26-0947 Issue 10
31/07/18
Smoke mode 3 requires that the concentration of smoke is kept up for a longer period to trigger the device into alarm, so patience
is required. Small regular applications of test smoke are best in order to avoid drenching the detector as this may result in sticky
residues being left behind.
Technical Data
Dimensions ..............................................................................107mm diameter x 75mm
Operating temperature ..............................................................................-10oC to +50oC
Operating Voltage Range ..............................................................................18V to 32V DC
Operating Current Quiescent ..............................................................56 uA (Typical)
End of line ON if applicable....................................+50 uA (Typical)
(no strobe version) Alarm Sounding – Sounder High............................8.00 mA (Typical)
Alarm Sounding – Sounder Low.............................2.50 mA (Typical)
Alarm Sounding – Sounder Off ..............................150 uA (Typical)
Alarm Activated......................................................15.50 mA (Typical)
(in addition to Alarm Sounding)
(strobe version) Alarm Sounding – Sounder High............................10.50 mA (Typical)
Alarm Sounding – Sounder Low.............................4.90 mA (Typical)
Alarm Sounding – Sounder Off ..............................2.60 mA (Typical)
Alarm Activated......................................................18.00 mA (Typical)
(in addition to Alarm Sounding)
LED Operation Detector in Normal State (Smoke)..........................Flash at 20 second intervals
Detector in Normal State (Heat).............................Double flash at 20 second intervals
Detector at EOL.....................................................Flash at 5 second intervals
Detector in Fault. ...................................................Flash at 1.3 second intervals
Detector Detecting Fire..........................................Flash at 0.7 second intervals
Detector in Fire (once processed at panel) ............Continuous
Loading Units V3 Panel: Pro Panel:
Max Loading Units per zone ..................................27 SLU..............160 DLU
(no strobe version) Sounder High.........................................................1.35 SLU...........8.0 DLU
Sounder Low .........................................................1.125 SLU.........6.5 DLU
No Sounder ...........................................................0.5 SLU.............1.0 DLU
(strobe version) Sounder High.........................................................2.7 SLU.............16.0 DLU
Sounder Low .........................................................1.35 SLU...........8.0 DLU
No Sounder ...........................................................1.35 SLU...........8.0 DLU
Volume Level Sounder High.........................................................90+ dB(A) (For more information on sound output
(@ 1m anechoic, Dual Tone) Sounder Low .........................................................70+ dB(A) contact your supplier Ref 26-0747)
Flammability ..............................................................................UL94-V2
IP Rating ..............................................................................IP 21C
Part Codes No Sounder ...........................................................204 0003
With Sounder.........................................................204 0001
With Sounder and Strobe.......................................204 0012
Product CPR Number
204-0003 0832-CPR-F0123
204-0001 0832-CPR-F0124
204-0012 0832-CPR-F0125
0832
Fike Safety Technology Ltd
Unit 31, Springvale Ind. Est.
Torfaen, NP44 5BD
14
DoP-204-0001, DoP-204-0003, DoP-204-0012
EN54-3: 2001 +A1: 2002 +A2: 2006, EN54-5 : 2000 +A1: 2002,
EN54-7: 2000 +A1: 2002 +A2: 2006,
Sounder Technical Data: See 26-0747
204-0001, 204-0003, 204-0012
Intended for use in the fire detection and fire alarm
Systems in and around buildings
Essential characteristics
Nominal activation conditions / Sensitivity, Response
delay (response time) and Performance under fire
Pass
Tolerance to supply voltage
Durability of operational reliability and response delay,
Temperature resistance
Pass
Durability of operational reliability, Vibration resistance
Durability of operational reliability, Humidity resistance
Durability of operational reliability, Corrosion resistance
Durability of operational reliability, Electrical stability
Durability of operational reliability, Resistance to ingress
Contact your supplier for technical support on this product.
Due to the complexity and inherent importance of a life risk type
system, training on this equipment is essential, and commissioning
should only be carried out by competent persons. Fike cannot
guarantee the operation of any equipment unless all documented
instructions are complied with, without variation. This unit complies
with the EMC directive.
Fike’s policy is one of continual improvement and the right to change
a specification at any time without notice is reserved. Whilst every
care has been taken to ensure that the contents of this document are
correct at time of publication, Fike shall be under no liability
whatsoever in respect of such contents. E&OE.