manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Frico
  6. •
  7. Air Conditioner
  8. •
  9. Frico Thermozone AC 300 User manual

Frico Thermozone AC 300 User manual

Other manuals for Thermozone AC 300

1

Other Frico Air Conditioner manuals

Frico Pamir 3200 User manual

Frico

Frico Pamir 3200 User manual

Frico ACC1000WL User manual

Frico

Frico ACC1000WL User manual

Frico PA34WB15 User manual

Frico

Frico PA34WB15 User manual

Frico AR3500E User manual

Frico

Frico AR3500E User manual

Frico PAEC4000 NA Series User manual

Frico

Frico PAEC4000 NA Series User manual

Frico Thermozone PA4200 User manual

Frico

Frico Thermozone PA4200 User manual

Frico Thermozone AD310W User manual

Frico

Frico Thermozone AD310W User manual

Frico Thermozone PA2200C User manual

Frico

Frico Thermozone PA2200C User manual

Frico AR200 Series User manual

Frico

Frico AR200 Series User manual

Frico AGS5500 User manual

Frico

Frico AGS5500 User manual

Frico TKW20 User manual

Frico

Frico TKW20 User manual

Frico AR3500 Series User manual

Frico

Frico AR3500 Series User manual

Frico PA3200C User manual

Frico

Frico PA3200C User manual

Frico Thermozone PA2200C User manual

Frico

Frico Thermozone PA2200C User manual

Frico PA2500 User manual

Frico

Frico PA2500 User manual

Frico 2210CA User manual

Frico

Frico 2210CA User manual

Frico Thermozone AD300A/E User manual

Frico

Frico Thermozone AD300A/E User manual

Frico AD200A User manual

Frico

Frico AD200A User manual

Frico SLW400 User manual

Frico

Frico SLW400 User manual

Frico ADAC090 User manual

Frico

Frico ADAC090 User manual

Frico Thermozone PA 1000 User manual

Frico

Frico Thermozone PA 1000 User manual

Frico AR3510W User manual

Frico

Frico AR3510W User manual

Frico PA2500 User manual

Frico

Frico PA2500 User manual

Frico AGI6000 User manual

Frico

Frico AGI6000 User manual

Popular Air Conditioner manuals by other brands

Fujitsu ASYG 09 LLCA installation manual

Fujitsu

Fujitsu ASYG 09 LLCA installation manual

York HVHC 07-12DS Installation & owner's manual

York

York HVHC 07-12DS Installation & owner's manual

Carrier Fan Coil 42B Installation, operation and maintenance manual

Carrier

Carrier Fan Coil 42B Installation, operation and maintenance manual

intensity IDUFCI60KC-3 installation manual

intensity

intensity IDUFCI60KC-3 installation manual

Frigidaire FAC064K7A2 Factory parts catalog

Frigidaire

Frigidaire FAC064K7A2 Factory parts catalog

Sanyo KS2432 instruction manual

Sanyo

Sanyo KS2432 instruction manual

LG MultiV Series installation manual

LG

LG MultiV Series installation manual

CLIMAVENETA a-CHD U-2T 606+2209 OPERATING AND INSTALLATION Manual

CLIMAVENETA

CLIMAVENETA a-CHD U-2T 606+2209 OPERATING AND INSTALLATION Manual

Midea EWK06CW5 user manual

Midea

Midea EWK06CW5 user manual

Pioneer FAB Series installation manual

Pioneer

Pioneer FAB Series installation manual

SPT WA-1511S user manual

SPT

SPT WA-1511S user manual

Mitsubishi Electric Mr.Slim MSZ-A24NA operating instructions

Mitsubishi Electric

Mitsubishi Electric Mr.Slim MSZ-A24NA operating instructions

Mitsubishi Electric PUHZ-RP50VHA4 Service manual

Mitsubishi Electric

Mitsubishi Electric PUHZ-RP50VHA4 Service manual

Panasonic CS-S18HKQ Service manual

Panasonic

Panasonic CS-S18HKQ Service manual

Panasonic CS-E15NKE3 operating instructions

Panasonic

Panasonic CS-E15NKE3 operating instructions

Gree GWH18TC-K3DNA1B/I Service manual

Gree

Gree GWH18TC-K3DNA1B/I Service manual

Friedrich ZoneAire Compact P08SA owner's manual

Friedrich

Friedrich ZoneAire Compact P08SA owner's manual

Daikin R32 Split Series installation manual

Daikin

Daikin R32 Split Series installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Thermozone AC 300
SE
... 12
... 8
NO
FR
... 28
... 24 PL ... 40
... 44
IT
FI
... 20
...16
GB
NL
... 36
... 32
RU
ES ... 48
DE
Thermozone AC 300Thermozone AC 300
2
1000 / 1665
335
Ø 11
Ø 20
490
Fig. 1
975 / 1640 640
400
min 300
580
Fig. 3
280
325
24
65
100
3x Ø29
287
Fig.2
360
Thermozone AC 300
Thermozone AC 300
3
AC 300
Fig. 4
45
AVMP300
AVMP300
45
AC 300
Thermozone
Thermozone
Thermozone AC 300
4
7531
268
ACR 304 01357
1
2
3
4
NL
PTC
123456NL
NL
789
230V~
AC 301, -302 230V~
KS101.1
~
N
2221 AG
AC 301, -302 1234NL
230V~
KS102.2
AGB 304
~
N
2221 AG
AC 301, -302 1234NL
230V~
KS103.2
~
M
˚C
~
M
˚C
~
M
˚C
Thermozone AC 300
AC 301, -302 123456NL 9
230V~
AC 301, -302 4569
AC 301, -302 4569
1234
AGB 304
456783
ACR 3042
2
1
KS104.1
5
Thermozone AC 300
7531
2468
ACR 304 01357
1
2
3
4
51
2
6
EV 300
62
13121110
321
400V 3~
LLL
K1 K2
230 V 3~
14
400V 3~ / 230V 3~
AC 308, -312 400V 3(N)~ / 230V 3~
~
M
NL
PTC
123456NL
NL
789
230V~
1
2
32
3
1
Hi
Lo
KRT 2800
KS106.1
~
M~
M
˚C ˚C ˚C
Diff Hi - Lo 1 - 4 ˚C
˚C
˚C
˚C
6
Thermozone AC 300
AC 308, -312 123456NL 7
230V~
AC 308, -312 456
AC 308, -312 456
321
LLL
400V 3~ / 230V 3~
51
2
6
EV 300
121314
10
321
LLL
400V 3~ / 230V 3~
121314
10
321
LLL
400V 3~ / 230V 3~
121314
10
1
2
32
3
1
Lo
KRT 2800
AGB 304
34 35 36 37 3833
ACR 3042
32
1234
31
KS107.1
Diff Hi - Lo 1 - 4 ˚C
˚C
7
Thermozone AC 300
Application area
The Thermozone AC 300 air curtains are
intended for stationary installation above or
at the side of entrance and smaller doors with
a height between 2.5 and 3.5 metres.
The Thermozone AC 300 is supplied with
or without heating elements. Electric heat
can be added to units without heat
afterwards.
The efficiency of the air curtains is
dependent on the difference of air pressure
and temperature (between the rooms that are
separeated by the air curtain) and pressure
caused by wind.
The protection class of AC 300 is IP 24,
drip-proof design.
Operation
The air is drawn in from the upper and under
side of the unit and is blown out at high
velocity across the doorway, providing a
protective air shield. The air shield
minimizes heat and cold air leakage.
When mounted on supplied brackets, the
units can be directed with regard to the size
of load on the door in question. The more
load caused by negativ pressure, temperature
differences and wind, the more should the air
stream be directed outwards.
The air flow is adjusted with a selector
(ACR304 eller ACR3042) to provide maxi-
mum protection to the opening.
Units with electric heat can be regulated
with the output selector EV300 in 3 stages
(0 - 1/2 - 1/1) and with a 2-stage thermostat,
KRT 2800.
NOTE! Air pressure imbalance between
rooms separated by air curtains, considerably
reduces the efficiency of the air curtain. The
ventilation should therefore be balanced!
Mounting
a) Above the doorway
• The unit is usually mounted inside the
doorway as close to the opening as
possible with the nozzle closest to the
opening.
• When used above interior freezer doors,
the unit should be mounted on the warm
side.
• To minimize air leakage between the units,
they should be mounted close to each
other. To reach the wall mounting
screws, a min gap of 50 mm between the
units is required.
• Attach the two (2) wall mounting brackets
securely to the wall or suitable structure.
Attach the air curtain to the brackets
(Fig.1). The units are secured with M10-
screws in the centre hole of each bracket
and in one of the notches, thus allowing
the whole unit to be turned and the angle
of the air stream to be adjusted.
• Observe the minimum distances given in
fig.3 and also that the units may not be
mounted directly below a power outlet.
b) Standing at the side of the doorway
• When space above the doorway is
limited, the units can be mounted standing
beside the opening, thus creating a side-
blowing air stream (fig.4). Mounting plates
AVMP300 are mounted between units and
between the lowest unit and the floor.
• The units are mounted vertically inside the
doorway as close to the edge of the
opening as possible with the nozzle
closest to the opening.
• The mounting plate consists of two parts.
The outer one is secured in the floor (or at
the top of the lower unit) with the supplied
screws. The units are secured with M10-
screws in the centre hole of each bracket
and in one of the notches, thus allowing
the whole unit to be turned and the angle
of the air stream to be adjusted. The inner
part is mounted on the under side of unit
that is standing on the floor. The plate is
secured with 3 M10-screws in the
prepared screw holes.
• Lift the unit on to the plate and screw the
plates together. Maximum building height
for vertical units is 3.5 metres.
• At the end of the uppermost unit, one of
the supplied mounting consoles (or other
suitable strut) is mounted and then
attached to the wall in order to secure the
top of the tower.
• We recommend that the collision
protection AXP300 is mounted to prevent
the units from being hit by trucks and
similar.
• Mount the air flow selector ACR304 or
ACR3042 withing easy reach for
controlling the air curtains.
• To control units with electric heat, the
output selector EV300 is mounted in
conjunction with the speed selector and a
thermostat (for ex. KRT2800), in such a
place that changes of the temperature
close to the opening, can be quickly
detected.
Installation and Operating Instructions
GB
20
Thermozone AC 300
• When mounting vertically, draught can
occur due to rotating air. The mounting of
a narrow wall at the side of the opening
(the side where no units are mounted),
can decrease the rotation.
Electrical installation
The electrical installation should be carried
out by a qualified electrician in conformity
with prevailing regulations. The appliance
should be preceded by a triple pole switch
with at least 3 mm breaking gap.
Different alternatives for air flow
regulation are possible, see wiring diagram
pages 4-7.
The hatch on the underside of the unit is
opened by turning the locking pins 1/4 of a
lap. The connection should be made with a
cable type S05VV-U, A05VV-R or similar.
On the upper side of the unit there are
knock-outs, 2 pcs ø 37 mm and 3 pcs ø 29
mm. The cable-glands used must guarantee
the protection class requirements!
Type Power Voltage Min. area
kW V mm2
All control 230V 1,5
AC 308 8 230V 3~ 4
AC 308 8 400V 3~ 2,5
AC 312 12 230V 3~ 10
AC 312 12 400V 3~ 4
For the units with electrical heating, the
power and voltage should be supplied in
different connection areas (see wiring
diagram).
In the distribution board it is to be
indicated that ”the air curtains can be
supplied from more than one connection”.
Adjusting the unit and the air stream
Direction and speed of the air stream should
be adjusted with regard to the load on the
door. Pressure forces the air stream to bend
towards the interior of the room (when the
room is heated and the outside is cold). To
withstand the load, the air stream should be
directed outwards. An angel up to 15° can be
recommended. The more load caused by
negativ pressure, temperature differences
and wind, the more should the air stream be
directed outwards.
A baffle on each side of the doorway will
improve the efficiency of the air curtains.
When used above freezer or cooler doors,
the units should be mounted on the warm
side with the air stream directed 0-10°
towards the warm side.
Basic air flow settings
The air flow is set with the air flow selector
so that the speed of the air is 3-4 m/s 1 m
above the floor. The direction of the air
stream and the air speed may need to be
adjusted more exactly depending on the
load on the door.
Trouble shooting
If the fans stand still, check the following:
a) Power supply; check fuses, circuit-breaker,
time switch (if any) that starts and stops
the unit.
b) That the air flow selector is correctly set.
c) That the position limit switch is working
(if any).
If the error cannot be fixed, please contact
qualified service technician.
If there is no heat, check the following:
a) Power supply to electric heater; check
fuses and circuit-breaker (if any).
b) Thermostat settings and actual
temperature.
c) That the output selector (if any) is set
correctly.
d) That the overheat protection has not
been released. If so, please check
description on next page.
Overheating
(applies to units with electric heat)
The Thermozone is equipped with an
overheat protector. If it is released due to
overheating, reset as follows:
a) Disconnect the electricity with the fully
isolated switch.
b) Investigate the matter and repair the
fault.
c) Reset is performed as follows:
• Dismount the service hatch on the
underside of the unit.
• Locate the red buttons.
• Press the buttons until a click is heard
(you do not need to press them
simultaneously).
d) Connect the Thermozone again.
If the error cannot be fixed, please contact
qualified service technician.
GB
21
Thermozone AC 300
Security
• Ensure that the area around the intake and
exhaust grille is kept free from material
which could prevent the air to flow through
the unit!
• During operation the surfaces of the unit
are hot!
• The unit must not be covered fully or
partially with clothes, or similar materials,
as overheating can result in a fire risk!
Maintenance
NOTE! Disconnect electricity prior to cleaning
or inspection (units with electric heat can be
supplied from more than one connection).
The fan motors and the other components
require no maintenance other than cleaning
when necessary, however at least once year.
Grille, impeller and elements are vacuum
cleaned or dried clean with a damp cloth.
Open the inspection hatch to reach elements
and impellers.
Safety cut-out
(applies to units with electric heat)
If the installation is protected by means of a
safety cut-out, which trips when the appliance
is connected, this may be due to moisture in
the heating element. When an appliance
containing a heater element, has not been
used for a long period and is stored in a
damp environment, moisture can enter the
element. This should not be seen as a fault,
but is simply rectified by connecting the
appliance to the mains supply via a socket
without a safety cut-out, so that the moisture
can be driven out of the element.
The drying time can vary from a few hours
to a few days. As a preventive measure the
Thermozone should occasionally be run for a
short time when it is not being used for an
extended period of time.
The garantee is only valid if the
Thermozone units are used in the manner
intended by the manufacturer and in
accordance with the installation and
maintenance instructions.
GB
22
Manufacturer
Our products are manufatured in accordance
with applicable international standards and
regulations.
Frico AB
Box 102
SE-433 22 PARTILLE
SVERIGE
The manufacturer hereby declares that the
following products
AC301, AC302, AC308, AC312,
comply with the following EC-directives.
EC Declaration of Conformity
Defined by the EC Low Voltage Directive
73/23/EEC.
The following harmonised standards are in
use:
SS-EN 60 335-1: 1988, A2, A5, A6,
A51- A54, A56
SS-EN 60 335-2-30: 1992, A51, A52
Complete technical documentation is
available.
EC Declaration of Conformity
Defined by the EC Electromagnetic
Compatibility Directive 89/336/EC och
92/31/EC.
The following harmonised standards are in
use:
SS-EN 50 082-1: 1992
SS-EN 60 555-2/3: 1991
Complete technical documentation is
available.
Partille, 19 januari 1998
Mats Careborg
Technical Manager