BEFORE INSTALLING
This pull station must be installed in compliance with the control panel sys-
tem installation manual, the SWIFT Wireless Gateway Manual, applicable
NFPA standards, national and local Fire codes and the requirements of the
AHJ (Authority Having Jurisdiction). Regular testing of the devices should be
done in accordance with the appropriate NFPA standards. Pull stations offer
maximum performance when installed in compliance with the National Fire
Protection Association (NFPA); see NFPA 72.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The FIK-W-PULL-DA wireless, addressable pull station is a UL38-compliant
dual-action manual pull station with a key-lock reset feature intended for
use with a wireless gateway or wireless fire alarm control panel (FACP). (See
Figure 1.) It provides Fike panels one addressable alarm initiating input. The
device communicates through a robust, bi-directional mesh network to the
gateway and/or FACP. Rotary dial switches are provided for setting the pull
station’s address. (See Figure 2.) Operating instructions are molded into the
pull station handle along with Braille text. The wireless pull station meets
the Americans with Disabilities Act Accessibility Guidelines (ADAAG) controls
and operating mechanisms guidelines (section 4.1.3[13]), the Americans with
Disabilities Act (ADA) requirement for a 5 lb. maximum pull force to activate
the pull station and conforms to ANSI/UL Standard 38.
Panels offer different feature sets across the various models. As a result, cer-
tain features may be available on some control panels, but not on others. The
possible feature sets available with the wireless pull station include:
• An LED on the wireless pull station is controlled by the panel to indicate
device status. Operational modes include red, green and amber colors in
various solid or blink patterns.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Fike system control panel (list available from Fike).
FIGURE 1. WIRELESS MANUAL PULL STATION
C2039-00
BATTERY DOOR
The battery door includes a magnet for activation and tamper resistance. (See
Figure 2.) The battery door magnet activates communication to the panel,
therefore, the battery door must be installed and closed for the pull station
to work properly. The magnet also activates a tamper fault at the panel if the
battery door is opened. Do NOT remove this magnet.
BATTERY REPLACEMENT
Low battery levels on the wireless devices are displayed as a trouble in the
FACP. Therefore when the message “TROUBLE BATTERY LOW” is displayed,
replace the battery in the device. This message is an indication that approxi-
mately one week of battery life remains.
To replace the batteries in a wireless device use the following steps:
1. Have 4 CR123A (or DL123A) batteries available.
2. Use the key to unlock and open the pull station door.
3. Open the battery compartment. (See Figure 2.)
4. Remove the used batteries and replace with new batteries. Batteries can
be inserted directly into the pull station or inserted as a set of 4 batteries
pre-loaded in a battery cartridge available from Fike. (See Figure 2.) The
battery compartment and cartridge indicate the correct orientation of the
batteries. Carefully align the batteries with these markings, and do not force
them into place.
5. Close the battery compartment cover.
6. Close and lock the pull station door.
FIGURE 2. BATTERY INSTALLATION
Rotary Address Switches
Battery Compartment With Door Open
Battery Compartment Door in the Open (Down) Position
Battery
Magnet
Location
Battery Compartment Door in the Closed (Up) Position
C2041-00
Battery Cartridge
C2030-00
SPECIFICATIONS
Maximum Operating Voltage: 3.3 VDC
Maximum Current Draw: 5.0 mA (LED on)
Average Operating Current: 210 µA
Maximum Transmit RF Power: 17 dBm
Radio Frequency Range: 902-928 MHz
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10% to 93% Non-condensing
Battery Type: 4 Panasonic CR123A or 4 Duracell DL123A
Battery Life: 2 year minimum
Battery Replacement: Upon TROUBLE BATTERY LOW display and/or during annual maintenance
Dimensions: 5.6" (142 mm) H x 4.2" (107 mm) W x 2.1" (53 mm) D
Accessories: Battery Cartridge W-BATCART
I56-6964-001
INSTALLATION AND MAINTENANCE INSTRUCTIONS
R
704 SW 10th Street
Blue Springs, MO 64015
Phone: 816.229.3405; Fax: 816.228.9277
www.fike.com
FIK-W-PULL-DA Wireless Pull Station
http://www.fike.com/06-912
Fo
r system/product documentation including
installation, operation, and maintenance,
scan QR code or enter URL provided.
1 I56-6964-001
10/5/2021