Fire-Lite Alarms MS-5UD Series User manual

B1
P/N 52626:B1 ECN 09-432
Document 52626
6/30/2009 Rev:
Fire Alarm Control Panels
MS-5UD Series
MS-10UD Series
Manual

2MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of
smoke detectors, heat detectors, manual pull stations, audible
warning devices, and a fire alarm control panel with remote
notification capability—can provide early warning of a develop-
ing fire. Such a system, however, does not assure protection
against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec-
tors be located throughout a protected premise following the
recommendations of the National Fire Protection Association
Standard 72 (NFPA 72), manufacturer's recommendations,
State and local codes, and the recommendations contained in
the Guides for Proper Use of System Smoke Detectors, which
are made available at no charge to all installing dealers.
These documents can be found at http://www.systemsen-
sor.com/html/applicat.html. A study by the Federal Emer-
gency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not
guarantee warning or protection against fire. A fire alarm sys-
tem may not provide timely or adequate warning, or simply
may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a first-
floor or basement fire.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ion-
izing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different
ways and are often unpredictable in their growth, neither type
of detector is necessarily best and a given type of detector
may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predeter-
mined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire pro-
tection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys-
tem for the connection of alarm transmission wiring, communi-
cations, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crip-
pling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medica-
tion. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsi-
bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically com-
patible with the control panel. It is essential to use only equip-
ment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against tele-
phone line failure, backup radio transmission systems are rec-
ommended.
The most common cause of fire alarm malfunction is inade-
quate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA stan-
dards. At a minimum, the requirements of NFPA 72 shall be
followed. Environments with large amounts of dust, dirt or
high air velocity require more frequent maintenance. A main-
tenance agreement should be arranged through the local man-
ufacturer's representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes and
should be performed by authorized professional fire alarm
installers only. Adequate written records of all inspections
should be kept.
Limit-C1-2-2007

MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ-
ated equipment may be damaged by removing and/or insert-
ing cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro-
gramming operation or change in site-specific software. Re-
acceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All compo-
nents, circuits, system operations, or software functions known
to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º
C/32-120º F and at a relative humidity 93% ± 2% RH (non-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic com-
ponents may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indi-
cating device loops. Most devices cannot tolerate more thana
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to light-
ning induced transients. Although no system is completely
immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Ser-
vices Department if any problems are anticipated or encoun-
tered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-
tightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before han-
dling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interfer-
ence, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Cana-
dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radi-
oelectriques depassant les limites applicables aux appa-
reils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark of Honeywell International Inc.Echelon® is a registered trademark and
LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are
registered trademarks of the Microsoft Corporation.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

4MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact Technical Support with any questions about software and the appropriate version for
a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.T[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services.

Table of Contents
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 5
Table of Contents
SECTION 1 Product Description............................................................................................11
1.1: Product Features ..........................................................................................................................................12
1.2: Specifications...............................................................................................................................................13
1.3: Controls and Indicators................................................................................................................................15
1.4: Digital Alarm Communicator/Transmitter ..................................................................................................16
1.5: Components.................................................................................................................................................17
1.6: Optional Modules and Accessories .............................................................................................................17
1.7: Telephone Requirements and Warnings.......................................................................................................19
1.7.1: Telephone Circuitry...........................................................................................................................19
1.7.2: Digital Communicator.......................................................................................................................19
1.7.3: Telephone Company Rights and Warnings.......................................................................................20
1.7.4: For Canadian Applications................................................................................................................21
SECTION 2 Installation...........................................................................................................22
2.1: Backbox Mounting ......................................................................................................................................22
2.2: Operating Power..........................................................................................................................................25
2.3: Input Circuits ...............................................................................................................................................26
2.4: Output Circuits.............................................................................................................................................28
2.4.1: Notification Appliance Circuits.........................................................................................................28
2.4.2: Special Application DC Power Output Connections.........................................................................29
2.4.3: Relays - Programmable .....................................................................................................................29
2.4.4: Remote Synchronization Output .......................................................................................................30
2.5: Power-limited Wiring Requirements...........................................................................................................31
2.6: Digital Communicator .................................................................................................................................32
2.7: Installation of Optional Modules.................................................................................................................33
2.7.1: CAC-5X Class A Converter Module.................................................................................................33
2.7.2: 4XTMF Option Module ....................................................................................................................35
2.8: ANN-BUS Devices......................................................................................................................................37
2.8.1: ANN-BUS Wiring.............................................................................................................................37
2.8.2: ANN-BUS Device Addressing..........................................................................................................40
2.8.3: ANN-80 Remote Fire Annunciator ...................................................................................................41
2.8.4: Specifications.....................................................................................................................................41
2.8.5: Installation.........................................................................................................................................41
2.8.6: ANN-S/PG Serial/Parallel Printer Interface Installation...................................................................44
2.8.7: ANN-I/O LED Driver Module..........................................................................................................46
2.8.8: ANN-LED Annunciator Module.......................................................................................................49
2.8.9: ANN-RLY Relay Module .................................................................................................................51
2.9: ANN-BUS Audio Panel...............................................................................................................................53
SECTION 3 Programming ......................................................................................................55
3.1: User Programming.......................................................................................................................................55
3.2: Initial Power-up ...........................................................................................................................................56
3.3: Programming Screens Description ..............................................................................................................56
3.4: Programming and Passwords.......................................................................................................................57
3.5: Master Programming Level.........................................................................................................................58
3.5.1: Input Zones........................................................................................................................................59
3.5.2: NAC (Notification Appliance Circuit) ..............................................................................................67
3.5.3: Relays ................................................................................................................................................71
3.5.4: System Setup .....................................................................................................................................73
3.5.5: Option Modules................................................................................................................................79
3.5.6: History.............................................................................................................................................100
3.5.7: Walktest...........................................................................................................................................102
3.5.8: Clear Program..................................................................................................................................103
3.5.9: Password Change.............................................................................................................................103
3.6: Maintenance Programming Level..............................................................................................................104

Table of Contents
6MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
3.6.1: Input Zones - Enable/Disable ..........................................................................................................105
3.6.2: History .............................................................................................................................................105
3.6.3: Walktest...........................................................................................................................................106
3.6.4: Time-Date........................................................................................................................................107
SECTION 4 Operating Instructions.....................................................................................109
4.1: Panel Control Buttons................................................................................................................................109
4.1.1: Acknowledge/Step...........................................................................................................................109
4.1.2: Alarm Silenced ................................................................................................................................109
4.1.3: Drill/Hold 2 Sec...............................................................................................................................109
4.1.4: Reset ................................................................................................................................................109
4.2: LED Indicators...........................................................................................................................................110
4.3: Normal Operation ......................................................................................................................................110
4.4: Trouble Operation......................................................................................................................................111
4.5: Alarm Operation ........................................................................................................................................112
4.6: Supervisory Operation ...............................................................................................................................113
4.7: Process Monitor Operation ........................................................................................................................114
4.8: Hazard/Tornado Condition Operation........................................................................................................114
4.9: Medical Alert Condition Operation ...........................................................................................................114
4.10: Disable/Enable Operation........................................................................................................................115
4.11: Waterflow Circuits Operation ..................................................................................................................115
4.12: Detector Functions...................................................................................................................................115
4.13: Time Functions: Real-Time Clock...........................................................................................................115
4.14: Coded Operation......................................................................................................................................115
4.15: Presignal...................................................................................................................................................116
4.16: Positive Alarm Sequence.........................................................................................................................116
4.17: Special System Timers.............................................................................................................................117
4.17.1: Silence Inhibit Timer.....................................................................................................................117
4.17.2: Autosilence Timer .........................................................................................................................117
4.17.3: Trouble Reminder..........................................................................................................................117
4.17.4: Waterflow Retard Timer................................................................................................................117
4.17.5: Alarm Verification (None or One Minute)....................................................................................118
4.18: Walktest....................................................................................................................................................118
4.19: Read Status...............................................................................................................................................119
4.19.1: Input Zones....................................................................................................................................120
4.19.2: NAC...............................................................................................................................................120
4.19.3: Relays ............................................................................................................................................121
4.19.4: System Settings..............................................................................................................................121
4.19.5: Timers............................................................................................................................................122
4.19.6: Daylight Savings............................................................................................................................122
4.19.7: History ...........................................................................................................................................123
4.19.8: Print................................................................................................................................................123
4.19.9: ANN-BUS......................................................................................................................................124
4.19.10: Central Station .............................................................................................................................125
4.19.11: Phone Line...................................................................................................................................126
4.19.12: Service Terminal..........................................................................................................................126
SECTION 5 Central Station Communications....................................................................127
5.1: Transmittal Priorities..................................................................................................................................128
SECTION 6 Local/Remote Site Upload/Download.............................................................130
6.1: Remote Download .....................................................................................................................................130
6.2: Transferring a Program..............................................................................................................................132
6.2.1: Security Features .............................................................................................................................132
SECTION 7 Power Supply Calculations..............................................................................134
7.1: Overview....................................................................................................................................................134
7.2: Calculating the AC Branch Circuit............................................................................................................134

Table of Contents
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 7
7.3: Calculating the System Current Draw.......................................................................................................135
7.3.1: Overview .........................................................................................................................................135
7.3.2: How to Use Table 7-3 on page 136 to Calculate System Current Draw.........................................135
7.4: Calculating the Battery Size ......................................................................................................................137
7.4.1: NFPA Battery Requirements...........................................................................................................137
7.4.2: Selecting and Locating Batteries.....................................................................................................137
APPENDIX A Ademco Contact ID Format Event Code Descriptions...............................138
A.1: Transmission Format Between DACT and Receiver................................................................................138
A.2: Ademco Contact ID Typical Printout .......................................................................................................138
APPENDIX B NFPA Standard-Specific Requirements.......................................................143
B.1: Central Station/Remote Station Transmitter: ................................... Connection to FACP Dry Contacts149
APPENDIX C FACP with Keltron .........................................................................................150
APPENDIX D Wire Requirements........................................................................................151
D.1: MS-5UD-3(E) & MS-10UD-3(E) NAC Wiring.......................................................................................152
D.2: MS-5UD-7(C/E) & MS-10UD-7(C/E) NAC Wiring................................................................................152
Index.......................................................................................................................................153

8MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
• Underwriters Laboratories Standards
• NFPA 72 National Fire Alarm Code
• CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote
Station Fire Alarm Systems (requires an optional Remote Station Output Module)
Underwriters Laboratories Documents for Reference:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
UL 2017 General-Purpose Signaling Devices and Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
This Class (A) digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document Document #15384
411UD Manual Document #50759
411UDAC Manual Document #51073
ANN-80 Product Installation Doc. Document #52749
ANN-(R)LED Product Installation Doc. Document #53032
ANN-I/O Product Installation Doc. Document #151416
ANN-RLY Product Installation Doc. Document #53033
ANN-S/PG Product Installation Doc. Document #151417
ACC-25/50 Series Audio Panel Document #51889
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not
been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
Before proceeding, the installer should be familiar with the following documents.

MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 9
MS-5UD Series Main Circuit Board
DACT Phone Line Jacks
(Nonpower-Limited)
Resettable Power - 24 VDC filtered,
power-limited (0.500 amps maximum)
to smoke detectors (IDC).
Supervision required.
Nonresettable or Resettable Power
Jumper selectable by JP31, 24 VDC filtered,
power-limited (0.500 amps maximum)
Supervision required. NonresettablePower
suitable for powering annunciators, Resettable
Power suitable for powering smoke detectors.
Configure TB9, Terminals 1 & 2
as Resettable or Nonresettable Power.
• Resettable Power - jumper JP31
pins 2 & 3.
• Nonresettable Power - jumper JP31 pins 1 & 2
(as shown).
Special Application Power
NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited)
(See Style Z illustrated near right edge ofboard).
4.7K , ½ watt
End-of-Line Resistor
PN 71252
Nonsupervised relay contacts
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Contacts shown below in normal
condition (AC power with no alarm,
trouble or supervisory activity).
A Fail Safe Trouble
relay switches to the
NC position during
trouble conditionsand
under loss of all power.
Special Application
DC Power Outputs (24 VDC)
Nonsupervised, power-limited circuits
Supervise with a power supervision relay EOLR-1
Battery (see note 3)
Basic System Connections
5-Zone Panel
Notification Appliance Circuits (see note 1)
3 Programmable Relays
Alarm* Trouble* Supervisory*
NO NC C
24 VDC, supervised,
nonpower-limited
NO NC CNO NC C NO NC C
(* )Factory default relay programming
Power Supply Connector J15
NAC #1
+
+
+
4
3
FIRE ALARM
AC POWER
TROUBLE
1
4
7
*
231
56
89
0#
ABC DEF
GHI JKL
PRS TUV
QZ_ _/.
CLEAR
ESC
MODE
ST
ENTER
ALARM
DRILL RESET
J12
BATTERY
- +
TB5 TB4 TB8
TB9
J2
J15
J3
JP24
JP31
JP30
J5
J4
J6
J8 J9
TB3
GND PWR ANN-BUS
A B
RST AUX
PWR
RST/NONRST
AUXPWR
OUT1 OUT2
4XTM OPT BD
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
Cut this jumper to
enable Supervisory
relay when 4XTM
module is installed
2
1
JP43
Class A Converter Module
-
+
+
-
3
2
1
NAC #2
+
+
+
B
+B
-
11
B
+B
-
22
B
+B
-
11
Initiating Device Circuits
IDCs 1 through 5, Style B
(Class B) (Supervised,
Power Limited)
(See Style D illustrated
near right edge of board).
4.7K , ½ watt
End-of-Line Resistor
PN 71252
Remove jumper JP43
to disable Ground Fault
Detection circuit (only
with approval of AHJ).
+
+
+
TB5/
TB7 TB4/
TB6
OUT1/3 OUT2/4
B
+B
-
11 2
B
+B
-
11
OUT OUT
TB2 TB1
J2
Class AConverter Module
Dummy load all unused circuits with
4.7K , ½ watt End-of-Line resistors
Style Z (ClassA) NAC
Style D (Class A) IDC
+ - + - + - + - + - + - + -
Important!
Removing Ground Fault
DisableJumper JP43 voids UL/NFPA
Style/Class identifications for circuits.
Remove jumper JP43 only with the
approval of the AHJ
(Authority Having Jurisdiction).
- +
TB2
Remote
Synchronization
Output (see note 2)
Special Application Power
24 VDC filtered, supervised
and power-limited.
0.040 amps maximum.
Requires ELR.4.7K
Primary Phone
Active LED Secondary Phone
Active LED
Primary Secondary
Kiss-off LED
- +
NAC #3
+
+
+
TB7
OUT3 OUT4
NAC #4
+
+
+
B
+B
-
11
B
+B
-
22
+ - + -
J7
J11
USB Port for local programming using
a personal computer and PK-5X Utility
Notes:
1. MS-5UD-3(E) = 2.5 amps max. per NAC
MS-5UD-7(C/E)= 3 amps max. per NAC
2. Remote Sync Output is required only for
the MS-5UD-3(E): refer to “Remote
Synchronization Output” on page 30
3. 18 Amp Hour max. for MS-5UD-3(E)
26 Amp Hour max. for MS-5UD-7(C/E)

10 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
MS-10UD Series Main Circuit Board
DACT Phone Line Jacks
(Nonpower-Limited)
Resettable Power - 24 VDC filtered,
power-limited (0.500 amps maximum)
to smoke detectors (IDC).
Supervision required.
Nonresettable or Resettable Power
Jumper selectable by JP31, 24 VDC filtered,
power-limited (0.500 amps maximum)
Supervision required. NonresettablePower
suitable for powering annunciators, Resettable
Power suitable for powering smoke detectors.
Configure TB9, Terminals 1 & 2
as Resettable or Nonresettable Power.
• Resettable Power - jumper JP31
pins 2 & 3.
• Nonresettable Power - jumper JP31 pins 1 & 2
(as shown).
Special Application Power
NAC #1, #2, #3 & #4,Style Y (Class B) (Supervised, Power Limited)
(See Style Z illustrated near right edge of board).
4.7K , ½ watt
End-of-Line Resistor
PN 71252
Nonsupervised relay contacts
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Contacts shown below in normal
condition (AC power with no alarm,
trouble or supervisory activity).
A Fail Safe Trouble
relay switchesto the
NC position during
trouble conditions and
under loss of all power.
Special Application
DC Power Outputs (24 VDC)
Nonsupervised, power-limited circuits
Supervise with a power supervision relay EOLR-1
Battery (see note 3)
Basic System Connections
10-Zone Panel
Notification Appliance Circuits (see note 1)
3 Programmable Relays
Alarm* Trouble* Supervisory*
NO NC C
24 VDC, supervised,
nonpower-limited
NO NC CNO NC C NO NC C
(* )Factory default relay programming
Power Supply Connector J15
NAC #1
+
+
+
4
3
FIRE ALARM
AC POWER
TROUBLE
1
4
7
*
231
56
89
0#
ABC DEF
GHI JKL
PRS TUV
QZ_ _/.
CLEAR
ESC
MODE
ST
ENTER
ALARM
DRILL RESET
J12
BATTERY
- +
TB5 TB4 TB7
TB6 TB8
TB9
J2 J7
J15
J3
JP24
JP31
JP30
J5
J4
J6
J8 J9
TB3
GND PWR ANN-BUS
A B
RST AUX
PWR
RST/NONRST
AUXPWR
OUT1 OUT2 OUT3 OUT4
4XTM OPT BD
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
Cut this jumper to
enable Supervisory
relay when 4XTM
module is installed
2
1
JP43
Class A Converter Module
-
+
+
-
3
2
1
NAC #2
+
+
+
B
+B
-
11
B
+B
-
22
NAC #3
+
+
+
NAC #4
+
+
B
+B
-
33
B
+B
-
44
B
+B
-
11
B
+B
-
66
Initiating Device Circuits
IDCs 1 through 5, Style B
(Class B) (Supervised,
Power Limited)
(See Style D illustrated
near right edge of board).
4.7K , ½ watt
End-of-Line Resistor
PN 71252
IDCs 6 through 10, Style B
(Class B) (Supervised,
Power Limited)
(See Style D illustrated
near right edge of board).
4.7K , ½ watt
End-of-Line Resistor
PN 71252
Initiating Device Circuits
Remove jumper JP43
to disable Ground Fault
Detection circuit (only
with approval of AHJ).
+
+
+
TB5/
TB7 TB4/
TB6
OUT1/3 OUT2/4
B
+B
-
11 2
B
+B
-
11
OUT OUT
TB2 TB1
J2
Class AConverter Module
Dummy load all unused circuits with
4.7K , ½ watt End-of-Line resistors
Style Z (ClassA) NAC
Style D (Class A) IDC
+ - + - + - + -
+ - + - + - + - + - + - + - + - + - + -
+
Important!
Removing Ground Fault
DisableJumper JP43 voids UL/NFPA
Style/Class identifications for circuits.
Remove jumper JP43 only with the
approval of the AHJ
(Authority Having Jurisdiction).
- +
TB2
Remote
Synchronization
Output (see note 2)
SpecialApplication Power
24 VDC filtered, supervised
and power-limited.
0.040 amps maximum.
Requires ELR.4.7K
Primary Phone
Active LED Secondary Phone
Active LED
Primary Secondary
Kiss-off LED
- +
J11
USB Port for local programming using
a personal computer and PK-5X Utility
Notes:
1. MS-10UD-3(E) = 2.5 amps max. per NAC
MS-10UD-7(C/E) = 3 amps max. per NAC
2. Remote Sync Output is required only for
the MS-10UD-3(E): refer to “Remote
Synchronization Output” on page 30
3. 18 Amp Hour max. for MS-10UD-3(E)
26 Amp Hour max. for MS-10UD-7(C/E)

11
SECTION 1 Product Description
The MS-5UD is a five zone FACP (Fire Alarm Control Panel) and the MS-10UD is a ten zone
FACP. The information in this manual refers to both the MS-5UD and MS-10UD unless otherwise
specified. The combination control and digital communicator panels provide reliable fire signaling
protection for small to medium sized commercial, industrial and institutional buildings. The FACP
is compatible with System Sensor’s i3detectors which are conventional smoke detectors that can
transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a
supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating of
approximately 45oF (refer to System Sensor i3Installation and Maintenance Instructions). In
addition, the control panel is compatible with conventional input devices such as two-wire smoke
detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other
normally-open contact devices. Refer to Fire•Lite Device Compatibility Document for a complete
listing of compatible devices.
Outputs include four NACs (Notification Appliance Circuits), three programmable Form-C relays
(factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application
resettable and nonresettable power outputs. The FACP supervises all wiring, AC voltage, battery
level and telephone line integrity. Available accessories include local and remote upload/download
software, remote annunciators and reverse polarity/city box transmitter.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via
the public switched telephone network. It also allows remote programming or interrogation of the
control panel using the PS-Tools Upload/Download utility via the public switched telephone
network. Local programming interrogation is also possible using the PS-Tools and the USB port on
the FACP. Any personal computer with Windows™XP or newer, compatible modem with a speed
of 2400 baud and PS-Tools may serve as a Service Terminal. This allows download of the entire
program or upload of the entire program, history file, walktest data and current status.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will
activate audible and visual signaling devices, illuminate an indicating LED, display alarm
information on the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm
relay and operate an optional module used to notify a remote station or initiate an auxiliary control
function.

Product Description Product Features
12 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
The following versions of the MS-5UD and MS-10UD are available:
Note: Unless otherwise specified, the information in this manual applies to all versions of the
panels.
1.1 Product Features
• Built-in DACT (Digital Alarm Communicator/Transmitter)
• Style B (Class B) IDC (Initiating Device Circuit)
MS-5UD - five programmable IDCs
MS-10UD - ten programmable IDCs
• Four Style Y (Class B) NAC (Notification Appliance Circuit)
- special application power
• Three programmable Form-C relays
• Built-in Programmer
• Touchtone/Rotary dialing
• Programmable Make/Break Ratio
• Optional Dress Panel DP-51050
• A modified Dress Panel is provided standard with Canadian models: includes an ANN-LED
Annunciator module
• Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet
• ANN-BUS for connection to optional:
ANN-80 Remote LCD Annunciator
ANN-I/O LED Driver
ANN-S/PG Printer Module
ANN-RLY Relay Module
ANN-LED Annunciator Module
• 80-character LCD display (backlit)
• Real-time clock/calendar with daylight savings time control
• History log with 256 event storage
FACP Version Description
MS-5UD-3 Five Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-5UD-7 Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
MS-5UD-7C Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current. Includes built-in ANN-LED Annunciator.
This panel is approved for Canadian applications
MS-5UD-3E Five Zone Panel: 240 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-5UD-7E Five Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
MS-10UD-3 Ten Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-10UD-7 Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
MS-10UD-7C Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current. Includes built-in ANN-LED Annunciator.
This panel is approved for Canadian applications.
MS-10UD-3E Ten Zone Panel: 240 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-10UD-7E Ten Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current

Specifications Product Description
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 13
• Control Buttons
ACK (Acknowledge)
Alarm Silence
System Reset/Lamp Test
Drill
• LED Indicators
Fire Alarm
Supervisory
Trouble
AC Power
Alarm Silence
Primary and Secondary Phone Line Active LEDs
• Piezo sounder for alarm, trouble and supervisory
• 24 volt operation
• Low AC voltage sense
• Alarm Verification
• NACs Programmable for:
Silence Inhibit
Auto-Silence
Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)
Selective Silence (horn-strobe mute)
Temporal or Steady Signal
Silenceable or Nonsilenceable
• Automatic battery charger with charger supervision
• Silent or audible walktest capabilities
• Optional PK-CD (contains PS-Tools utility) for local or remote Upload/Download of
program and data
• Optional CAC-5X Class A Converter Module for NACs and IDCs
• Optional 4XTMF Transmitter Module
1.2 Specifications
Note: For wiring specifications, refer to "Wire Requirements" on page 151.
AC Power
MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps
MS-5UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps
MS-5UD-7C (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps
MS-10UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps
MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps
MS-10UD-7C (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps
MS-5UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps
MS-5UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps
MS-10UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps
MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps
Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation
Supervised, nonpower-limited

Product Description Specifications
14 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
Battery (sealed lead acid only) - J12
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp
Supervised, nonpower-limited
Maximum Charger Capacity: 18 Amp Hour battery for MS-5UD-3(E), MS-10UD-3(E) and 26
Amp Hour battery for MS-5UD-7(E), MS-10UD-7(E) [two 18 Amp Hour batteries can be
housed in FACP cabinet. Larger batteries require separate battery box such as BB-26 or BB-55]
Minimum Battery Size: 7 Amp Hour (12 Amp Hour for MS-5UD-7C & MS-10UD-7C)
Initiating Device Circuits - TB4 (and TB6 on MS-10UD only)
Alarm Zones 1 - 5 on TB 4 (MS-5UD and MS-10UD)
Alarm Zones 6 - 10 on TB6 (MS-10UD only)
Supervised and power-limited circuitry
Operation: All zones Style B (Class B)
Normal Operating Voltage: Nominal 20 VDC
Alarm Current: 15 mA minimum
Short Circuit Current: 40 mA max.
Maximum Loop Resistance: 100 ohms (2,000 ohms per zone for linear heat detection)
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)
Standby Current: 2 mA
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Notification Appliance Circuit(s) - TB5 and TB71
Four NACs
Operation: Style Y (Class B)
Special Application power
Supervised and power-limited circuitry
Normal Operating Voltage: Nominal 24 VDC
Maximum Signaling Current: 3.0 amps for MS-5UD-3(E), MS-10UD-3(E) (2.5 amp maximum
per NAC); 7.0 amps for MS-5UD-7(E), MS-10UD-7(E) (3.0 amps maximum per NAC)
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Form-C Relays - Programmable - TB8
Relay 1 (factory default programmed as Alarm Relay)
Relay 2 (factory default programmed as fail-safe Trouble Relay)
Relay 3 (factory default programmed as Supervisory Relay)
Relay Contact Ratings: 2 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Special Application Resettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see
note 1)
Power-limited Circuitry
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Special Application Resettable or Nonresettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA (see note 1)
Power-limited Circuitry
Jumper selectable by JP31 for resettable or nonresettable power:
Jumper pins 1 & 2 on JP31 for nonresettable power
Jumper pins 2 & 3 on JP31 for resettable power
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
1. Total current for resettable power, nonresettable power and Notification Appliance Circuits
must not exceed 3.0 amps for the FACP versions which are powered by the FLPS-3 power
supply or 7.0 amps for the FACP versions which are powered by the FLPS-7 power supply.

Controls and Indicators Product Description
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 15
Remote Sync Output - TB2
Remote power supply synchronization output, only required for the MS-5UD-3(E), MS-10UD-
3(E) [refer to "Remote Synchronization Output" on page 30]
24 VDC nominal special application power
Maximum current is 40 mA
End-of-Line Resistor: 4.7KΩ
Supervised and power-limited circuit
Auxiliary Trouble Input - J6
The Auxiliary Trouble Input is an open collector circuit which can be used to monitor an
external device for trouble conditions. It can be connected to the trouble bus of a peripheral,
such as a power supply, which is compatible with open collector circuits.
All connections must be in conduit, less than 20 ft. (610 cm) in length in the same room.
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high viewing angle
LCD display. The display includes a long life
LED backlight that remains illuminated. If AC
power is lost and the system is not in alarm, the
LED backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
• Acknowledge/Step
• Alarm Silence
• Drill
• System Reset (lamp test)
Service/program keys:
• Keys labeled 1 to 9
• * key
• # key
• 0 (recall) key
• 1st Event key
• Clear key
• Escape key
• Mode key
• Four cursor keys (up, down, left and right)
• Enter key
SYSTEM ALL NORMAL
10:00A 012105
Figure 1.1 Membrane/Display Panel
9050udkypd.cdr

Product Description Digital Alarm Communicator/Transmitter
16 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
LED Indicators
LEDs are provided to annunciate the following conditions:
• Fire Alarm - red LED
• Supervisory - yellow LED
• AC Power - green LED
• System Trouble - yellow LED
• Alarm Silence - yellow LED
• Primary Phone Line Active (on circuit board) - red LED
• Secondary Phone Line Active (on circuit board) - red LED
• Kiss-off (on circuit board) - green LED
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance, process
monitor and supervisory conditions as follows:
• Alarm - on steady
• Trouble - pulse 1 second on and 1 second off
• Maintenance - pulse 1 second on and 1 second off
• Supervisory - pulse ½ second on and ½ second off
• Process Monitor - pulse ¼ second on and ¼ second off
1.4 Digital Alarm Communicator/Transmitter
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1
for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs
are provided as well as a green Kissoff LED. The integral digital communicator provides the
following functions:
• Line Seizure: takes control of the phone lines disconnecting any premises phones
• Off/On Hook: performs on and off-hook status to the phone lines
• Listen for dial tone: 440 Hz tone typical in most networks
• Dialing the Central Station(s) number: default is Touch-Tone®, programmable to rotary
• For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The
frequency and time duration of the tone(s) varies with the transmission format. The control
panel will adjust accordingly.
• Communicate in the following formats:
Ademco Contact ID
SIA-DCS-8
SIA-DCS-20

Components Product Description
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 17
1.5 Components
Main Circuit Board
The main circuit board contains the system’s CPU, DACT and other primary components and
wiring interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One power supply is provided standard with each FACP, mounted to a chassis.
• FLPS-3 for the MS-5UD-3(E), MS-10UD-3(E)
• FLPS-7 for the MS-5UD-7(C/E), MS-10UD-7(C/E)
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides
space for two batteries (up to 18 Amp Hours). Also available are an optional dress panel (DP-
51050) which mounts inside the cabinet and trim-ring (TR-CE). The Canadian version is supplied
standard with a modified dress panel and one ANN-LED annunciator module.
Batteries
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL
listed battery box such as the BB-26 or BB-55). Batteries must be ordered separately.
1.6 Optional Modules and Accessories
CAC-5X Class A Converter Module
The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to
Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The
module connects to J2 on the MS-5UD and MS-10UD main circuit board and to J7 on the MS-
10UD. Note that two Class A Converter modules are required for the 10 zone panel.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper
option allows the reverse polarity circuit to open with a system trouble condition if no alarm
condition exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.
ANN-80 LCD Annunciator
The ANN-80 is a remote LCD annunciator which mimics the information displayed on the FACP
LCD display.
ANN-LED Annunciator Module
The ANN-LED Annunciator Module provides three LEDs for each zone: Alarm, Trouble and
Supervisory. ANN-LED module is installed in dress panel for Canadian version.
ANN-RLY Relay Module
The ANN-RLY Module, which can be mounted inside the cabinet, provides 10 Form-C relays.
ANN-S/PG Serial/Parallel Printer Gateway
The ANN-S/PG module provides a connection for a serial or parallel printer.
ANN-I/O LED Driver Module
The ANN-I/O module provides connections to a user supplied graphic annunciator.
DP-51050 Dress Panel
A dress panel DP-51050 is available as an option. The dress panel restricts access to the system
wiring while allowing access to the membrane switch panel. The Canadian version is supplied
standard with a modified dress panel.

Product Description Optional Modules and Accessories
18 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
TR-CE Trim-ring
A trim-ring TR-CE is available as an option. The trim-ring allows semi-flush mounting of the
cabinet.
Battery Box
The BB-26 or BB-55 battery box may be used to house two batteries greater than 18 Amp Hour.
The battery box mounts directly below the control panel cabinet, centered to the main circuit board.
PS-Tools Programming Utility
The PS-Tools Programming Utility can be used to locally or remotely program the FACP directly
from most IBM compatible personal computers (PC), running Windows™XP (or newer). FACP
program files can also be created and stored on the PC and then downloaded later to the control
panel. The P/N: PK-CD includes the Windows-based Programming Utility software on CD-ROM
with on-line help file. A standard USB cable with male-A to male-B connectors, which must be
purchased separately, is required for local connection of the PC to the USB port J11 on the FACP
main circuit board. Remote programming requires that the PC have a 2400 baud (or faster)
modem.
Important: Remote modification of FACP programming requires that the panel be enabled for
remote download (refer to "Remote Download" on page 130). Remote interrogation of panel
programming, history logs, detector status, etc., is possible without enabling the remote download
option.

Telephone Requirements and Warnings Product Description
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 19
1.7 Telephone Requirements and Warnings
1.7.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 0.0B
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone
line. Excessive RENs on the telephone line may result in the devices not ringing in response to an
incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be
certain of the number of devices that may be connected to the line as determined by the total RENs,
contact the telephone company to determine the maximum REN for the calling area.
1.7.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of
two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty
information, please contact:
Manufacturer:Fire•Lite Alarms
One Fire-Lite Place
Northford, CT 06472
(203) 484-7161
Product Model Number: MS-5UD/MS-10UD
FCC Registration Number: 1W6AL00B10UD
Ringer Equivalence: 0.0B
Important! The DACT must not be used to dial a phone number that is call-forwarded.
Note: This equipment complies with Part 68 of the FCC rules and the requirements
adopted by the ACTA. On the inside of the FACP door is a label that contains,
among other information, a product identifier in the format
US:AAAEQ##TXXXX. If requested, this number must be provided to the
telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency
situation. It must be able to do this even if other equipment (telephone, answering system,
computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment
must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of
all other equipment attached to the same telephone line. If there are any questions concerning these
instructions, consult the telephone company or a qualified installer about installing the RJ31X jack
and alarm dialing equipment. Refer to "Digital Communicator" on page 32 for an illustration of
the proper installation of this equipment.

Product Description Telephone Requirements and Warnings
20 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
1.7.3 Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or
make changes in its facilities, services, equipment or procedures which may affect the operation of
this control panel. However, the telephone company is required to give advance notice of such
changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right
to temporarily discontinue service. Advance notification will be provided except in cases when
advance notice is not practical. In such cases, notification will be provided as soon as possible.
The opportunity will be given to correct any problems and to file a complaint with the FCC if you
believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY
LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same
telephone line.
The control panel must be connected to the public switched telephone network upstream (as first
device) of any private telephone system at the protected premises.
A plug and jack used to connect this equipment to the premises wiring and telephone network must
comply with the applicable FCC Part 68 rules and requirements adopted by ACTA. This equipment
is designed to be connected to the telephone network or premises wiring using a compliant RJ31X
male modular plug and compatible modular jack that is also compliant.
This manual suits for next models
1
Table of contents
Other Fire-Lite Alarms Control Panel manuals

Fire-Lite Alarms
Fire-Lite Alarms MS-4012 User manual

Fire-Lite Alarms
Fire-Lite Alarms MS-4412B User manual

Fire-Lite Alarms
Fire-Lite Alarms MRP-4424 User manual

Fire-Lite Alarms
Fire-Lite Alarms MicroScan-2410B User manual

Fire-Lite Alarms
Fire-Lite Alarms ES-200XC User manual

Fire-Lite Alarms
Fire-Lite Alarms MS-9200UD User manual

Fire-Lite Alarms
Fire-Lite Alarms MS-5024UD User manual

Fire-Lite Alarms
Fire-Lite Alarms MS-9200E Operating and maintenance manual

Fire-Lite Alarms
Fire-Lite Alarms FIRE COMMAND 25 Supplement

Fire-Lite Alarms
Fire-Lite Alarms MS-5210UD User manual