5 | 16 Page
•The parameter is stated in the first line.
•The value that is to be changed is shown in the
second line, the display flashes.
•The input limits are displayed in the 3rd line (if
there is one).
The required value is set with the buttons þand ÿ
and then confirmed with û.
5.3 Menu
Description Parameter name
Menu Level Switch points
Switch point 1:
Switch point 1 On..................... ............SP1 On
Switch point 1 Off..................... ............SP1 Off
Switch point 1 Delay................. ............SP1 Delay
Switch point 1 Function ............ ............SP1 Function
Switch point 2:
Switch point 2 On..................... ............SP2 On
Switch point 2 Off..................... ............SP2 Off
Switch point 2 Delay................. ............SP2 Delay
Switch point 2 Function ............ ............SP2 Function
Menu Level Input
Damping................................... ............Damping
Offset correction....................... ............Offset correction
Zero-point window.................... ............Zero-point window
Menu Level Measuring
Measuring range start .............. ............Meas. range Start
Measuring range end ............... ............Meas. range. End
Measuring range unit................ ............Unit
Measuring range limit............... ............Limit
Menu Level Output
min. output .............................. ............min. Output
max. output .............................. ............max. Output
Error signal............................... ............Error signal
Menu Level Function
The menu will change depending on the entered value, linear,
square rooted or table:
(a) Value = linear:
Function:............................ ............linear
(b) Value = square rooted
Function: ........................... ............Square rooted
Measuring range decimal places.....Decimal places MB
Start of measuring range.... ............MB-start
End of measuring range..... ............MB-end
Measuring range unit ......... ............Unit MB
(c) Value= Table
Function: ........................... ............Table
Measuring range decimal places.....Decimal places MB
Start of measuring range.... ............MB-start
End of measuring range..... ............MB-end
Measuring range unit ......... ............Unit MB
Number of pair(s)............... ............Number of pairs
Depending on the input followed by :
Pair 1 ........................... ............Value pair 1
Pair 2 ........................... ............Value pair 2
Pair 3 ........................... ............Value pair 3
•
•
Pair n ........................... ............Value pair n
Menu Level Display
Colour....................................... ...........Colour
(a) The menu changes for the value Auto1:
Red-green switchover......... ...........Red-green switcho.
Green-red switchover ......... ...........Green-red switcho.
Hysteresis........................... ...........Hysteresis
Delay ........................... ...........Delay
Colour ........................... ...........Colour
(a) The menu changes for the value Auto2:
Red-yellow switchover........ ...........Red-yellow switcho.
Yellow-green switchover..... ...........Yellow-green switcho.
Green-yellow switchover..... ...........Green-yellow switcho.
Yellow-red switchover......... ...........Yellow-red switcho.
Hysteresis........................... ...........Hysteresis
Delay ........................... ...........Delay
Colour ........................... ...........Colour
Lighting time............................. ...........Lighting
Contrast.................................... ...........Contrast
Bar chart................................... ...........Bar chart
Menu Level System
Language switchover................ ...........Language
Device information.................... ...........Software Info
Device information.................... ...........Config Info
Operating time/switch cycles..... ...........Statistics
Access control .......................... ...........Password
Data backup ............................. ...........Load config.
Data backup ............................. ...........Save config.
5.3.1 Menu Level Switch points
The two switching outputs are configured by four
parameters respectively.
For the switch point 1 these are
SP1 On
SP1 Off
SP1 Delay
SP1 Function
Accordingly for switch point 2:
SP2 On
SP2 Off
SP2 Delay
SP2 Function
SP1 On defines the activation point, SP1 Off the
deactivation point of switch output 1. The values are
shown in the valid unit and set accordingly. The
values are shown in the valid unit and set accord-
ingly.
Together, the two parameters determine the switch
function of switch output 1:
If SP1 Off < SP1 ON, the output switches on, if the
measured value exceeds SP1 ON. It is only
switched off again if the measured value SP1 Off is
undercut (hysteresis function).
If SP1 On = SP1 Off, the output switches on if the
measured value exceeds SP1 On and off if the
measured value undercuts SP1 Off.
If SP1 Off > SP1 ON, the output switches on, if SP1
On < Measured value < SP1 Off applies (window
function).