General Description
The Twinex Soundpoint unit allows for audible indication when the system enters an alarm
condition. This device is compatible with the Twinex 2-wire range of Fire Alarm equipment
and comprises a 2-wire zone-powered sounder. This device may be installed on the same
zone as the Multipoint detector/sounder and associated Twinex devices.
Before Installation
The MCP must be installed in compliance with the control panel installation manual.
The installation must also meet the requirements of any local authority.
Spacing
Fike recommends spacing of call points in accordance with any local authority.
Device Installation
Surface Mounting
Fix the surface back box to a at vertical surface using at least two of the four mounting
holes provided. The back box may be drilled to allow cable access as required. A
20mm hole is already provided at the rear. Zone cabling may be connected to the
terminals in the back box.
Flush Mounting
The Soundpoint may be ush mounted utilising the optional adaptor plate, combined
with any standard single gang ush mounting back box (with a minimum internal depth
of 47mm).
After installing the back box securely, attach the adaptor plate using the two screws
provided, and terminate your cables directly into a ying terminal block.
Installation 2nd Fix
Once all testing has been carried out on the cabling and ‘continuity & integrity’ has
been proven, the Soundpoint front may be installed.
Connect the wires from the Soundpoint front in to the appropriate terminals in the
back box according to the wire colours. The Soundpoint front may then be installed by
locating the upper mounting hooks into the back box and then pushing the unit gently
home. The single xing screw may then be tightened as required.
Please remember that all high voltage testing must be carried out before the installation
of the Soundpoint front unit, otherwise the electronics will be damaged.
313-0021(RED) 313-0022(WHITE) TWINFLEX SOUNDPOINT

Document No. 26-0510 Issue 9
Subject to change
Connections
Twinex Soundpoints can be mixed on the same zone as other types of Twinex device (eg. Twinex Multipoint
Detectors). The above diagram shows how to make the zone positive, zone negative and screen connections between
the control panel and Twinex Soundpoints. Refer to the instruction leaets supplied with other Twinex devices for their
equivalent wiring/terminal labelling details.
Please note that the E terminal on the Soundpoints should only be connected to the zone cable screen and NOT to the
building earth. The cable screen is connected to earth at the panel end only, via the zone “SCRN” terminal (or EARTH
terminal on the Twinex V3 2/4/8 Zone panels). It is important to maintain the screen continuity in order to protect against
data corruption from interference.
Remember that the device at the end of the line must have its EOL signal activated using the relevant DIL
switch. Do not use a resistor or capacitor (or another manufacturer’s End of Line device) as the end of line, as
this may prevent correct operation of the zone.
Device Settings
The detector DIL switches may be used to program the operation of the Flashpoint Sounder / Beacon. They may be
altered when the device is removed from the base.
The last device on the circuit must have the EOL signal enabled
(switch number 1 in the ‘ON’ position).
E
BLUE RED
YELLOW
Y
B R
DIL SWITCH SETTINGS
1 2 3 4
End of line Enabled ON
Disabled OFF
Sound Levels High ON
Low OFF
Sound Patterns Sound OFF ON ON
Dual Tone UK Evacuate – 800 & 970 Hz ON OFF
Slow Whoop Up - 500 to 1200 Hz sweep up OFF OFF
Dual Tone French Warble – 440 & 550 HZ OFF ON
SWITCH OFF
SWITCH ON
1 2 3 4
O N

Fike Safety Technology Ltd
Unit 31, Springvale Industrial Estate
Cwmbran
NP44 5BD
Tel: 01633 865 558 | Email: fstinfo@ke.com Document No. 26-0510 Issue 9
Subject to change
Technical Support
Contact your supplier for technical support on this
product.
Due to the complexity and inherent importance of
a life risk type system training on this equipment is
essential, and commissioning should only be carried
out by competent persons. Fike cannot guarantee the
operation of any equipment unless all documented
instructions are complied with, without variation.
Fike’s policy is one of continual improvement and the
right to change a specication at any time without
notice is reserved. Whilst every care has been taken to
ensure that the contents of this document are correct
at time of publication, Fike shall be under no liability
whatsoever in respect of such contents. E&OE
2831
Fike Safety Technology Ltd
Unit 31, Springvale Ind. Est.
Torfaen, NP44 5BD
11
DoP-313-0021
EN54-3: 2001 +A1: 2002 +A2: 2006
Sounder Technical Data: See 26-0747
313-0021, 313-0022
Intended for use in the re detection and re alarm
Systems in and around buildings
Essential characteristics Performance
Nominal activation conditions/Sensitivity, response delay (response time)
and performance under re conditions Pass
Operational reliability Pass
Durability of operational reliability and response delay, Temperature
resistance Pass
Durability of operational reliability, Vibration resistance Pass
Durability of operational reliability, Humidity resistance Pass
Durability of operational reliability, Corrosion resistance Pass
Durability of operational reliability, Electrical stability Pass
Durability of operational reliability, Resistance to ingress Pass
Dimensions Width x Height................................................................ 89mm x 89mm
Flush Depth Protruding................................................... 34mm
Surface Depth................................................................. 62mm
Operating Temperature ....................................................................................... -10oC to +50oC
Voltage Ranges DC Output from Mains Powered Panel.......................... 25.5 to 35V DC
DC Output from Battery Powered Panel........................ 20 to 26V DC
Operating Current (Typical) Quiescent........................................................................ 185 uA
End of line ON if applicable............................................
(in addition to Quiescent) 175 uA
Alarm Sounding - Sounder High.................................... 14.5 mA
Alarm Sounding - Sounder Low..................................... 12.6 mA
Loading Units V3 Panel Pro/Pro2Panel
Max Loading Units per zone.......................................... 27 SLU 160 DLU
Sounder High................................................................. 2.5 SLU 14.5 DLU
Sounder Low.................................................................. 2.0 SLU 13.0 DLU
Sounder High................................................................. 85+ dB(A)
Sounder Low.................................................................. 65+ dB(A)
Flammability ....................................................................................... UL94-V2
IP Rating ....................................................................................... IP 21C
Technical Data