Fisher FIELDVUE DVC2000 User manual

www.Fisher.com
Fisher™FIELDVUE™DVC2000 Digital Valve
Controller
This manual applies to
Instrument Level HC, AD, PD AC
Device Type 05 F5
Device Revision 1 1
Hardware Revision 1 & 2 1 & 2
Firmware Revision 1, 2, 3, 4 & 5 1, 2, 3, 4 & 5
DD Revision 3 1
Contents
Section 1 Introduction and Specifications 3.
Installation, Electrical and Pneumatic Connections,
and Basic Setup and Calibration 3...............
Scope of Manual 3..............................
Instrument Description 3........................
Terminology 4.................................
Specifications 4................................
Related Documents 7...........................
Educational Services 8...........................
Section 2 Detailed Setup and Calibration via
HART Communication 9.................
Detailed Setup 9...............................
Setting Modes 9..............................
Instrument Mode 9........................
Control Mode 9...........................
Restart Control Mode 10....................
Restarting the Instrument 10................
Burst Mode 10............................
Protection 12.................................
General Information 14........................
HART Tag
Message
Descriptor
Date
Valve Serial Number
Instrument Serial Number
Polling Address
LUI Language
W8755
Measured Variable Units and Ranges 15...........
Analog Input Units
Analog Input Range High and Low
Pressure Units
Temperature Units
Actuator and Valve Information 16...............
Maximum Supply Pressure
Actuator Style
Valve Serial Number
Valve Style
Zero Control Signal
Setting Response 16...........................
Tuning Set
Damping Factor
Expert Tuning Gains
Input Characteristic
Custom Characteristic Table
Set Point Filter Time
Limits and Cutoffs
Minimum Opening and Closing Time
Integral Settings
Setting Alerts 19..............................
Travel Alerts 20............................
Cycle Counter Alert 22......................
Other Alerts 23............................
Alert Record 23............................
Instruction Manual
D103176X012
DVC2000 Digital Valve Controller
June 2017

Instruction Manual
D103176X012
DVC2000 Digital Valve Controller
June 2017
2
Self-Test Failure for Instrument Shutdown 24......
Transmitter/Switches 25.......................
Tuning 26.....................................
Automatic 26.................................
Manual 26...................................
Calibration 27..................................
Analog Input Calibration 27.....................
Using the Field Communicator 27............
Using Local Operator Interface 28............
Auto Calibrate Travel 28........................
Manual Calibrate Travel 29......................
Analog Calibration Adjust 29................
Digital Calibration Adjust 29.................
Pressure Sensor Calibration 30..................
Output Pressure Sensor 30..................
Position Transmitter 31........................
Section 3 Viewing Device Variables and
Diagnostics 33.........................
Viewing Variables 33............................
Analog Input, Travel, Valve Set Point, Drive Signal
and Output Pressure 33......................
Additional Instrument Variables 33...............
Viewing Device Information 34...................
Viewing Instrument Status 35....................
Section 4 Maintenance and
Troubleshooting 39.....................
Stroking the Digital Valve Controller Output 39......
Replacing the Instrument 40.....................
Replacing the Magnetic Feedback Assembly 41......
Component Replacement 41.....................
Replacing the I/P Converter 41..................
Replacing the Pneumatic Relay 43...............
Troubleshooting 44.............................
Checking Available Voltage 46....................
Technical Support Checklist 47...................
Section 5 Parts 49......................
Parts Ordering 49...............................
Parts Kits 49...................................
Parts List 50...................................
Appendix A Principle of Operation 55......
DVC2000 Operation 55..........................
Appendix B Local Interface Flow Chart and
Field Communicator Menu Trees 57.......
Glossary 65............................
Index 73..............................

Instruction Manual
D103176X012
Introduction and Specifications
June 2017
3
Section 1 Introduction and Specifications1‐1‐
Installation, Electrical and Pneumatic Connections, and Basic
Setup and Calibration using the Local Operator Interface
Refer to the DVC2000 Quick Start Guide (D103203X012) for DVC2000 installation,
connection, and basic setup and calibration using the local operator interface. If a copy
of this quick start guide is needed scan or click the QR code at the right, contact your
Emerson sales office, Local Business Partner, or visit our website at Fisher.com.
Scope of Manual
This instruction manual is a supplement to the quick start guide that ships with every instrument. This instruction
manual includes specifications, detailed configuration and calibration using a Field Communicator, maintenance and
troubleshooting information and replacement part details.
Note
ValveLink software can also be used for detailed configuration and calibration, as well as performing diagnostic and performance
tests. For information on using ValveLink software with the instrument, refer to the appropriate user guide or help.
Do not install, operate, or maintain a DVC2000 digital valve controller without being fully trained and qualified in
valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage,
it is important to carefully read, understand, and follow all of the contents of this manual, including all safety cautions
and warnings. If you have any questions regarding these instructions, contact your Emerson sales office or Local
Business Partner before proceeding.
Instrument Description
The DVC2000 digital valve controller is a communicating, microprocessor-based current-to-pneumatic valve
positioner. It is designed to replace standard pneumatic and electro-pneumatic valve positioners.
In addition to the traditional function of converting an input current signal (4-20 mA) to a pneumatic output pressure,
the DVC2000 digital valve controller communicates via a local display panel and/or via the HART®protocol. An option
is available which provides isolated circuitry for two (2) integrated limit switches (for open/close valve indication) and a
valve position transmitter (for separate valve position feedback).
Scan or click
to access
field support

Instruction Manual
D103176X012
Introduction and Specifications
June 2017
4
Terminology
Instrument Level— There are four (4) levels of functionality available: AC, HC, AD and PD.
AC—This level provides the capability to setup and calibrate the positioner through the LCD or the Field
Communicator.
HC—This level provides additional capability for advanced configuration of the positioner (such as travel limits/cutoffs,
custom characterization, and minimum open/closing time). Also, information is available through the HART protocol
for diagnostic alerts such as travel deviation, cycle count, and travel accumulation.
AD—This level provides advanced diagnostic capabilities for performance testing. When used with ValveLink software,
instrument health can be evaluated with tests such as Valve Signature, step response and dynamic error band. The
software program provides detailed analysis with graphics.
PD—This level provides automated, non-intrusive testing of the operating performance of the control valve assembly.
When used with ValveLink software, tests to isolate component degradation can be run on the valve assembly without
affecting the process.
Local Interface— The DVC2000 comes standard with a Liquid Crystal Display (LCD) and four (4) pushbuttons. The local
interface provides the capability to setup and calibrate the positioner and view basic diagnostic messages.
Magnet Assembly—This is the feedback component that is mounted directly to the valve stem. It supplies a magnetic
field that is sensed by the digital valve controller.
Options Board—The DVC2000 digital valve controller is available with two (2) limit switches and a valve position
transmitter. The options board includes the additional circuitry and terminations that are required to support these
output signals.
Pole Piece—Inserted into the DVC2000 housing and protruding through the back of the instrument is a two-pronged
fork that houses the magnetic sensor for position feedback.
Specifications
Specifications for the DVC2000 digital valve controller are shown in table 1‐1. Specifications for the Field
Communicator can be found in the User's Manual.
WARNING
This product is intended for a specific range of application specifications. Incorrect configuration of a positioning
instrument could result in the malfunction of the product, property damage, or personal injury.

Instruction Manual
D103176X012
Introduction and Specifications
June 2017
5
Table 1‐1. Specifications
Available Configurations
JIntegral mounting to the Fisher GX Control Valve
and Actuator System JSliding-stem applications
JQuarter-turn rotary applications
The DVC2000 digital valve controller can also be
mounted on other actuators that comply with IEC
60534-6-1, IEC 60534-6-2, VDI/VDE 3845 and
NAMUR mounting standards.
Input Signal
Analog Input Signal: 4-20 mA DC, nominal; split
ranging available
Minimum Voltage: Voltage available at instrument
terminals must be 8.5 volts for analog control, 9.0
volts for HART communication
Maximum Voltage: 30 volts DC
Minimum Control Current: 4.0 mA (below 3.5 mA
may cause microprocessor restart)
Overcurrent Protection: Input circuitry limits current
to prevent internal damage
Reverse Polarity Protection: No damage occurs from
reversal of loop current
Output Signal
Pneumatic signal as required by the actuator, up to
full supply pressure
Minimum Span: 0.5 bar (7 psig)
Maximum Span: 7 bar (101 psig)
Action: Single Acting, direct
Supply Pressure(1)
Recommended: 0.5 bar (7 psig) greater than the
maximum actuator requirements
Maximum: 7 bar (101 psig)
Supply pressure medium must be clean, dry air or
noncorrosive gas
Per ISA Standard 7.0.01
A maximum 40 micrometer particle size in the air
system is acceptable. Further filtration down to 5
micrometer particle size is recommended. Lubricant
content is not to exceed 1 ppm weight (w/w) or
volume (v/v) basis. Condensation in the air supply
should be minimized
Per ISO 8573-1
Maximum particle density size: Class 7
Oil content: Class 3
Pressure Dew Point: Class 3 or at least 10_C less than
the lowest ambient temperature expected
Temperature Limits(1)
-40 to 85_C (-40 to 185_F). LCD may not be readable
below -20_C (-4 _F).
Air Consumption(2)
Supply pressure:
At 1.5 bar (22 psig)(3):0.06 normal m3/h (2.3 scfh)
At 4 bar (58 psig)(4):0.12 normal m3/h (4.4 scfh)
Air Capacity(2)
Supply pressure:
At 1.5 bar (22 psig)(3):4.48 normal m3/h (167 scfh)
At 4 bar (58 psig)(4):9.06 normal m3/h (338 scfh)
Independent Linearity
±0.5% of output span
Electromagnetic Compatibility
Meets EN 61326-1:2013
Immunity—Industrial locations per Table 2 of the
EN 61326-1 standard. Performance is shown
in table 1‐2 below
Emissions—Class A
ISM equipment rating: Group 1, Class A
Tested to NAMUR NE21 requirements.
Vibration Testing Method
Tested per ANSI/ISA 75.13.01 Section 5.3.5. A
resonant frequency search is performed on all three
axes. The instrument is subjected to the ISA specified
1/2 hour endurance test at each major resonance,
plus an additional two million cycles.
Input Impedance
The input impedance of the DVC2000 active
electronic circuit is not purely resistive. For
comparison to resistive load specifications, an
equivalent impedance of 450 ohms may be used. This
value corresponds to 9 V @ 20 mA.
Electrical Classification
Hazardous Area:
CSA—Intrinsically Safe and Non-incendive
FM—Intrinsically Safe and Non-incendive
ATEX—Intrinsically Safe
IECEx—Intrinsically Safe
-continued-

Instruction Manual
D103176X012
Introduction and Specifications
June 2017
6
Table 1‐1. Specifications (continued)
Electrical Housing:
CSA—IP66 and Type 4X
FM, ATEX, IECEx—IP66
Other Classifications/Certifications
CUTR— Customs Union Technical Regulations
(Russia, Kazakhstan, Belarus, and Armenia)
INMETRO—National Institute of Metrology, Quality
and Technology (Brazil)
KGS— Korea Gas Safety Corporation (South Korea)
NEPSI—National Supervision and Inspection Centre
for Explosion Protection and Safety of
Instrumentation (China)
PESO CCOE— Petroleum and Explosives Safety
Organisation - Chief Controller of Explosives (India)
Contact your Emerson sales office or Local Business
Partner for classification/certification specific
information
Connections
Standard
Supply and Output Pressure: G1/4 internal
Electrical: M20 internal
Optional
Supply and Output Pressure: 1/4 NPT internal
Electrical: 1/2 NPT internal
Materials of Construction
Housing and Cover: A03600 low copper aluminum
alloy
Elastomers: nitrile, fluorosilicone
Stem Travel
Minimum: 6.35 mm (0.25 inch)
Maximum: 606 mm (23-7/8 inches)
Shaft Rotation
Minimum: 45_
Maximum: 90_
Mounting
Designed for direct actuator mounting. For
weatherproof housing capability, the vent must be
positioned at the lowest point of the instrument.
Weight
1.5 kg (3.3 lbs)
Options
JAirset: 67CFR with filter
Language Packs:
JStandard: English, German, French, Italian, Spanish,
Japanese, Chinese, Portuguese, Russian, Polish, and
Czech
JOptional: English, German, French, Italian, Spanish,
Japanese, Chinese, and Arabic
JPipe-away vent
JLimit Switches: Two isolated switches,
configurable throughout calibrated travel range
Supply Voltage: 5-30 VDC
OFF State: 0.5 to 1.0 mA
ON State: 3.5 to 4.5 mA (above 5 V)
Reference Accuracy: 2% of travel span(5)
JTransmitter: 4-20 mA output, isolated
Supply Voltage: 8-30 VDC
Fault Indication: offrange high or low
Reference Accuracy: 1% of travel span(5)
Declaration of SEP
Fisher Controls International LLC declares this
product to be in compliance with Article 4 paragraph
3 of the PED Directive 2014/68/EU. It was designed
and manufactured in accordance with Sound
Engineering Practice (SEP) and cannot bear the CE
marking related to PED compliance.
However, the product may bear the CE marking to
indicate compliance with other applicable European
Community Directives.
1. The pressure/temperature limits in this document and any applicable standard or code limitation should not be exceeded. Note: Temperature limits vary based on hazardous area approval.
2. Normal m3/hour - Normal cubic meters per hour at 0_C and 1.01325 bar, absolute. Scfh - Standard cubic feet per hour at 60_F and 14.7 psia.
3. Low pressure relay: 0 to 3.4 bar (0 to 50 psig).
4. High pressure relay: 3.5 to 7.0 bar (51 to 102 psig).
5. Typical values when calibrated at temperature.

Instruction Manual
D103176X012
Introduction and Specifications
June 2017
7
Table 1‐2. EMC Summary Results—Immunity
Port Phenomenon Basic Standard Test Level Performance Criteria(1)
Enclosure
Electrostatic discharge
(ESD) IEC 61000-4-2 6 kV contact
8 kV air B
Radiated EM field IEC 61000-4-3
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
A
Rated power frequency
magnetic field IEC 61000-4-8 30 A/m at 50 Hz, 60 sec A
I/O signal/control
Burst (fast transients) IEC 61000-4-4 $1 kV A
Surge IEC 61000-4-5 $1 kV (line to ground only, each) B
Conducted RF IEC 61000-4-6 150 kHz to 80 MHz at 10 Vrms A
Performance criteria is + / - 1% effect.
1. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering.
Related Documents
Other documents containing information related to the DVC2000 digital valve controller include:
D DVC2000 Digital Valve Controller Quick Start Guide (D103203X012)
D Bulletin 62.1:DVC2000 (D103167X012)
D INMETRO Hazardous Area Approvals for FIELDVUE DVC2000 Digital Valve Controller (D103780X012)
D FIELDVUE Digital Valve Controller Split Ranging (D103262X012)
D Using FIELDVUE Instruments with the Smart HART Loop Interface and Monitor (HIM) (D103263X012)
D Audio Monitor for HART Communications (D103265X012)
D HART Field Device Specification - Fisher FIELDVUE DVC2000 Digital Valve Controller (D103783X012)
D Using the HART Tri-Loopt HART-to-Analog Signal Converter with Fisher FIELDVUE Digital Valve Controllers
(D103267X012)
These documents are available from your Emerson sales office, Local Business Partner, or at Fisher.com.

Instruction Manual
D103176X012
Introduction and Specifications
June 2017
8
Educational Services
For information on available courses for the DVC2000 digital valve controller, as well as a variety of other products,
contact:
Emerson Automation Solutions
Educational Services - Registration
Phone: 1-641-754-3771 or 1-800-338-8158
E-mail: [email protected]
emerson.com/fishervalvetraining

Instruction Manual
D103176X012
Detailed Setup and Calibration
June 2017
9
Section 2 Detailed Configuration and Calibration via HART
Communication2‐2‐
Detailed Setup
The DVC2000 digital valve controller has the capability to communicate via the HART protocol. This section describes
the advanced features that can be accessed with the Field Communicator. Table 2‐1 lists the default settings for a
standard factory configuration. Table 2‐2 provides the actuator information required to setup and calibrate the
instrument.
Setting Modes
Field Communicator Setup & Diag > Detailed Setup > Mode (1-2-1)
Instrument Mode
You can change the instrument mode by selecting Instrument Mode from the Mode menu, or press the Hot Key and
select Instrument Mode.
Instrument Mode allows you to either take the instrument Out Of Service or place it In Service. Taking the instrument
Out Of Service allows you to perform instrument calibration and also allows you to change setup variables that affect
control, provided the calibration/configuration protection is properly set. See Setting Protection.
Note
Some changes that require the instrument to be taken Out Of Service will not take effect until the instrument is placed back In
Service or the instrument is restarted.
Control Mode
You can change the control mode by selecting Control Mode from the Mode menu, or press the Hot Key and select
Control Mode.
Control Mode lets you define where the instrument receives its set point. Follow the prompts on the Field
Communicator display to choose one of the following control modes: Analog or Digital.
Choose Analog if the instrument is to receive its set point over the 4-20 mA loop. Normally the instrument control
mode is Analog.
Choose Digital if the instrument is to receive its set point digitally, via the HART communications link.
A third mode, Test, is also displayed. Normally the instrument should not be in the Test mode. The Field
Communicator automatically switches to this mode whenever it needs to stroke the valve, for example during

Instruction Manual
D103176X012
Detailed Setup and Calibration
June 2017
10
calibration or stroke valve. However, if you abort from a procedure where the instrument is in the Test mode, it may
remain in this mode. To take the instrument out of the Test mode, select Control Mode then select either Analog or
Digital.
Restart Control Mode
Restart Control Mode (Restart Cont Mode) lets you choose which operating mode you want the instrument to be in
after a restart. Follow the prompts on the Field Communicator display to define the restart control mode as Resume
Last, Analog, or Digital.
Restarting the Instrument
Restart resets the instrument in the same manner as when power to the instrument is interrupted. When Restart is
issued, all of the newly entered configuration variables become active. Otherwise, they may not take effect until the
instrument is placed In Service.
Burst Mode
Enabling burst mode provides continuous communication from the digital valve controller. Burst mode applies only to
the transmission of burst mode data (analog input, travel target, pressure, and travel) and does not affect the way
other data is accessed.
Access to information in the instrument is normally obtained through the poll/response of HART communication. The
Field Communicator or the control system may request any of the information that is normally available, even while
the instrument is in burst mode. Between each burst mode transmission sent by the instrument, a short pause allows
the Field Communicator or control system to initiate a request. The instrument receives the request, processes the
response message, and then continues “bursting” the burst mode data.
There are four burst mode commands. Command 3 is recommended for use with the RosemountR333 HART
Tri-LooptHART-to-analog signal converter. The other three are not used at this time.
Command 3 provides the following variables:
D Primary variable—analog input in % or mA,
D Secondary variable—travel target (valve set point) in % of ranged travel,
D Tertiary variable—output pressure in psig, bar, or kPa,
D Quaternary variable—travel in % of ranged travel.
To enable burst mode select Mode > Burst > Burst Enable. To send a burst mode command, select Burst Command.
Burst mode must be enabled before you can change the burst mode command.

Instruction Manual
D103176X012
Detailed Setup and Calibration
June 2017
11
Table 2‐1. Factory Default Detailed Setup Parameters
Setup Parameter Default Setting(1)
Control Mode
Restart Control Mode
Burst Mode Enabled
Burst Mode Command
HART Tag
Analog
Resume Last
No
3
As specified on order
Message
Description
Date
Valve Serial Number
Polling Address
Blank
Blank
Factory Calibration Date
Blank
0
Max Supply Pressure
Zero Control Signal
100(2)
Open(2)
Analog Input Units
Analog In Range High
Analog In Range Low
Travel Range High
Travel Range Low
mA
20 mA
4.0 mA
100%
0%
Pressure Units
Temperature Units
Input Characteristic
Setpoint Filter Time
PSI(2)
F
Linear
Filter Off
Travel Limit High
Travel Limit Low
Travel Cutoff High
Travel Cutoff Low
125%
-25%
99.5%
0.5%
Minimum Opening Time
Minimum Closing Time
Integral Gain
Integral Deadband
Travel Hi/Lo Alert Enabled
Travel Hi Hi/Lo Lo Alert Enabled
0 secs
0 secs
1 repeat/minute
0.5%
No
No
Travel Alert High Point
Travel Alert Low Point
Travel Alert High-High Point
Travel Alert Low-Low Point
Travel Alert Deadband
125%
-25%
125%
-25%
1%
Travel Deviation Alert Enable
Travel Deviation Alert Point
Travel Deviation Time
Yes
7%
5 secs
Cycle Counter Alert Enable
Cycle Counter Alert Point
Cycle Counter Deadband
Cycle Counter
No
2,147,483,646
3%
0
Travel Accumulator Alert Enable
Travel Accumulator Alert Point
Travel Accumulator Deadband
Travel Accumulator
No
2,147,483,646%
3%
0
Drive Alert Enable
Flash ROM Fail
Ref Voltage Fail
No
No
No
Drive Current Fail
Critical NVM Fail
Temperature Sensor Fail
Pressure Sensor Fail
Travel Sensor Fail
No
No
No
No
No
1. The settings listed are for standard factory configuration. DVC2000 instruments can also be ordered with custom configuration
settings. For the default custom settings, refer to the order requisition.
2. If the instrument is shipped mounted on an actuator, these values depend upon the actuator on which the instrument is mounted.

Instruction Manual
D103176X012
Detailed Setup and Calibration
June 2017
12
Table 2‐2. Actuator Information for Setup
Actuator
Manufacturer Actuator Model Actuator Style Actuator Size Starting
Tuning Set Feedback Connection
Fisher
585C & 585CR
Piston Dbl w/ or w/o Spring. See
actuator instruction manual and
nameplate.
25, 50, 60, 68,
80, 100, 130 Undefined
SStem-Standard for travels
up to 4 inches. SStem-
Roller for longer travels
657 Spring & Diaphragm
30, 30i G
SStem-Standard
34, 34i, 40, 40i I
45, 45i, 50, 50i J
46, 46i, 60, 60i, 70,
70i & 80-100 Undefined
667 Spring & Diaphragm
30, 30i G
SStem-Standard
34, 34i, 40, 40i I
45, 45i, 50, 50i J
46, 46i, 60, 60i, 70,
70i, 76, 76i & 80-100 Undefined
1051 & 1052 Spring & Diaphragm 20, 30, 33,
40, 60, 70 Undefined Rotary
1066SR Piston Sgl w/Spring 20
27, 75 Undefined Rotary
3024 Spring & Diaphragm
GA 1.21
GA 1.31
GA 1.41
Undefined SStem-Standard
3025 Spring & Diaphragm P460, P462, P900 Undefined Rotary
GX Spring & Diaphragm
225 G
SStem-Standard
750 I
1200 K
GX 3-Way Spring & Diaphragm 225 G SStem-Standard
750 I
Baumann
Air to Extend Spring & Diaphragm
16 C
SStem-Standard
32 D
54 Undefined
70 H
Air to Retract Spring & Diaphragm
16 C
SStem-Standard
32 D
54 Undefined
70 H
Rotary Spring & Diaphragm
10
25
54
Undefined
Undefined
G
Rotary
Setting Protection
Field Communicator Setup & Diag > Detailed Setup > Protection (1-2-2)
Some setup parameters may require changing the protection with the Field Communicator.
Two levels of protection are available:
D None—Neither setup nor calibration is protected. Allows changing calibration and setup parameters.
D Config & Calib—Both setup and calibration are protected. Prohibits changing calibration and protected setup
parameters.

Instruction Manual
D103176X012
Detailed Setup and Calibration
June 2017
13
Table 2‐3 lists configurable parameters in the instrument and the requirements for modifying these parameters, in
terms of instrument mode and protection.
Table 2‐3. Conditions for Modifying FIELDVUE DVC2000 Digital Valve Controller Parameters
Parameters In Service/
Config Protected
In Service/
Config Unprotected
Out of Service/
Config Protected
Out of Service/
Config Unprotected
Control Mode
Restart Ctrl Mode
Burst Mode Enable
Burst Mode Command
Protection
- - -
- - -
n
- - -
n
- - -
- - -
n
- - -
n
n
- - -
n
- - -
n
n
n
n
n
n
HART Tag
Message
Description
Date
Valve Serial Num
Inst Serial Num
Polling Address
- - -
- - -
- - -
- - -
- - -
- - -
- - -
n
n
n
n
n
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
n
n
n
n
n
n
n
Max Supply Pressure
Zero Ctrl Signal
- - -
- - -
- - -
- - -
- - -
- - -
n
n
Analog In Units
Input Range High
Input Range Low
Pressure Units
Temp Units
- - -
- - -
- - -
- - -
n
- - -
- - -
- - -
- - -
n
- - -
- - -
- - -
- - -
n
n
n
n
n
n
Tuning Set
Prop Gain
Velocity Gain
MLFB Gain
Input Char
Define Custom Char
Set Pt Filter Time
- - -
- - -
- - -
- - -
- - -
- - -
- - -
n
n
n
n
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
n
n
n
n
n
n
n
Tvl Limit High
Tvl Limit Low
Tvl Cutoff High
Tvl Cutoff Low
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
n
n
n
n
Min Opening Time
Min Closing Time
- - -
- - -
- - -
- - -
- - -
- - -
n
n
Integral Gain
Integral Deadband
- - -
- - -
n
n
- - -
- - -
n
n
Tvl Hi/Lo Enab
Tvl HH/LL Enab
Tvl Alert Hi Pt
Tvl Alert Lo Pt
Tvl Alert HiHi Pt
Tvl Alert LoLo Pt
Tvl Alrt DB
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Tvl Dev Alrt Enab
Tvl Dev Alrt Pt
Tvl Dev Time
n
n
n
n
n
n
n
n
n
n
n
n
Cycl Cnt Alrt Enab
Cycl Count Alrt Pt
Cycl Count DB
Cycl Count
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Tvl Acum Alrt Enab
Tvl Acum Alrt Pt
Tvl Acum DB
Tvl Acum
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n—indicates parameter may be modified for instrument mode and protection shown.
-Continued-

Instruction Manual
D103176X012
Detailed Setup and Calibration
June 2017
14
Table 2‐3. Conditions for Modifying FIELDVUE DVC2000 Digital Valve Controller Parameters
Parameters In Service/
Config Protected
In Service/
Config Unprotected
Out of Service/
Config Protected
Out of Service/
Config Unprotected
Drive Alert Enable n n n n
Flash ROM Fail
Ref Voltage Fail
Drive Current Fail
Critical NVM Fail
Temp Sensor Fail
Press Sensor Fail
Tvl Sensor Fail
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
n
n
n
n
n
n
n
n—indicates parameter may be modified for instrument mode and protection shown.
To change an instrument's protection, press the Hot key on the Field Communicator display window and select
Protection or select Protection from the Detailed Setup menu. Select the desired level of protection. Follow the prompts
on the Field Communicator display to set the protection level.
General Information
Field Communicator Setup & Diag > Detailed Setup > General (1-2-3)
Follow the prompts on the Field Communicator to enter or view information in the following fields:
D HART Tag—Enter an up to 8 character HART tag for the instrument. The HART tag is the easiest way to distinguish
between instruments in a multi-instrument environment. Use the HART tag to label instruments electronically
according to the requirements of your application. The tag you assign is automatically displayed when the Field
Communicator establishes contact with the digital valve controller at power-up.
D Message—Enter any message with up to 32 characters. Message provides the most specific user-defined means for
identifying individual instruments in multi-instrument environments.
D Descriptor—Enter a descriptor for the application with up to 16 characters. The descriptor provides a longer
user-defined electronic label to assist with more specific instrument identification than is available with the HART
tag.
D Date—Enter a date with the format MM/DD/YY. Date is a user-defined variable that provides a place to save the date
of the last revision of configuration or calibration information.
D Valve Serial Num—Enter the serial number for the valve in the application with up to 12 characters.
D Inst Serial Num—Enter the serial number on the instrument nameplate, up to 12 characters.
D Polling Address—If the digital valve controller is used in point-to-point operation, the Polling Address is 0. When
several devices are connected in the same loop, such as for split ranging, each device must be assigned a unique
polling address. The Polling Address is set to a value between 0 and 15. To change the polling address the
instrument must be Out Of Service.
For the Field Communicator to be able to communicate with a device whose polling address is not 0, it must be
configured to automatically search for all or specific connected devices.
D LUI Language—Select the language to be displayed on the local user interface; English, French, German, Italian,
Spanish, Chinese and Japanese.

Instruction Manual
D103176X012
Detailed Setup and Calibration
June 2017
15
Measured Variable Units and Ranges
Field Communicator Setup & Diag > Detailed Setup > Measured Var (1-2-4)
Follow the prompts on the Field Communicator to define the following measured variables units and ranges:
D Analog In Units—Permits defining the Analog Input Units in mA or percent of 4-20 mA range.
D Input Range Hi—Permits setting the Input Range High value. Input Range High should correspond to Travel Range
High, if the Zero Control Signal is configured as closed. If the Zero Control Signal is configured as open, Input Range
High corresponds to Travel Range Low. See figure 2‐1.
D Input Range Lo—Permits setting the Input Range Low value. Input Range Low should correspond to Travel Range
Low, if the Zero Control Signal is configured as closed. If the Zero Control Signal is configured as open, Input Range
Low corresponds to Travel Range High. See figure 2‐1.
D Pressure Units—Defines the output and supply pressure units in either psi, bar, or kPa.
D LUI Pressure Units—Enter the pressure units displayed on the local user interface; psi, bar, or kPa.
D Temp Units—Degrees Fahrenheit or Celsius. The temperature measured is from a sensor mounted on the digital
valve controller's printed wiring board.
Figure 2‐1. Calibrated Travel to Analog Input Relationship
TRAVEL
RANGE
HIGH
TRAVEL
RANGE
LOW
THE SHAPE OF
THESE LINES DEPENDS ON
THE INPUT CHARACTERISTICS
LINEAR CHARACTERISTIC SHOWN
INPUT RANGE
LOW
INPUT RANGE
HIGH
ANALOG INPUT
MA OR % OF 4-20 MA
CALIBRATED TRAVEL, %
A6531-1
ZCS = CLOSED
ZCS = OPEN
NOTE:
ZCS = ZERO CONTROL SIGNAL

Instruction Manual
D103176X012
Detailed Setup and Calibration
June 2017
16
Actuator and Valve Information
Field Communicator Setup & Diag > Detailed Setup > Actuator & Valve (1-2-5)
Follow the prompts on the Field Communicator to edit or view information in the following fields:
D Max Supply Press—Enter the maximum supply pressure in psi, bar, or kPa, depending on what was selected for
pressure units.
Note
If the actual measured pressure exceeds this setting by 25%, the pressure measurement will not be displayed.
D Actuator Style—Enter the actuator style, spring and diaphragm, piston double-acting without spring, piston
single-acting with spring, or piston double-acting with spring.
D Valve Style—Enter the valve style, rotary or sliding-stem
D Zero Control Signal—Identifies whether the valve is fully open or fully closed when the input is 0%. If you are unsure
how to set this parameter, disconnect the current source to the instrument. The resulting valve travel is the Zero
Control Signal. (With direct acting digital valve controllers, disconnecting the current source is the same as setting
the output pressure to zero.)
Setting Response
Field Communicator Setup & Diag > Detailed Setup > Response Control (1-2-6)
Follow the prompts on the Field Communicator to configure the following response control parameters:
WARNING
Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury and property damage
caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly.
D Tuning Set—There are eleven tuning sets to choose from. Each tuning set provides a preselected value for the digital
valve controller gain settings. Tuning set C provides the slowest response and M provides the fastest response.
Table 2‐4 lists the proportional gain, velocity gain, and minor loop feedback gain values for preselected tuning sets.

Instruction Manual
D103176X012
Detailed Setup and Calibration
June 2017
17
Table 2‐4. Gain Values for Preselected Turning Sets
Tuning Set Proportional Gain Velocity Gain Minor Loop Feedback
Gain
C 5 2 55
D 6 2 55
E 7 2 55
F 8 2 52
G 9 2 49
H 10 2 46
I 11 2 44
J 12 1 41
K 14 1 38
L 16 1 35
M 18 1 35
D Damping Factor—If after selecting a tuning set the valve travel overshoot is excessive or unsatisfactory, the damping
factor allows you to either decrease damping to allow more overshoot, or increase damping to decrease the
overshoot.
D Expert Tuning Gains—With Expert Tuning, you can specify the proportional gain, velocity gain, and minor loop
feedback gain.
D Input Char—Defines the relationship between the travel target and ranged set point. Ranged set point is the input to
the characterization function. If the zero control signal equals closed, then a set point of 0% corresponds to a ranged
input of 0%. If the zero control signal equals open, a set point of 0% corresponds to a ranged input of 100%. Travel
target is the output from the characterization function.
You can select from the three fixed input characteristics shown in figure 2‐2 or you can select a custom
characteristic. Figure 2‐2 shows the relationship between the travel target and ranged set point for the fixed input
characteristics, assuming the Zero Control Signal is configured as closed.
You can specify 21 points on a custom characteristic curve. Each point defines a travel target, in % of ranged travel,
for a corresponding set point, in % of ranged set point. Set point values range from -6.25% to 106.25%. Before
modification, the custom characteristic is linear.
With input characterization you can modify the overall characteristic of the valve and instrument combination.
Selecting an equal percentage, quick opening, or custom (other than the default of linear) input characteristic
modifies the overall valve and instrument characteristic. However, if you select the linear input characteristic, the
overall valve and instrument characteristic is the characteristic of the valve, which is determined by the valve trim
(i.e., the plug or cage).
D Custom Char Table—To define a custom input characteristic, select Custom Char Table. Select the point you wish to
define (1 to 21), then enter the desired set point value. Press Enter then enter the desired travel target for the
corresponding set point. When finished, select point 0to return to the Response Control menu.

Instruction Manual
D103176X012
Detailed Setup and Calibration
June 2017
18
Figure 2‐2. Travel Target Versus Ranged Set Point, for Various Input Characteristics (Zero Control Signal = Closed)
Travel Target, %
Ranged Set Point, %
−25 0 125
100 −25 0 125
100
−25 0 125
100
Input Characteristic = Linear Input Characteristic = Equal Percentage
Input Characteristic = Quick Opening
100
0
-25
125
Travel Target, %
100
0
-25
125
Ranged Set Point, %
Travel Target, %
100
0
-25
125
Ranged Set Point, %
A6535-1
D Setpt Filter Time—Time constant for the set point filter, in seconds. The set point filter slows the response of the
digital valve controller and is typically used with noisy or fast processes. The filter provides improved closed loop
process control. To disable the filter, set the time constant to 0seconds.
D Limits and Cutoff
Travel Limit Hi—Defines the high limit for the travel in percent (%) of ranged travel. It is the maximum allowable
travel (in percent of ranged travel) for the valve. During operation, the travel target will not exceed this limit. When
a Travel Limit High is set, the Travel Cutoff High is deactivated, since only one of these parameters can be active.
Travel Limit High is deactivated by setting it to 125.0%.

Instruction Manual
D103176X012
Detailed Setup and Calibration
June 2017
19
Travel Limit Lo—Defines the low limit for the travel in percent (%) of ranged travel. It is the minimum allowable travel
(in percent of ranged travel) for the valve. During operation, the travel target will not exceed this limit. When a
Travel Limit Low is set, the Travel Cutoff Low is deactivated, since only one of these parameters can be active. Travel
Limit Low is deactivated by setting it to -25.0%.
Travel Cutoff Hi—Defines the high cutoff point for the travel in percent (%) of ranged travel. Above this cutoff, the
travel target is set to 123.0% of the ranged travel. When a Travel Cutoff High is set, the Travel Limit High is
deactivated, since only one of these parameters can be active. Travel Cutoff High is deactivated by setting it to
125.0%.
Travel Cutoff Lo—Defines the low cutoff point for the travel. Travel Cutoff Low can be used to ensure proper seat load
is applied to the valve. When below the travel cutoff low, the output is set to zero or to full supply pressure,
depending upon the zero control signal. A Travel Cutoff Low of 0.5% is recommended to help ensure maximum
shutoff seat loading.
When a Travel Cutoff Low is set, the Travel Limit Low is deactivated, since only one of these parameters can be
active. Travel Cutoff Low is deactivated by setting it to -25.0%.
D Min Open/Close
Min Opening Time—Minimum Opening Time is configured in seconds and defines the minimum time for the travel to
increase the entire ranged travel. This rate is applied to any travel increases. A value of 0.0 seconds deactivates this
feature and allows the valve to stroke open as fast as possible. This parameter should be set to 0in firmware 1, 2, 3,
and 4.
Min Closing Time—Minimum Closing Time is configured in seconds and defines the minimum time for the travel to
decrease the entire ranged travel. This rate is applied to any travel decreases. A value of 0.0 seconds deactivates this
feature and allows the valve to stroke closed as fast as possible. This parameter should be set to 0in firmware 1, 2,
3, and 4.
D Integral Settings
Enab Int Control—Select Yes or No
Integral Gain—By setting this value to 0.0 the positioner integrator is disabled. Any other value will provide reset
action to improve static performance.
Integral Dead Zone—When the travel target and actual target deviate by less than this amount, the integrator is
automatically disabled. This prevents the positioner integrator from fighting with the process controller integrator
which may result in valve oscillation.
Setting Alerts
Field Communicator Setup & Diag > Detailed Setup > Alerts (1-2-7)
The following menus are available for configuring Alerts. Items on the menus may be changed with the instrument In
Service. Protection does not need to be removed (no need to set to None). Alerts are not processed when a Diagnostic
is in progress. Follow the prompts on the Field Communicator display to configure alerts.
Note
Alerts are not available with instrument level AC.

Instruction Manual
D103176X012
Detailed Setup and Calibration
June 2017
20
Setting Travel Alerts
Setting High, High-High, Low and Low-Low Alerts
Follow the prompts on the Field Communicator to set the following travel alerts:
D Tvl Hi/Lo Enab—Yes or No. Travel Hi/Lo Enable activates checking of the ranged travel against the Travel Alert High
and Low Points. Travel Alert Hi is set if the ranged travel rises above the alert high point. Once the alert is set, the
ranged travel must fall below the alert high point by the Travel Alert Deadband before the alert is cleared. See figure
2‐3.
Travel Alert Lo is set if the ranged travel falls below the alert low point. Once the alert is set, the ranged travel must
rise above the alert low point by the Travel Alert Deadband before the alert is cleared. See figure 2‐3.
D Tvl HH/LL Enab—Yes or No. Travel HH/LL Enable activates checking of the ranged travel against the Travel Alert
High-High and Low-Low Points. Travel Alert Hi Hi is set if the ranged travel rises above the alert high-high point.
Once the alert is set, the ranged travel must fall below the alert high-high point by the Travel Alert Deadband before
the alert is cleared. See figure 2‐3.
Travel Alert Lo Lo is set if the ranged travel falls below the alert low-low point. Once the alert is set, the ranged travel
must rise above the alert low-low point by the Travel Alert Deadband before the alert is cleared. See figure 2‐3.
Figure 2‐3. Travel Alert Deadband
ALERT IS CLEARED
ALERT IS SET
TRAVEL ALERT
HIGH POINT
TRAVEL ALERT
DEADBAND
A6532
D Tvl Alert Hi Pt—Travel Alert High Point is the value of the travel, in percent (%) of ranged travel, which, when
exceeded, sets the Travel Alert High alert.
D Tvl Alert Lo Pt—Travel Alert Low Point is the value of the travel, in percent (%) of ranged travel, which, when
exceeded, sets the Travel Alert Low alert.
D Tvl Alert Hi Hi Pt—Travel Alert High-High Point is the value of the travel, in percent (%) of ranged travel, which, when
exceeded, sets the Travel Alert Hi Hi alert.
D Tvl Alert Lo Lo Pt—Travel Alert Low-Low Point is the value of the travel, in percent (%) of ranged travel, which, when
exceeded, sets the Travel Alert Lo Lo alert.
Other manuals for FIELDVUE DVC2000
2
Table of contents
Other Fisher Control Unit manuals

Fisher
Fisher V150S User manual

Fisher
Fisher TBX-T User manual

Fisher
Fisher EMERSON ACE95JR User manual

Fisher
Fisher EZ-C User manual

Fisher
Fisher GX 3-Way User manual

Fisher
Fisher FIELDVUE DVC6200p User manual

Fisher
Fisher NPS 12 User manual

Fisher
Fisher D2T FloPro User manual

Fisher
Fisher 377 User manual

Fisher
Fisher 9500 User manual

Fisher
Fisher EZ easy-e User manual

Fisher
Fisher 8590 User manual

Fisher
Fisher Vee-Ball V150 User manual

Fisher
Fisher 8580 User manual

Fisher
Fisher Design CAV4 User manual

Fisher
Fisher EMERSON DVC6200 User manual

Fisher
Fisher RSS User manual

Fisher
Fisher V260 User manual

Fisher
Fisher ET easy-e User manual

Fisher
Fisher D4 User manual