Fire-Lite Alarms MS-5024UD User manual

Fire Alarm Control Panel
MS-5024UD/MS-5024UDE
PN: 15140:G ECN 01-685
G
Document #15140
01/02/02 Revision

Precau-Lg.p65 01/18/2000
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warn-
ing devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec-
tors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emer-
gency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are de-
signed to provide early warning against fire, they do not guar-
antee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a build-
ing. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors be-
cause:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before reach-
ing the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ion-
izing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in differ-
ent ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detec-
tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a prede-
termined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire pro-
tection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys-
tem for the connection of alarm transmission wiring, communi-
cations, signaling, and/or power. If detectors are not so lo-
cated, a developing fire may damage the alarm system, crip-
pling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medica-
tion. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibil-
ity to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com-
patible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against tele-
phone line failure, backup radio transmission systems are rec-
ommended.
The most common cause of fire alarm malfunction is inade-
quate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA stan-
dards. At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed. Environments with large amounts of
dust, dirt or high air velocity require more frequent mainte-
nance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized pro-
fessional fire alarm installers only. Adequate written records
of all inspections should be kept.
While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
Fire Alarm System Limitations

Precau-Lg.p65 01/18/2000
WARNING - Several different sources of power can be con-
nected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equip-
ment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific soft-
ware. Reacceptance testing is required after any change, ad-
dition or deletion of system components, or after any modifica-
tion, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func-
tions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvert-
ently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 de-
vices, must also be tested and proper system operation veri-
fied.
This system meets NFPA requirements for operation at
0-49° C/32-120° F and at a relative humidity of 85% RH (non-
condensing) at 30° C/86° F. However, the useful life of the
system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nomi-
nal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to light-
ning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility. Overhead or outside
aerial wiring is not recommended, due to an increased sus-
ceptibility to nearby lightning strikes. Consult with the Techni-
cal Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or in-
serting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are re-
moved from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used
in accordance with the instruction manual, may cause interference to radio communications. It has been tested and
found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which
is designed to provide reasonable protection against such interference when operated in a commercial environ-
ment.
Operation of this equipment in a residential area is likely to cause interference, in which case the user will be re-
quired to correct the interference at his own expense.
FCC Warning
Installation Precautions

4Document #15140 Rev.G 01/02/02 P/N 15140:G
Notes

Document 15140 Rev. G 01/02/02 P/N: 15140:G 5
CHAPTER 1: Product Description .........................................................................................................................10
1.1: Product Features..........................................................................................................................................10
FIGURE 1-1: Optional DP-5024UD.................................................................................................... 11
FIGURE 1-2: MS-5024UD Panel ........................................................................................................12
1.2: Controls and Indicators ...............................................................................................................................13
FIGURE 1-3: Controls and Indicators .................................................................................................13
1.3: Circuits ........................................................................................................................................................13
1.4: Digital Communicator.................................................................................................................................14
1.5: Components.................................................................................................................................................14
1.5.1: Main Circuit Board ...........................................................................................................................14
1.5.2: Cabinet ..............................................................................................................................................14
1.5.3: Transformer Assembly......................................................................................................................15
FIGURE 1-4: XRM-24(E) Transformer ..............................................................................................15
1.5.4: Batteries ............................................................................................................................................15
1.6: Optional Devices .........................................................................................................................................15
1.6.1: RM-5F Five-Zone Relay Module .....................................................................................................15
1.6.2: CAC-5F Class A Converter Module .................................................................................................15
1.6.3: ADM-24 Annunciator Driver Module ..............................................................................................15
1.6.4: RZA-5F Remote Annunciator...........................................................................................................15
1.6.5: PRT-24 Printer Interface Module......................................................................................................16
1.6.6: DP-5024UD Dress Panel ..................................................................................................................16
1.6.7: BB-17F Battery Box .........................................................................................................................16
1.6.8: PK-5024UD Programming Kit .........................................................................................................16
1.7: Specifications ..............................................................................................................................................16
1.8: Telephone Requirements and Warnings ......................................................................................................18
1.8.1: Telephone Circuitry...........................................................................................................................18
1.8.2: Digital Communicator.......................................................................................................................18
1.8.3: Telephone Company Rights and Warnings .......................................................................................18
CHAPTER 2: Installation.........................................................................................................................................19
2.1: Mounting Options ......................................................................................................................................19
FIGURE 2-1: MS-5024UD Cabinet ....................................................................................................19
2.2: Backbox Mounting......................................................................................................................................19
FIGURE 2-2: Cabinet Dimensions and Knockout Locations..............................................................20
FIGURE 2-3: Backbox and Battery Box .............................................................................................21
2.3: Operating Power..........................................................................................................................................22
FIGURE 2-4: Operating Power Connections.......................................................................................22
2.4: Input Circuits...............................................................................................................................................23
FIGURE 2-5: Typical Initiating Device Circuit Connections .............................................................23
2.5: Output Circuits ............................................................................................................................................24
FIGURE 2-6: Auxiliary Power Connections .......................................................................................24
FIGURE 2-7: Notification Appliance Circuit Connections.................................................................24
FIGURE 2-8: Auxiliary Relay and Relay Driver Terminals ...............................................................25
2.6: UL Power-limited Wiring Requirements ....................................................................................................26
FIGURE 2-9: Typical Wiring Diagram for UL Power-limited Requirements ....................................26
2.7: Digital Communicator.................................................................................................................................27
FIGURE 2-10: Wiring Phone Jacks.....................................................................................................27
2.8: Optional Boards...........................................................................................................................................28
2.8.1: ADM-24 Annunciator Driver Module ..............................................................................................28
FIGURE 2-11: ADM-24 Annunciator Driver Module ........................................................................28
2.8.2: RZA-5F Remote Annunciator ..........................................................................................................28
FIGURE 2-12: RZA-5F .......................................................................................................................28
Table of Contents

Table of Contents
6Document 15140 Rev. G 01/02/02 P/N: 15140:G
FIGURE 2-13: Wiring the RZA-5F/ADM-24 .....................................................................................29
FIGURE 2-14: Installing the Annunciator (Single-Gang Electrical Box) ...........................................29
2.8.3: PRT-24 Printer Interface Module ......................................................................................................30
FIGURE 2-15: Remote Printer Connections........................................................................................30
2.8.4: RM-5F Five-Zone Relay Module......................................................................................................31
FIGURE 2-16: RM-5F Installation and Wiring ...................................................................................31
2.8.5: CAC-5F Class A Converter Module .................................................................................................32
FIGURE 2-17: CAC-5F Style D Converter .........................................................................................32
CHAPTER 3: Programming Instructions...............................................................................................................33
3.1: Entering Program Mode ..............................................................................................................................33
3.2: Switch Functions .........................................................................................................................................34
FIGURE 3-1: Control Panel Keypad ...................................................................................................34
3.3: Programming Options .................................................................................................................................34
TABLE 3-1: Primary Event Codes - 3+1, 4+1 Express, 4+1 Standard, Expanded & 4+2 Expanded.36
TABLE 3-2: Primary Event Codes - 4+2 Standard and 4+2 Express..................................................37
TABLE 3-3: Event Codes, Primary Central Station Number ..............................................................38
TABLE 3-4: Secondary Event Codes-3+1, 4+1 Express, 4+1 Standard, Expanded & 4+2 Expanded41
TABLE 3-5: Secondary Event Codes - 4+2 Standard and 4+2 Express..............................................42
TABLE 3-6: Event Codes, Secondary Central Station Number ..........................................................43
FIGURE 3-2: Verification Timing Diagram........................................................................................44
TABLE 3-7: Zone Function Selection .................................................................................................45
3.4: Default Programming ..................................................................................................................................49
CHAPTER 4: Operating Instructions ....................................................................................................................50
4.1: Switches in Normal Mode...........................................................................................................................50
4.1.1: RESET...............................................................................................................................................50
4.2: Displays .......................................................................................................................................................51
FIGURE 4-1: Phone Connectors and LEDs.........................................................................................52
4.3: Operation .....................................................................................................................................................53
4.3.1: Alarm Response ................................................................................................................................53
4.3.2: Alarm Restoral ..................................................................................................................................54
4.3.3: System Supervisory Condition Response .........................................................................................54
4.3.4: System Supervisory Restoral Response ............................................................................................54
4.3.5: Trouble Condition Response .............................................................................................................55
4.3.6: Trouble Condition Restoral ...............................................................................................................55
4.3.7: Off Normal Reporting .......................................................................................................................55
4.3.8: Zone Disable/Enable .........................................................................................................................56
4.3.9: Fire Drill............................................................................................................................................56
4.4: Central Station Communications.................................................................................................................57
TABLE 4-1: Format Selection Address (16 & 42) ..............................................................................58
TABLE 4-2: Format Selection Address Explanation...........................................................................59
4.4.1: Transmittal Priorities .........................................................................................................................60
TABLE 4-3: Compatible UL Listed Receivers....................................................................................61
CHAPTER 5: Servicing............................................................................................................................................62
5.1: Walktest Mode.............................................................................................................................................62
5.2: History Mode...............................................................................................................................................63
5.3: Troubleshoot Mode......................................................................................................................................64
5.3.1: Zone Voltages ....................................................................................................................................64
TABLE 5-1: Nominal Zone Voltages ..................................................................................................64
5.3.2: AC Line Voltage................................................................................................................................65
5.3.3: Battery Voltage ..................................................................................................................................65
5.3.4: Telephone Lines ................................................................................................................................65
FIGURE 5-1: Phone Connectors and LEDs.........................................................................................65
TABLE 5-2: AC Line Voltage Range..................................................................................................65

Document 15140 Rev. G 01/02/02 P/N: 15140:G 7
Table of Contents
TABLE 5-3: Battery Voltage...............................................................................................................65
5.3.5: NAC 1 & 2 ........................................................................................................................................66
5.3.6: Resettable Power...............................................................................................................................66
5.4: Lamp Test....................................................................................................................................................66
5.5: Print Mode...................................................................................................................................................66
CHAPTER 6: Slave Communicator Configuration ...............................................................................................67
FIGURE 6-1: Slave Communicator Connections...............................................................................68
CHAPTER 7: Remote Site Upload/Download .......................................................................................................69
7.1: Downloading Program ................................................................................................................................69
7.1.1: Security Features...............................................................................................................................70
7.2: Downloading Initiated at Control Panel......................................................................................................71
7.3: Downloading Initiated at a Service Terminal..............................................................................................71
7.4: Uploading Initiated at a Service Terminal...................................................................................................72
Appendix A: Battery Calculations .......................................................................................................................73
TABLE A-1: Battery Calculations ......................................................................................................73
A.1: The Main Power Supply ............................................................................................................................74
TABLE A-2: Filtered Load in Standby - external devices connected to TB4 only ............................74
TABLE A-3: Filtered Load in Alarm .................................................................................................75
Appendix B: Programming Reference Sheets .....................................................................................................76
Appendix C: Operation and Function Modes .....................................................................................................82
C.1: Operation Modes .......................................................................................................................................82
C.2: Function Modes ........................................................................................................................................82
TABLE C-1: Operation Modes ...........................................................................................................82
TABLE C-2: Function Modes .............................................................................................................82
Appendix D: Ademco Contact ID Format Event Code Descriptions ...............................................................83

This control panel has been designed to comply with standards set forth by the following regulatory agencies:
• Underwriters Laboratories Standard UL 864
• NFPA 72 National Fire Alarm Code for Local, Remote Station and Central Station Fire Alarm System
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Central Station Fire Alarm Systems Protected Premises Unit
(Automatic, Manual and Waterflow), Local Fire Alarm Systems (Automatic, Manual, Waterflow and
Sprinkler Supervisory), Auxiliary Protective Fire Alarm Systems (Automatic, Manual and Water-
flow), Proprietary Protective Fire Alarm Systems (Automatic, Manual and Waterflow) and Remote
Station Fire Alarm Systems (Automatic, Manual and Waterflow).
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document Document #15384
Before proceeding, the installer should be familiar with the following documents.
8 Document #15140 Rev.G 01/02/02 P/N 15140:G

Document #15140 Rev.G 01/02/02 P/N 15140:G 9
MS-5024UD Main Circuit Board

Product Description
10 Document #15140 Rev.G 01/02/02 P/N 15140:G
CHAPTER 1 Product Description
The MS-5024UD is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator
Transmitter) all on one circuit board. It is a five-zone panel which uses conventional input devices. The panel
accepts waterflow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally
open contact devices. Outputs include two NACs (Notification Appliance Circuits), alarm and trouble relays, super-
visory and communicator failure relay drivers.
The integral communicator transmits system status (alarms, troubles, AC loss, etc.) to UL-listed Central Stations via
the public switched telephone network. The control panel has a built-in programmer and may also serve as a slave
communicator to a host panel. It also supervises all wiring, AC voltage, telephone line input voltage and battery
level.
The control panel may be programmed or interrogated off-site via the public switched telephone network. Any IBM
compatible personal computer with DOS™4.01 or greater plus Windows™3.1 or greater, with a 1200 baud Hayes™
compatible modem and Fire•Lite Upload/Download software P/N PK-5024UD, may serve as a Service Terminal.
This allows download of the entire program or upload of the entire program, history file, walktest data, current status
and system voltages. The MS-5024UDE offers the same features as the MS-5024UD but allows connection to 220/
240 VAC input.
1.1 Product Features
• Selectable as Fire Panel, Fire Panel/Communicator or Slave Communicator
• Programmable Zone ID: 2-wire smoke, pull station, normally open contact device, supervisory, supervisory
autosilence, waterflow silenceable or waterflow nonsilenceable
• One Style D (Class A) zone
• Four Style B (Class B) zones
• 3.6 amps usable power expandable to 5.6 amps
• Optional 5-zone Relay Module (RM-5F)
• CAC-5F Style D (Class A) Zone Converter Module
• Two NFPA Style Y (Class B) or Style Z (Class A) Notification Appliance (bell) Circuits
• Built-in programmer
• Built-in voltmeter
• Telephone Line Active LED indicators
• Communication confirmation (Kissoff) LED
• Disable report by event
• Programmable event codes
• 24 volt operation
• Real-Time clock and calendar
• Trouble reminder
• Alarm verification
• RZA-5F remote annunciator (requires ADM-24 Annunciator Driver Module)
• Small size - 15" (38.1 cm) x 14.5" (36.83 cm) x 2.75" (6.985 cm)
• History file with 32 event storage
• Silence inhibit per NAC (Notification Appliance Circuit)
• Autosilence per NAC

Document #15140 Rev.G 01/02/02 P/N 15140:G 11
Product Features
• Touchtone/Rotary dialing
• Programmable make/break ratio
• Fuseless design
• PRT-24 (Printer Interface Module)
• Print real-time system status
• Print history and walktest files, program contents and troubleshoot mode voltages
• PK-5024UD Upload/Download Software Kit
• Number of dial attempts (minimum of 5 and maximum of 10)
• Programmable channel ID (slave)
• Programmable zone delay (waterflow only)
• Form-C alarm and trouble relays
• Supervisory and communication fail relay drivers
• Low AC voltage sense
•One-manwalktest
• Optional Dress Panel cover (DP-5024UD)
Note: Unless otherwise specified, MS-5024UD shall be used in this manual to refer to both the MS-5024UD and
MS-5024UDE Fire Alarm Control Communicators.
A
n
AC POWER
ALARM
1ST
EVENT
ENTER
STORE
1
4
7
A
2
5
8
0
3
6
9
B
F
E
D
C
RESET MODE
SILENCE
SUPERVISORY
TROUBLE
FIRE CONTROL/COMMUNICATOR
FIGURE 1-1:Optional DP-5024UD

Product Features
12 Document #15140 Rev.G 01/02/02 P/N 15140:G
1. Software for the Fire Alarm Control Communicator is located in a PROM inserted in the IC socket labeled
U23. The MS-5024UD and MS-5024UDE each contain unique software. For specific panel software infor-
mation, refer to the MS-5024UD(E) Field Software Change Procedure Document #50125.
FIGURE 1-2:MS-5024UD Panel
Alarm &
Trouble
Relays
5 Input
Zones Primary & Secondary Phone Lines
Notification Appliance
Circuits
Annunciator
Driver Module
Interface
Connector
Relay Module
Interface
Connector
PROM U231
Piezo 85dB
Printer
Interface
Module
Connector
Holds up to 7 AH Batteries
Up to 60 Hrs. of Standby
Optional
Transformer
Keypad
Four Character
7-Segment LED
Display
Standard
Transformer

Document #15140 Rev.G 01/02/02 P/N 15140:G 13
Controls and Indicators
1.2 Controls and Indicators
Front Panel Switches
RESET Digits 0-9
SILENCE A
MODE B
Up Arrow C
Down Arrow D
1st EVENT E
ENTER/STORE F
Displays
• Alarm - red LED
• Trouble - yellow LED
• Supervisory - yellow LED
• AC Power - green LED
• Four 7-Segment Displays - red
• Primary Phone Line Active - red LED
• Secondary Phone Line Active - red LED
• 'Kissoff' Signal from Central Station - green LED
• Silence - yellow LED
• Modem - green LED
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble and supervisory conditions.
1.3 Circuits
Input Circuits
Five input circuits provide Style B configuration with one circuit also configurable for Style D. Input circuits may be
used as standard fire control panel zones or slave communicator input channels.
• Initiating Device Circuit 1 (Style B) accepts normally open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 2 (Style B) accepts normally open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 3 (Style B/D) accepts normally open contact devices, 2-wire smoke detectors and
waterflow devices
• Initiating Device Circuit 4 (Style B) accepts normally open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 5 (Style B) accepts normally open contact devices and 2-wire smoke detectors
Output Circuits
• 24 Volt Resettable Power Output
• 24 Volt Nonresettable Power Output
• Primary Telephone Line
• Secondary Telephone Line
• 24 Volt Battery Charger
•PrinterPort
FIGURE 1-3: Controls and Indicators

Digital Communicator
14 Document #15140 Rev.G 01/02/02 P/N 15140:G
Notification Appliance Circuits
Two Notification Appliance Circuits configurable for Style Y (Class B) or Style Z (Class A) with various program-
mable features.
Relays
Two dry Form-C relay contacts for system alarm and system trouble are provided. Contacts are rated 2 amps @ 30
VDC and 0.5 amps @ 30 VAC resistive.
Relay Drivers
Two relay driver outputs for supervisory and communication failure are available.
1.4 Digital Communicator
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the
Primary and Secondary phone lines. Telephone line active red LEDs are provided as well as a green 'kissoff' LED.
The integral digital communicator provides the following functions:
• Line Seizure - takes control of the phone lines disconnecting any premises phones
• Off/On Hook - perform on and off-hook status to the phone lines
• Listen for dial tone - 440 hertz tone typical in most networks
• Dialing the Central Station(s) phone number - default is Touch-Tone®, programmable to rotary
• For tone burst or touchtone type formats: Discern proper 'Ack' and 'kissoff' tone(s). The frequency and time
duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly
• Communicate in the following formats:
✓12 Tone Burst Types (20 pps):
(3+1, 4+1, 3+1 Expanded, 4+1 Expanded and 4+2 Expanded)
✓3 Touchtone Types:
4+1 Ademco Express
4+2 Ademco Express
Ademco Contact ID
(see Table 4-3 for a list of compatible receivers)
1.5 Components
1.5.1 Main Circuit Board
The main circuit board contains the system's CPU, power supply, other primary components and wiring interface
connectors. Optional modules plug in and are mounted to the main circuit board. The main circuit board is delivered
premounted in the cabinet.
1.5.2 Cabinet
The cabinet is red with an attractive navy blue front overlay. The backbox measures 15" (38.1 cm) x 14.5" (36.83
cm) x 2.75" (6.985 cm) and provides space for two batteries (up to 7 Amp Hours). Also available is an optional dress
panel (DP-5024UD), which mounts inside the cabinet.

Document #15140 Rev.G 01/02/02 P/N 15140:G 15
Optional Devices
1.5.3 Transformer Assembly
One 100VA transformer is provided standard with the panel (3.6 amps
maximum). An optional 100VA transformer, XRM-24 (XRM-24E for
MS-5024UDE), is available to provide maximum accessory power (6.6
amps maximum).
1.5.4 Batteries
The cabinet provides space for 7 Amp Hour batteries (for 12 Amp Hour
up to 18 Amp Hour batteries, use the listed BB-17F battery box). Batter-
ies must be ordered separately.
1.6 Optional Devices
1.6.1 RM-5F Five-Zone Relay Module
The RM-5F option module provides five Form-C relays which track zones 1 through 5. The module mounts to con-
nector J7 on the lower right side of the main circuit board. Refer to Figure 1-2, “MS-5024UD Panel,” on page 12 and
Figure 2-16 on page 31.
1.6.2 CAC-5F Class A Converter Module
The CAC-5F Class A Converter module converts the Style B (Class B) Initiating Device Circuits to Style D (Class
A). The CAC-5F mounts to terminal block TB2, located in the upper center of the main circuit board. The remov-
able terminal block on the CAC-5F module provides for ease of wiring. Refer to Figure 2-17, “CAC-5F Style D Con-
verter,” on page 32
1.6.3 ADM-24 Annunciator Driver Module
The ADM-24 Annunciator Driver Module supports the RZA-5F Remote Annunciator module. Annunciator wiring is
supervised for open circuits by this module. The Annunciator Driver Module mounts to connector J3 in the upper
right corner of the main circuit board. Refer to Figure 1-2, “MS-5024UD Panel,” on page 12 and Figure 2-11 on page
28.
1.6.4 RZA-5F Remote Annunciator
The RZA-5F Remote Annunciator mounts on a standard single-gang box and provides LED indication of the
following:
• Alarm Zone 1 (red)
• Alarm Zone 2 (red)
• Alarm Zone 3 (red)
• Alarm Zone 4 (red)
• Alarm Zone 5 (red)
• System Trouble (yellow)
A Local Trouble Sounder and Tone Silence Switch are also provided. All LEDs and their wiring are supervised for
open conditions. Any open condition will cause the System Trouble LED to illuminate. Slide-in paper labels permit
an easy change of zone information. Refer to Figure 2-12, “RZA-5F,” on page 28, Figure 2-13 on page 29 and Figure
2-14 on page 29. Note that the Remote Annunciator requires the use of the ADM-24 Annunciator Driver Module.
FIGURE 1-4:XRM-24(E) Transformer
Standard
Transformer
Optional
Transformer
XRM-24(E)

Specifications
16 Document #15140 Rev.G 01/02/02 P/N 15140:G
1.6.5 PRT-24 Printer Interface Module
The Printer Interface Module may be used to connect a printer to the control panel for the purpose of printing a his-
tory report, walktest file, troubleshoot report, program entries or current system status. Printers require separate
external primary power. Connect the PRT-24 module (with cable) to the serial EIA-232 port on the printer. The
module mounts to the J2 connector on the main circuit board. Note that an EDP listed printer must be used if the
printer will be permanently attached to the control panel. Refer to Figure 2-15, “Remote Printer Connections,” on
page 30.
1.6.6 DP-5024UD Dress Panel
A red dress panel is available as an option. The dress panel restricts access to the system wiring while allowing
access to the membrane switch panel. Refer to Figure 1-1, “Optional DP-5024UD,” on page 11.
1.6.7 BB-17F Battery Box
The BB-17F battery box may be used to house two batteries, from 12 Amp Hour to 18 Amp Hour. The battery box
mounts directly below the cabinet and main circuit board. Refer to Figure 2-3, “Backbox and Battery Box,” on page
21. The BB-17F is red and is provided with knockouts.
1.6.8 PK-5024UD Programming Kit
This kit includes one 3½" diskette plus Instruction Manual P/N 50041. When the software is loaded into an IBM
compatible computer, it creates an off-line Service Terminal that allows any MS-5024UD panel to be uploaded or
downloaded over standard telephone lines.
1.7 Specifications
AC Power - TB1
MS-5024UD: 120 VAC, 60 Hz, 2.3 amps
MS-5024UDE: 220/240 VAC, 50 Hz, 1.2 amps
Wire size: minimum #14 AWG (2 mm2) with 600V insulation
Battery (lead acid only) - J1
Maximum Charging Circuit: Normal Flat Charge - 27.6V @ 0.8 amp
Maximum Charger Capacity: 17 Amp Hour battery. (MS-5024UD cabinet holds maximum 7 Amp Hour battery.
Larger batteries require Fire•Lite BB-17F or other UL listed battery cabinet).
Initiating Device Circuits - TB2
Detector Zones 1, 2, 3, 4, 5 Power-limited Circuitry
Operation: All zones are NFPA Style B, Zone 3 is NFPA Style B or Style D. Use CAC-5F module for Style D
operations
Normal Operating Voltage: 24 VDC (ripple = 100 mV maximum)
Alarm Current: 26 mA Short Circuit Current: 42 mA maximum
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7K ohms, ½ watt (P/N 27072 UL listed)
Detector Loop Current is sufficient to ensure operation of one alarmed detector per zone
Standby Current: 7.26 mA (includes ELR and 2 mA maximum detector current)
Smoke Detector Identifier A
Refer to Fire•Lite Device Compatibility Document for listed compatible devices

Document #15140 Rev.G 01/02/02 P/N 15140:G 17
Specifications
Notification Appliance Circuits - TB5 & TB6
Nonregulated, special purpose power, Styles Y and Z supported
Power-limited circuitry
Operating Voltage: Nominal 24 volts
Current for all external devices: 3.0 amps expandable to 5.6 amps
Current-limit: PTC
Maximum signaling current/circuit: 2.5 amps
End-of-Line resistor: 4.7K ohms, ½ watt (P/N 71252 UL listed) for NACs
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Alarm and Trouble Relays - TB3
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Alarm and Trouble: Form-C power-limited circuitry (see Figure 2-7 note for power-limited wiring application)
Auxiliary Outputs - TB4, Terminals 5 & 6
TB4-5 Supervisory Relay Driver: Normally high, active low, sinks up to 40 mA
TB4-6 Communication Failure: Normally high, active low, sinks up to 40 mA
Power-limited circuitry
Four-wire Smoke Detector Power - TB4, Terminals 3(+) & 4(-)
Maximum ripple voltage: 10 mVRMS Operating voltage: Nominal 24 volts
Up to 300 mA is available for powering 4-wire smoke detectors
Power-limited circuitry
Recommended maximum standby current is 50 mA (see Battery Calculations in Appendix A)
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Nonresettable Filtered 24V Power - TB4 Terminals 1(+) & 2(-)
Maximum ripple voltage: 10 mVRMS Operating voltage: Nominal 24 volts
Total DC current available from this output is up to 300 mA
Power-limited circuitry
Recommended maximum standby current is 150 mA (see Battery Calculations in Appendix A)
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Notes:
1. For power supply calculations, refer to Appendix A.
2. Total current for nonresettable power, 4-wire smoke detector power and two Notification Appliance Circuits
must not exceed 5.6 amps. Total external system current in excess of 3.6 amps requires the XRM-24 Trans-
former (XRM-24E for 220/240 VAC applications) and 12 Amp Hour or 17 Amp Hour batteries.

Telephone Requirements and Warnings
18 Document #15140 Rev.G 01/02/02 P/N 15140:G
1.8 Telephone Requirements and Warnings
1.8.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 1.3B
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive
RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all
areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be con-
nected to the line as determined by the total RENs, contact the telephone company to determine the maximum REN
for the calling area.
1.8.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is
necessary. The following information is provided if required by the local telephone company:
Manufacturer: Fire•Lite Alarms, Inc.
One Fire-Lite Place
Northford, CT 06472
Product Model Number: MS-5024UD
FCC Registration Number: 1W6USA-20004-AL-E
Ringer Equivalence 1.3B
Note: The FCC ID label is located on the inside of the control panel door
1.8.3 Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in
its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the
telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily
discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In
such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems
and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The control panel must be connected to the public switched telephone network upstream of any private telephone sys-
tem at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to
the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.

Document #15140 Rev.G 01/02/02 P/N 15140:G 19
Installation
CHAPTER 2 Installation
2.1 Mounting Options
The cabinet may be either surface mounted or semi-flush
mounted using the optional Trim Ring P/N: TR-1-R. The
door is removable during the installation period by opening
and lifting the door off the hinges. The cabinet mounts using
two key slots and two additional 0.25" (6.35 mm) diameter
holes located in the backbox. The key slots are located at the
top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage.
Mount the cabinet in a clean, dry, vibration-free area where
extreme temperatures are not encountered. The area should
be readily accessible with sufficient room to easily install and
maintain the panel. Locate the top of the cabinet approxi-
mately five feet above the floor with the hinge mounting on
the left. Determine the number of conductors required for the
devices to be installed. Sufficient knockouts are provided for
wiring convenience. Select the appropriate knockout(s) and
pull the required conductors into the box. Note that there are
no knockouts on the left (hinged) side of the cabinet. All wir-
ing should be in accordance with the National and/or Local codes for fire alarm systems.
2.2 Backbox Mounting
✓Open the door and lift the door off the pin hinges
✓Remove the main PC board assembly by unscrewing the four screws in the corners of the board. Two
standoffs support the board in the center. Set the board aside in a safe, clean place. Avoid static dis-
charge which may damage the board.
✓Mark and predrill holes for the top two keyhole mounting bolts using the dimensions shown
✓Install two upper fasteners in the wall with the screw heads protruding
✓Using the proper 'keyholes', mount the backbox over the two screws
✓Mark and drill the lower two holes
✓Mount backbox, install remaining fasteners and tighten
✓When the location is dry and free of construction dust, reinstall the main PC board
FIGURE 2-1: MS-5024UD Cabinet

Backbox Mounting
20 Document #15140 Rev.G 01/02/02 P/N 15140:G
Bottom
Height=15.000”
(38.10 cm)
10.375”
(26.35 cm)
0.75”(1.9 cm)
2.875” (7.3 cm)
Backbox = 14.5”
(36.8 cm)
Depth = 3.000”
(7.62 cm)
Top
9.1” (23.1 cm)
2.7”
(6.86cm)
1.125” (2.868 cm)
Backbox Mounting Holes
ms2-4cab.cdr
FIGURE 2-2:Cabinet Dimensions and Knockout Locations
Draw wires through the respective knockout locations.
TR-1-R Trim Ring
This manual suits for next models
1
Table of contents
Other Fire-Lite Alarms Control Panel manuals

Fire-Lite Alarms
Fire-Lite Alarms MS-5UD Series User manual

Fire-Lite Alarms
Fire-Lite Alarms FIRE COMMAND 25 Supplement

Fire-Lite Alarms
Fire-Lite Alarms MRP-4424 User manual

Fire-Lite Alarms
Fire-Lite Alarms MicroScan-2410B User manual

Fire-Lite Alarms
Fire-Lite Alarms MS-9200UD User manual

Fire-Lite Alarms
Fire-Lite Alarms MS-9200E Operating and maintenance manual

Fire-Lite Alarms
Fire-Lite Alarms MS-9600LS User manual

Fire-Lite Alarms
Fire-Lite Alarms MS-5210UD User manual

Fire-Lite Alarms
Fire-Lite Alarms MS-4012 User manual

Fire-Lite Alarms
Fire-Lite Alarms ES-200XC User manual