[01] Lockout setting
Set Lock / Unlock of lockout setting.
SETTING VALUE DESCRIPTION INITIAL VALUE
Lock Lockout setting enable Lock
Unlock Lockout setting disable
Even when setting is ‘Lock’, it is available to move on to
each setting mode and confirm the setting value of each set-
ting parameter. In each setting parameter display, when
‘Lock’, ‘DATA (Locked)’ is indicated, when ‘Unlock’, ‘DATA’
is indicated.
[12] 0 % input setting
0 % input setting is performed by teach.
For setting, use the corresponding value that input ratio for
total resistance is 0 – 10000.
Set as [12] 0% input setting < [13] 100 % input setting and
span 500 min. When the span is less than 500, ‘SETTING
ERROR’ is displayed and the setting is not determined. In-
put setting value set become 0% of ‘INPUT (Scaling)’ and
‘PERCENT’.
Initial value: 0
[13] 100 % input setting
100 % input setting is performed by teach.
For setting, use the corresponding value that input ratio for
total resistance is 0 – 10000.
Set as [12] 0% input setting < [13] 100 % input setting and
span 500 min. When the span is less than 500, ‘SETTING
ERROR’ is displayed and the setting is not determined. In-
put setting value set become 100% of ‘INPUT (Scaling)’ and
‘PERCENT’.
Initial value: 10000
[14] 0 % input scaling
Set the display value of 0 % input setting.
SETTING RANGE INITIAL VALUE
-99999 – 999999 0.00
[15] 100 % input scaling
Set the display value of 100 % input setting.
SETTING RANGE INITIAL VALUE
-99999 – 999999 100.00
[16] Input decimal point
Set the decimal point position of [14] 0 % and [15] 100 %
input scaling.
SETTING VALUE
DESCRIPTION INITIAL VALUE
oooooo Decimal point: None
2 places of
decimals
ooooo.o Number of decimal places: 1
oooo.oo Number of decimal places: 2
ooo.ooo Number of decimal places: 3
oo.oooo Number of decimal places: 4
o.ooooo Number of decimal places: 5
[17] Output range
Set the range of output signal of the unit.
SETTING VALUE DESCRIPTION INITIAL VALUE
0 – 20 mA Output: 0 – 20 mA DC
0 – 20 mA-5 – +5 V Output: -5 – +5 V DC
-10 – +10 V Output: -10 – +10 V DC
When output range is changed, turn the power off, and then
set the output setting DIP SW on the side of the unit. Set-
ting is as follows. Output setting value is changed to initial
value.
OUTPUT
RANGE
SW1
12345678
0 – 20 mA OFF ON OFF OFF OFF OFF ON OFF
-5 – +5 V OFF OFF ON OFF ON OFF OFF ON
-10 – +10 V OFF OFF ON OFF OFF ON OFF ON
[18] 0 % output setting
Set the 0 % output setting.
OUTPUT RANGE
SETTING RANGE
MIN. SPAN
INITIAL VALUE
0 – 20 mA 0.000 – 19.000 1.000 4.000
-5 – +5 V -5.000 – 4.750 0.250 -5.000
-10 – +10 V -10.000 – 9.000 1.000 -10.000
Set as follows.
[18] 0 % output setting < [19] 100 % output setting
The value is indicated by ‘OUTPUT’ at measuring mode.
[19] 100 % output setting
Set the 100 % output setting.
OUTPUT RANGE
SETTING RANGE
MIN. SPAN
INITIAL VALUE
0 – 20 mA 1.000 – 20.000 1.000 20.000
-5 – +5 V -4.750 – 5.000 0.250 5.000
-10 – +10 V -9.000 – 10.000 1.000 10.000
Set as follows.
[18] 0 % output setting < [19] 100 % output setting
The value is indicated by ‘OUTPUT’ at measuring mode.
[20] 0 % output scaling
Set the display value of [18] 0 % output setting.
SETTING RANGE INITIAL VALUE
-99999 – 999999 0.00
[21] 100 % output scaling
Set the display value of [19] 100 % output setting.
SETTING RANGE INITIAL VALUE
-99999 – 999999 100.00
[22] Output decimal point
Set decimal point position for [20] 0 % and [21] 100 % out-
put scaling.
SETTING VALUE
DESCRIPTION INITIAL VALUE
oooooo Decimal point: None
2 places of
decimals
ooooo.o Number of decimal places: 1
oooo.oo Number of decimal places: 2
ooo.ooo Number of decimal places: 3
oo.oooo Number of decimal places: 4
o.ooooo Number of decimal places: 5