P/N 10-2528 & 10-2476) Installation Instructions
06-479
Supplemental Power Supply (P/N 10-2474-P) Installation Instructions
06-340
Supplemental Loop Module (P/N 10-2473) Installation Instructions
06-339
Relay Module (P/N 10-2204) Installation Instructions
06-345
Reverse Polarity Module (P/N 10-2254) Installation Instructions
06-156
RS485 Network Module (P/N 10-2482) Installation Instructions
06-349
Fiber Optic Network Module (P/N 10-2624) Installation Instructions
06-387
Remote Display Unit Product Manual
06-610
Ethernet Module (P/N 10-074) Product Manual
06-388
Multi-Interface Module (P/N 10-2583) Product Manual
06-367
Intelligent Graphic Annunciator Product Manual
06-231
Firefighter’s Smoke Control Station Product Manual
06-447
Twenty Zone Remote Annunciator (P/N 10-2667) Product Manual
06-453
Six Zone Smoke Control Switch Card (P/N 10-2658) Product Manual
06-444
Input/Output Switch Card (P/N 10-2659) Product Manual
06-446
Twenty Zone Annunciator Card (P/N 10-2660) Product Manual
06-445
Solenoid Supervision and Protection Assembly (P/N 10-2360) Installation
06-344
Masterbox Supervisor (P/N 10-2413) Installation Instructions
06-229
VESDA Network Interface (P/N 68-023) Product Manual
06-158
Hand Held Programmer (P/N 10-2648) Operating Instructions
06-390
C-Linx Panel Configuration Software Manual
06-327
Standard Enclosure Installation Instructions
06-480
Solid Dead-front Door Installation Instructions
06-477
3 Module Dead-front Door Installation Instructions
06-478
Emergency Voice Alarm System Product Manual
06-557
Audio Control Card (P/N 10-2661) Product Manual
06-558
Fire-Phone Card (P/N 10-2728) Product Manual
06-559
Supplemental Fire-Phone Card (P/N 10-2730) Product Manual
06-560
Fire Command Center Enclosure Installation Instructions
06-570
Fire Command Center Enclosure, Option 2 Back-Box, Installation Instructions
06-607
Dead-Front Cover Plate, Installation Instructions
06-601
Relay Mounting Plate, Installation Instructions
06-619
Remote Audio Enclosure (1 Amp) Installation Instructions
06-597
Remote Audio Enclosure (3 Amp) Installation Instructions
06-572
Remote Audio Enclosure (5 Amp) Installation Instructions
06-573

1.0 INTRODUCTION
1-4 CyberCat 254/1016 Installation Manual UL S2203
Rev 14, 09/2015 P/N: 06-326 FM
Exhibit 1-2: Related Documentation – Continued
Document Title Part Number
Fire-Phone Housing Installation Instructions
06-568
FCC Microphone Housing (P/N 10-2757) Installation Instructions
06-569
Class A Speaker Card (P/N 10-2746) Installation Instructions
06-574
FCC Paging Control Card (P/N 10-2741) Installation Instructions
06-575
Amplifier Card (P/N 10-2773) Product Manual
06-576
HPM4 Relay Module (P/N 10-2770) Installation Instructions
06-443
Relay Control Assembly (P/N 10-2777) Installation Instructions
06-580
Relay Card (P/N 10-2785) Installation Instructions
06-586
3 Card Remote Equipment Enclosure (P/N 10-2780) Installation Instructions
06-590
5 Card Remote Equipment Enclosure (P/N 10-2781) Installation Instructions
06-591
Surge Suppressor Compatibility Document
06-588
FCC Digital Paging Assembly (P/N 10-2751) Product Manual
06-564
LOC Digital Paging Assembly (P/N 10-2814) Product Manual
06-613
LOC Enclosure (P/N 10-2793) Installation Instructions
06-599
LOC Enclosure w/ RDU (P/N 10-2796) Installation Instructions
06-600
LOC Paging Control Card (P/N 10-2798) Installation Instructions
06-602
LOC Microphone Housing (P/N 10-2813) Installation Instructions
06-603
Remote Display Enclosure (P/N 10-2794) Installation Instructions
06-598
Device Compatibility Document
06-186
Class A Peripheral Bus Card (P/N 10-2792) Installation Instructions
06-606
Class A Peripheral Bus Card Assembly (P/N 10-2818) Installation Instructions
06-609
Local Operating Console (P/N 10-2800) Component List
06-634
Local Operating Console w/ RDU (P/N 10-2801) Component List
06-635
Audio Adjunct Panel (P/N 10-2831) Component List
06-636
Audio Adjunct Panel (P/N 10-2832) Component List
06-637
Conventional Zone Module (CZM) Compatiblity Document
06-467
Solenoid Disconnect Switch (P/N 10-2705 & 10-2706)
06-471

2.0 SYSTEM OVERVIEW
UL S2203 CyberCat 254/1016 Installation Manual 2-1
FM P/N: 06-326 Rev 14, 09/2015
2.1 SYSTEM DESCRIPTION
The Fike CyberCat (P/N 10-064/10-066) is a state of the art, true addressable peer-to-peer fire alarm control
system. It provides the latest technology in detection communication with extensive programmability in one
cost effective system. Its Cyber intelligence has every device communicating as a peer on the signaling line
circuit. This intelligence provides speed with response times as little as one-quarter second between manual
pull station activation to notification appliance sounding.
Its Cat-like flexibility provides you the freedom to attach the devices you require for your specific installation.
The CyberCat 254 (P/N 10-066) is equipped with one signaling line circuit capable of communicating with 254
devices in any combination. The CyberCat 1016 (P/N 10-064) is equipped with two signaling line circuits,
each capable of communicating with 254 devices in any combination. An optional loop card can be added to
the CyberCat 1016 to increase the total number of signaling line circuits to four. This increases the total
system capacity to 1,016 devices.Each CyberCat is capable of being networked (up to 128 panels total)
providing 130,048 devices total.
Exhibit 2-1: Example CyberCat Block Diagram

2.0 SYSTEM OVERVIEW
2-2 CyberCat 254/1016 Installation Manual UL S2203
Rev 14, 09/2015 P/N: 06-326 FM
2.1.1 CYBERCAT FEATURES
GENERAL
♦Two 24V DC, 2A NAC (audible) circuits on main board
with integrated synchronization
♦Available with and without integral
SERIAL, Point ID
DACT interface
♦253 user defined zones
♦Removable terminal blocks for field wiring
♦80 character, backlit LCD display
♦Local piezo with distinct event tones
♦Real time clock
♦10 Status LED’s to easily identify system status
♦3200 event history buffer
♦Compatible with internal or external Firefighter’s Smoke
Control Station Modules
♦Critical process monitoring
♦One-person Walktest capability
♦Supports ability to network up to 128 nodes (each could
be CyberCat 254 or 1016)
♦Disable by point/circuit or zone
♦Drill function at panel and remote
♦
Emergency Voice/Alarm Communication via panel’s
RS485 peripheral bus
♦Provides solenoid releasing operation
♦Alarm verification
♦Supports up to 31 peripheral devices (i.e. Remote
Display, LED Graphics, and Smoke Control Switch
Cards)
♦Easy to add/remove devices
♦Diagnostic menus
♦Approved Security Function for FIPS PUB 140-2: NO ENCRYPTION EMPLOYED
- Communication Security: Level 0
- Stored Data Security: Level 0
- Access Control Security: Level 0
- Physical Security: Level 1
- Audit Control: Not Provided
POWER
♦6 amps useable alarm power, 2A standby- CyberCat 1016 expandable to 12 amps alarm power, 4 A standby
♦Operation from 120VAC/ 60 Hz or 240VAC 50 /60Hz
♦Two 24V DC, 2A continuous auxiliary power outputs (CyberCat 1016 Expandable to 5 circuits with SPS)
♦One 24V DC, 2A resettable auxiliary power output
♦Supports up to 75 AH of batteries, CyberCat 1016 expandable to 150 AH using SPS
SIGNALING LINE CIRCUIT
♦Address devices with Infrared (IR) tool, similar to remote control device, non-listed.
♦CyberCat 254 = One addressable loop, 254 devices per loop.
♦CyberCat 1016 = Two addressable loops expandable to four, 254 devices per loop, maximum 1016 devices.
♦Loops can be wired NFPA Class B, A or X with isolator devices.
♦True peer-to-peer digital protocol for extremely fast and reliable communications
♦Addressable Device “learn” and “auto-program” functions
♦Automatic day/night sensitivity adjustment
♦Automatic holiday sensitivity adjustment
♦New Acclimate operation for detectors
♦IR Tool provides ability to read sensitivity levels or perform remote test of device
♦Devices contain multi-color LED for quick reference of device status
♦Detectors provide early warning pre-alarm detection and can also provide a summing feature (up to 8 detectors), non-
listed.
♦Sounder or Relay Bases fully programmable
♦Optional Remote LED can be added to a detector base, programmable for any device, zone/state
ENCLOSURE
♦Three enclosures sizes are available to suit system requirements
♦Enclosures are equipped with a 0.50” wide lip to facilitate flush mounting
♦Removable door and dead-front panel options for ease of installation
♦Internal dead-front door options available
♦Available in Red or Black

2.0 SYSTEM OVERVIEW
UL S2203 CyberCat 254/1016 Installation Manual 2-3
FM P/N: 06-326 Rev 14, 09/2015
2.1.2 LISTINGS AND APPROVALS
Approval Agency File Number
Underwriters Laboratories S2203
Type: Local, Remote Station (PPU), Central Station (PPU), Proprietary Supervising Station
(PPU/SSU), Auxiliary Local Energy (PPU)
Service Type: A-Automatic Fire Alarm, M-Manual Fire Alarm, Releasing Device Service, WF-Water-
flow alarm, SS-Sprinkler Supervisory Service, DACT, Voice Evacuation and
Emergency Communication Systems
Type Signaling: Non-coded
Factory Mutual (FM) Approved
California State Fire Marshall (CSFM) 7165-0900:137
City of New York (COA) #6119
City of Denver Approved
City of Chicago Approved
2.1.3 AGENCY STANDARDS AND COMPLIANCE
This Fire Alarm Control Panel complies with the following NFPA and UL standards:
NFPA 72 – National Fire Alarm Code
NFPA 92A – Smoke Control Systems
NFPA 92B – Smoke Management in Malls, Atria and Large Spaces
International Fire Code Section 909 – Smoke Control Systems
UL 864 – Standard for Control Units and Accessories for Fire Alarm Systems
UL 1711 – Amplifiers for Fire Protective Signaling Systems
UL 2572 – Mass Notification Systems
UL 2017 – General Purpose Signaling Devices and Systems
The installer should also be familiar with the following documents and standards:
National Fire Protection Association (NFPA) Codes:
NFPA 13 – Sprinkler Systems
NFPA 15 – Water Spray Fixed Systems
NFPA 16 – Deluge, Foam-water and Foam-water Spray Systems
NFPA 70 – National Electrical Code (NEC)
NFPA 70 - Article 300 – Wiring Methods
NFPA 70 - Article 760 – Fire Protective Signaling Systems
NFPA 72 – National Fire Alarm Code
NFPA 101 – Life Safety Code
NFPA 110 – Emergency Standby Power Systems
Underwriters Laboratories (UL) Standards:
UL 38 – Manually Actuated Signaling Boxes
UL 217 – Smoke Detectors, Single and Multiple Station
UL 228 – Door Closers – Holders for Fire Protective Signaling Systems
UL 268 – Smoke Detectors for Fire Protective Signaling Systems
UL 268A – Smoke Detectors for Duct Applications
UL 346 – Waterflow Indicators for Fire Protective Signaling Systems
UL 464 – Audible Signaling Appliances
UL 521 – Heat Detectors for Fire Protective Signaling Systems
UL 1481 – Power Supplies for Fire Protective Signaling Systems
UL 1638 – Visual Signaling Appliances
UL 1971 – Visual Signaling Appliances
Factory Mutual (FM) Standards:
FMRC 1011 and 1012 – Deluge and Pre-action Sprinkler Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction

2.0 SYSTEM OVERVIEW
2-4 CyberCat 254/1016 Installation Manual UL S2203
Rev 14, 09/2015 P/N: 06-326 FM
2.1.4 MINIMUM SYSTEM CONFIGURATIONS
Exhibit 2-2: MINIMUM SYSTEM CONFIGURATIONS
This table indicates the minimum components needed to meet the intended
applications.
Y = Yes
N = No
O = Optional
Protected Premises
(Local)
Central Station (PPU)
Remote Supervising
Station (PPU)
Proprietary Supervising
Station (PPU/SSU)
Auxiliary - Local Energy
(PPU)
Releasing Service
(Sprinkler)
Emergency
Communication Sys.
UL Listed
FM Approved
Part Number
Description
10-2525/2472
CyberCat 254/1016 Controller
Y
Y
Y
Y
Y
Y
Y
Y
Y
10-2483
CyberCat 1016 Enclosures
Y
Y
Y
Y
Y
Y
Y
Y
Y
10-2527 CyberCat 254 Enclosures Y Y Y Y Y Y Y Y Y
02-10881 (Note 1)
120VAC Primary Transformer
Y
Y
Y
Y
Y
Y
Y
Y
Y
10-2772 CyberCat 254/1016 Controller with 25 card deadfront Y Y Y Y Y Y Y Y Y
02-10882 (Note 1)
240VAC Primary Transformer
O
O
O
O
O
O
O
Y
Y
10-2528 (Note 2)
5-Zone DACT (Bosch FPT-DACT-LC), internal
O
Y
Y
O
O
O
O
Y
Y
10-2476 (Note 2)
5-Zone DACT (Bosch FPT-DACT), external
O
O
O
O
O
O
O
Y
Y
10-2474 (Note 3)
Supplemental Power Supply (SPS)
O
O
O
O
O
O
O
Y
Y
10-2473 (Note 3)
Supplemental Loop Module (SLM)
O
O
O
O
O
O
O
Y
Y
10-2204
CRM4 Relay Module
O
O
O
O
O
O
O
Y
Y
10-2254
CRPM Reverse Polarity Module
O
O
Y
O
O
O
O
Y
Y
10-2482
Network Module (RS485)
O
O
O
O
O
O
O
Y
Y
10-2624
Multi-Mode Fiber Optic Network Module
O
O
O
O
O
O
O
Y
Y
10-2792 (Note 4) Class A Peripheral Bus Card O O O O O O O Y Y
10-2646
14 Button Remote Display
O
O
O
O
O
O
O
Y
Y
10-2631
10 Button Remote Display
O
O
O
O
O
O
O
Y
Y
10-2630
2 Button Remote Display
O
O
O
O
O
O
O
Y
Y
68-023
VESDA Open Protocol High Level Interface (HLI)
O
O
O
O
O
O
O
Y
Y
10-2627
Ethernet Module
O
O
O
Y
O
O
O
Y
Y
10-2583
Multi-Interface Module
O
O
O
Y
O
O
O
Y
Y
10-1XX
Intelligent LED Graphic Annunciator
O
O
O
O
O
O
O
Y
Y
10-2XX
Firefighter’s Smoke Control Station (FSCS)
O
O
O
O
O
O
O
Y
Y
10-2667
20-Zone Remote Annunciator
O
O
O
O
O
O
O
Y
Y
10-2658 Six Zone Smoke Control Card O O O O O O O Y Y
10-2659
Input/Output Control Card
O
O
O
O
O
O
O
Y
Y
10-2660 Twenty Zone Annunciator Card O O O O O O O Y Y
10-2661
Audio Control Card
O
O
O
O
O
O
O
Y
Y
10-2728
Fire-Phone Card
O
O
O
O
O
O
O
Y
Y
10-2730
Supplemental Fire-Phone Card
O
O
O
O
O
O
O
Y
Y
10-2773-p (Note 5) Amplifier Kit (p: 1 = 120 VAC; 2 = 240 VAC) O O O O O O Y Y Y
10-2797
Remote Audio Enclosure, Single AMP
O
O
O
O
O
O
O
Y
Y
10-2754
Remote Audio Enclosure, Three AMP
O
O
O
O
O
O
O
Y
Y
10-2755
Remote Audio Enclosure, Five AMP
O
O
O
O
O
O
O
Y
Y
10-2746
Class A Speaker Card
O
O
O
O
O
O
O
Y
Y
10-2751 (Note 6)
FCC Digital Paging Assembly
O
O
O
O
O
O
Y
Y
Y
Notes: 1. Only one transformer (120VAC or 240VAC) can be used.
2. DACT must be purchased from Fike for proper operation with the CyberCat panel.
3. Available on CyberCat 1016 only.
4. Included in 10-080 Class A Peripheral Bus Assembly.
5. Amplifier Card (P/N 10-2726) is included as part of this assembly.
6. FCC Digital Paging Card (P/N 10-2727), Paging Control Card(P/N 10-2741, and Microphone Housing (P/N 10-2757) is
included as part of this assembly.

2.0 SYSTEM OVERVIEW
UL S2203 CyberCat 254/1016 Installation Manual 2-5
FM P/N: 06-326 Rev 14, 09/2015
Exhibit 2-2: MINIMUM SYSTEM CONFIGURATIONS – CONT.
This table indicates the minimum components needed to meet the intended
applications.
Y = Yes
N = No
O = Optional
Protected Premises
(Local)
Central Station (PPU)
Remote Supervising
Station (PPU)
Proprietary Supervising
Station (PPU/SSU)
Auxiliary - Local Energy
(PPU)
Releasing Service
(Sprinkler)
Emergency
Communication Sys.
UL Listed
FM Approved
Part Number
Description
10-2814 (Note 1)
LOC Digital Paging Assembly
O
O
O
O
O
O
O
Y
Y
10-2800 (Note 2) Local Operating Console (LOC) O O O O O O O Y Y
10-2801 (Note 2)
Local Operating Console (LOC) with RDU
O
O
O
O
O
O
O
Y
Y
10-2831
Audio Adjunct Panel (AAP1), 1 AMP
O
O
O
O
O
O
O
Y
Y
10-2832
Audio Adjunct Panel (AAP3), 3 AMP
O
O
O
O
O
O
O
Y
Y
63-1052
Photoelectric Detector
O
O
O
O
O
O
O
Y
Y
63-1058
Photoelectric Detector, Isolator Version
O
O
O
O
O
O
O
Y
Y
67-033
Ionization Detector
O
O
O
O
O
O
O
Y
Y
67-034 Ionization Detector, Isolator Version O O O O O O O Y Y
63-1053
Combination Photo/135°F Heat Detector
O
O
O
O
O
O
O
Y
Y
63-1059
Combination Photo/135°F Heat Detector, Isolator Version
O
O
O
O
O
O
O
Y
Y
60-1039 Heat Detector, 135°F-190°F (57-88°C) FT/RR O O O O O O O Y Y
60-1040
Heat Detector, 135°F-190°F (57-88°C) FT/RR, Isolator
O
O
O
O
O
O
O
Y
Y
68-140
FAAST Aspirating Smoke Detector
O
O
O
O
O
O
O
Y
Y
68-302
FAAST XT Aspirating Smoke Detector
O
O
O
O
O
O
O
Y
Y
63-1054 (EBF)
Detector Base, 6-inch
O
O
O
O
O
O
O
Y
Y
63-1060 (EBFI)
Detector Base, 6-inch, Isolator Version
O
O
O
O
O
O
O
Y
Y
63-1055 (EB)
Detector Base, 4-inch
O
O
O
O
O
O
O
Y
Y
63-1061 (EBI) Detector Base, 4-inch, Isolator Version O O O O O O O Y Y
63-1064 (EBS)
Sounder Base, 6-inch
O
O
O
O
O
O
O
Y
Y
63-1063 (EBR)
Relay Base, 6-inch
O
O
O
O
O
O
O
Y
Y
55-045 (Note 3) MMM – Mini Monitor Module O O O O O Y O Y Y
55-050 (Note 3)
MMM – Mini Monitor Module, Isolator Version
O
O
O
O
O
Y
O
Y
Y
55-041 (Note 3)
MM – Monitor Module 4-inch
O
O
O
O
O
Y
O
Y
Y
55-046 (Note 3)
MM – Monitor Module 4-inch, Isolator Version
O
O
O
O
O
Y
O
Y
Y
55-056
Dual Monitor Module
O
O
O
O
O
O
O
Y
Y
55-061
Dual Monitor Module, Isolator Version
O
O
O
O
O
O
O
Y
Y
20-1063
APS – Addressable Pull Station
O
O
O
O
O
O
O
Y
Y
20-1064 APS – Addressable Pull Station, Isolator Version O O O O O O O Y Y
55-055
Conventional Zone Monitor Module
O
O
O
O
O
O
O
Y
Y
55-060
Conventional Zone Monitor Module, Isolator Version
O
O
O
O
O
O
O
Y
Y
55-042 SCM – Supervised Control Module O O O O Y Y O Y Y
55-047
SCM – Supervised Control Module, Isolator Version
O
O
O
O
Y
Y
O
Y
Y
10-2360
Series Solenoid Diode/Resistor
O
O
O
O
O
Y
O
Y
Y
10-2413 Masterbox Interface O O O O Y O O Y Y
55-043
RM – Relay Module
O
O
O
O
O
O
O
Y
Y
55-048
RM – Relay Module, Isolator Version
O
O
O
O
O
O
O
Y
Y
63-1057
Photo Duct Detector
O
O
O
O
O
O
O
Y
Y
63-1062 Photo Duct Detector, Isolator Version O O O O O O O Y Y
63-1158
Duct Detector Housing (isolator base)
O
O
O
O
O
O
O
Y
Y
24-135
Fire-Phone Module
O
O
O
O
O
O
O
Y
Y
Notes: 1. LOC Digital Paging Card (P/N 10-2816) is included as part of this assembly.
2. LOC Digital Paging Assembly (P/N 10-2814) is included as part of this assembly.
3. Module is required to monitor sprinkler system components (e.g., Waterflow, Tamper, Low Air, etc.).

2.0 SYSTEM OVERVIEW
2-6 CyberCat 254/1016 Installation Manual UL S2203
Rev 14, 09/2015 P/N: 06-326 FM
Exhibit 2-2: MINIMUM SYSTEM CONFIGURATIONS – CONT.
This table indicates the minimum components needed to meet the intended
applications.
Y = Yes
N = No
O = Optional
Protected Premises
(Local)
Central Station (PPU)
Remote Supervising
Station (PPU)
Proprietary Supervising
Station (PPU/SSU)
Auxiliary - Local Energy
(PPU)
Releasing Service
(Sprinkler)
Emergency
Communication Sys.
UL Listed
FM Approved
Part Number
(isolator version)
Description
10-2154
Battery Enclosure, 33 AH maximum
O
O
O
O
O
O
O
Y
Y
10-2236
Battery Enclosure, 75 AH maximum
O
O
O
O
O
O
O
Y
Y
10-2780
Remote Equipment Enclosure, 3 Card
O
O
O
O
O
O
O
Y
Y
10-2781 Remote Equipment Enclosure, 5 Card O O O O O O O Y Y
10-2770
HPM4 Relay Card
O
O
O
O
O
O
O
Y
Y
10-2777
Relay Control Assembly
O
O
O
O
O
O
O
Y
Y
10-2785 Relay Card O O O O O O O Y Y
Other manuals for CyberCat 1016
2
This manual suits for next models
1
Table of contents
Other Fike Control System manuals

Fike
Fike 10-2539 Owner's manual

Fike
Fike 10-071 User manual

Fike
Fike Cheetah Xi User manual

Fike
Fike CyberCat 50 10-070 Manual

Fike
Fike Epaco User manual

Fike
Fike CyberCat 1016 Manual

Fike
Fike Cheetah Xi User guide

Fike
Fike CyberCat 1016 Owner's manual

Fike
Fike 55-042 User manual

Fike
Fike FIK-CZ-6 User manual