futuredesion Orion-M User manual

Orion-M Honeywell UDC3500 Series Controller System Guide Rev C
February , 2011
Supersedes: Rev B (March 25, 2010)
Orion-M
Honeywell UDC3500
Controller System Guide

Orion-M
FDC Orion-M PREFACE
Safety Information in this Manual
Notes, cautions and warnings appear throughout this book to draw your attention to important operational and
safety information.
A “NOTE” marks a short message to alert you to an important detail.
A “CAUTION” safety alert appears with information that is important for protecting your equipment and
performance.
A “WARNING” safety alert appears with information that is important for protecting you, others and equipment
from damage. Pay very close attention to all warnings that apply to your application.
This symbol (an exclamation point in a triangle) precedes a general CAUTION or WARNING
statement.
This symbol (a lightning bolt in a lightning bolt in a triangle) precedes an electric shock hazard
CAUTION or WARNING safety statement.
Technical Assistance
If you encounter a problem with your Orion-M controller, review all of your configuration information to verify
that your selections are consistent with your application: inputs; outputs; alarms; limits; etc. If the problem
persists after checking the above, you can get technical assistance by dialing +1 (866) 342-5332 or by faxing
your request to +1 (866) 332-8014, Monday thru Friday, 8:00 a.m. to 5:00 p.m. Eastern Standard Time. You
can also email your request to support@futuredesigncontrols.com.
An applications engineer will discuss your application with you.
Please ha e the following information a ailable:
• Complete Model #’s and/or Serial #’s for Component(s) in Question
• Complete Software Version #’s
• All Configuration Information
• All User Manuals
Warranty and return information is on the back co er of this manual.
Your Comments
Your comments or suggestions on this manual are welcome. Please send them to:
Future Design Controls, P.O. Box 1196, Bridgeview, Illinois, 60455
Telephone: +1 (888) 51-5444; fax: +1 (888) 30 -8014
csr@futuredesigncontrols.com
The Orion-M Honeywell UDC3500 Controller System Guide is copyrighted by Future Design Controls, Inc., ©
2009, all rights reserved (http://www.futuredesigncontrols.com/Orion-M.htm).
.

Orion-M
TABLE OF CONTENTS FDC Orion-M i
1 What is the Orion-M? ............................................................................................... 1.1
1.1 Features............................................................................................................................................... 1.1
2 Getting Started.......................................................................................................... 2.1
2.1 Installing the UDC3500 Controller....................................................................................................... 2.1
2.1.1 Communications Wiring ................................................................................................................ 2.1
3 Configuring the Honeywell UDC3500 Controller ................................................... 3.1
3.1 Assigning the Proper Communications Settings ................................................................................. 3.1
3.2 Input Type Assignments ...................................................................................................................... 3.1
3.2.1 Input 1 and 2 Operation ................................................................................................................ 3.1
3.3 Control Output Assignments ............................................................................................................... 3.1
3.3.1 Auto-Tune and Auto/Manual Operation ........................................................................................ 3.1
3.4 Loop Permissions ................................................................................................................................ 3.1
3.4.1 Set oint ermission Exception.................................................................................................... 3.1
3.4.2 Auto/Manual ermission Requirement ......................................................................................... 3.1
Appendix
Software Usage Note
Warranty
Returns


Orion-M
WHAT IS THE ORION-M? FDC Orion-M 1.1
1 What is the Orion-M?
The Orion-M is a multi-loop process control system combined with an embedded SCADA color touch
interface. The Orion-M provides a configurable control platform for a variety of OEM applications requiring up
to 15 separate loops of control. In addition to 15 loops of control, the Orion-M can also provide up to an
additional 15 inputs for process monitoring, for a total of 30 process inputs.
The system is provided with eight 24Vdc digital inputs, two 24Vdc outputs and 6 relay outputs standard. The
Orion-M can be expanded to a total of 16 digital inputs and 32 digital outputs. The Orion-M also provides the
capability of accepting analog inputs for remote set point control and analog outputs capable of retransmitting
system variables (PV, SP or %Out) to other devices such as a chart recorder. The 0-10Vdc or 4-20mA user
selectable signals are provided through the addition of optional analog expander cards.
The Orion-M complements its versatile hardware platform by providing a host of standard features and
configuration capabilities, all through its visual, touch interface. The touch screen interface is an embedded,
industrial PC with all software included. No external PC software is required for setup or configuration of the
Orion-M. All of the setup and configuration data is saved to the Orion-M’s internal memory.
Individual process controllers, one for each loop in the system, provide reliable, consistent and accurate
control by distributing the process control requirements of the system among multiple processors. Each loop
controller provides full auto tune functionality with high resolution, universal process inputs. When coupled
with the built in ramping profiler of the Orion-M, it allows for automatic, timed control of all processes and
outputs of the system. No other control system on the market provides the flexibility, functionality and
configurability of the Orion-M.
1.1 Features
The digital inputs of the Orion-M can be configured as alarm inputs with adjustable delay timers, as control
inputs for controlling profile operation or for direct control of the system’s digital outputs.
The digital outputs of the Orion-M can be used as direct outputs for controlling external equipment related to
the application through software switches, called events, or be programmed to act as system alarm or status
outputs. All outputs have adjustable delay times for on, off and cycle times.
The Orion-M can be operated in single set point or automatic profile control mode. Profile entry is made easy
through the use of copy, paste and delete menu selections. Profiles can be copied to the external ‘USB’
memory stick and then imported to another Orion-M controller which eliminates the need to enter duplicate
profiles into multiple Orion-M systems. When running in automatic profile mode, the operator can place the
system into hold and change any control parameter without modifying the saved profile. This gives the
operator maximum flexibility over the controlled process.
Data file analysis tools (auto-trend) make looking at historical data a simple task. Any control variable saved
to the Orion-M flash memory can be plotted on the historical data trend, for any time frame within the data
file’s total time range. Full ‘USB’ print capabilities from the Orion-M interface to a standard HP inkjet printer
Model 6540, 6940, 6980 (or compatible printer), eliminates the need for a PC, strip or circular chart-recording
device. Graphics trends, historical and report print functions are standard.
The built in Ethernet functionality includes a ‘Web Server’ to provides access to all Orion-M data (view only), a
VNC interface for remote control and monitoring and an NTS clock, all available via a local Intranet
connection (wired or wireless), or the World Wide Web using standard software like Microsoft’s Internet
Explorer.

Orion-M
1.2 FDC Orion-M WHAT IS THE ORION-M?
The Orion-M provides a rich set of tools for control interaction and data analysis. Views include system
overviews, trends, alarms, profiles as well as historical data, alarm history and audit trail views. The menu
driven interface eliminates screen ‘clutter’ by providing an easy to use ‘Windows’ interface for interaction
between the user and the Orion-M system.
The Orion-M can store more than one year of data on its internal compact flash card. Data logging can be
enabled manually or automatically during automatic profile run. Data backup is provided with the ‘USB I-
Stick’ for plug and play transfer of files to any PC running Microsoft Windows XP operating systems.
The Orion-M security module provides full system security with three levels of access. Each of the three
access levels allow for independent user rights. Up to 30 users can be entered into the system while the
audit trail tracks all operator actions and records them.
The Orion-M control system includes the following interface features:
• Overview screen that displays all “runtime” information.
• Profile run and monitor views.
• Profile entry, open, save and download interface screens.
• Current alarm and alarm history views (alarm history for up to 1 year).
• Real time trends (with adjustable X,Y limits) for all inputs.
• System and application setup (control loops, monitors, inputs/outputs, alarms, etc.).
• Data logging interface screens include log point selection and historical viewing.
• ‘Plug and Play’ memory stick functionality for data transfer/backup.
• Full USB print capabilities and on-line help screens
• Web server for intranet/internet access (view only).
• VNC server for intranet/internet access (control/view).
• FTP data back-up for automatic data file transfer over intranet/internet.
• Integrated email server for alarm notification and file transfer.
• NTS clock with daylight savings time insures that the system is up to date.
• Full security with audit trail for tracking user actions.
• Maintenance counters for output cycles and on times.
• Helps screens are available for most screen views; configurable in English, Spanish and French
• Voice assisted help in English, Spanish and French (external speakers required – not included).

Orion-M
GETTING STARTED FDC Orion-M 2.1
2 Getting Started
The Orion-M requires one Honeywell UDC3500 for every two control loops required in the system. Since the
Orion-M is capable of interfacing to more than one brand of controller, refer to the Orion-M part number matrix
for the operating system to be sure that the HWDL, CM application software has been provided. The Orion-M
will not operate correctly if any other version of CM application software is used with a Honeywell UDC3500
controller.
2.1 Installing the UDC3500 Controller
For applications requiring several loops of control or more, proper planning and arrangement of the Honeywell
UDC controllers prior to mounting is critical for optimum routing of the controller wiring. For applications
requiring frequent access to the controllers, panel mounting provides direct access. For applications where
operator access to the controllers is not required, or is desired to be kept at a minimum, the controllers can be
mounted directly inside of an enclosure. This also reduces wiring concerns by eliminating the need to run the
sensor, communication and control wiring for each controller to and from an enclosure door.
Refer to the Honeywell UDC3500 Controller Product Manual for dimensions, appropriate mounting and
operating conditions, including proper electrical connections. Connect sensor and control wiring as required,
paying close attention to all wiring precautions and guidelines as noted in the controller manual. It is
recommended that all sensor and communication wiring, to and form the UDC controllers, be routed away
from all high voltage and/or output control wiring. This will minimize the chances of electrical transients or
spikes in the power/control wiring from causing communications or sensor reading errors.
2.1.1 Communications Wiring
Each UDC3500 control used in the Orion-M system is its own independent loop control. However, in order for
the controllers to work as part of the system, they must communicate with the Orion-M control module using
RS485 serial communications. Therefore, each UDC3500 used must be equipped with the RS485 Modbus
RTU communications option or they will not operate as part of the Orion-M system:
DC350X-XX-2XXX-XXX-XX000-XX-0
Order code 2 designates RS-485 Modbus serial communications
(see Honeywell UDC Product Manual for model number interpretation)
Communications wiring must be run using a minimum of 24 AWG twisted-pair, copper conductors. For short
runs (< 50 feet total), non-shielded wiring can be used as long as proper separation from power/control
conductors is maintained. For communications wiring where the total length will exceed 50 feet, up to the
maximum allowed length of 650 feet, shielded twisted-pair must be used.
NOTE: FDC recommends the use of shielded wire for all installations regardless of the total length in order
to maintain optimum performance and minimize the possibility of communications errors.
When using shielded twisted-pair, be sure to ground the shield at only one end, preferably at the Orion-M
control module. Allowing any other portion of the cable shield to come in contact with ground, or grounding
both ends, will allow ground loop currents to flow in that section of the cable shield which can disrupt
communications.

Orion-M
2.2 FDC Orion-M GETTING STARTED
NOTE: Refer to the Honeywell UDC3500 roduct Manual for all other connections including power, sensor
and control wiring. Since no two applications are the same, it is up to the system designer to insure
that the controllers are properly installed and wired to meet design specifications.

Orion-M
CONFIGURING THE UDC3500 CONTROLLER FDC Orion-M 3.1
3 Configuring the Honeywell UDC3500 Controller
The unique and inherently flexible design of the Orion-M system allows the OEM to tailor each component of
the system to the application. By using independent loop controls, each one can be configured for various
input and output types, control algorithms, etc., based on the requirements of the application. It also allows
control loops to be added or replaced on the system at any time, simply by connecting the controller to the
Orion-M’s control module, RS-485 communication link.
If the application requirements change and a different input or output type is required, or if the controller were
to fail, it can be replaced quickly, and at a lower cost as compared to having to repair or replace larger,
integrated multi-loop controllers. The Orion-M only requires that the communications settings for each loop
control be properly assigned, and that the input type of the controller is set in the Orion-M Configurator, so
that the control loop input and set point can be displayed and set properly through the Orion-M interface.
3.1 Assigning the Proper Communications Settings
The Orion-M can support up to eight UDC3500 controls; however, the last UDC3500 will only be able to have
its first control loop integrated into the Orion-M. The Orion-M only supports 15 loops and there are a total of
16 provided by eight UDC3500 dual loop controllers. However, the Orion-M does allow the last UDC3500
controller (the unit assigned to communication address 8) to be replaced with a UDC2500 or UDC3200 single
loop controller to reduce installation costs since the second loop of the UDC3500 is not supported.
When assigning communications addresses, the allowable address range is 1 – 8. Loops are assigned in
sequential order in the Orion-M, two per UDC3500, starting with address 1 up to address 8 which only has a
single loop assigned to it. As control loops are enabled in the Orion-M Configurator, the Orion-M will
automatically assign Loop Inputs 1 and 2 to the controller at address 1, loop inputs 3 and 4 to the controller at
address 2, and so on up to Loop Input 15 which is assigned to the controller at address 8. If more than one
UDC controller has the same address, or a loop input is enabled but a controller is not assigned to the
corresponding address, the Orion-M will report a communications alarm for that loop input when the runtime
application is started.
NOTE: The order of the loop controls on the communication link is not important. The communications
address for a controller can be assigned regardless of its position on the link.
*Required UDC3500 Communications Group Settings:
• Communications station address (ComADR): 1-8 (based on system design)
• Communications selection (ComSTATE): MODBUS
• Infrared communications (IRENAB): DISABLE (recommended but not required)
• Baud rate (BAUD): 9600
• Transmit delay (TX DELAY): 1
• Floating point data format (WS FLOAT): FP_B
• Shed enable (SHED ENAB): ENABLE
• Shed time (SHEDTIME) : 60 (recommended – minimum of 30 secs)
• Shed mode (SHEDMODE): LAST
• Shed set point (SHED SP): TO CSP
• UNITS: ENG
• Computer set point ratio (CSP(2) RATIO): 1 (for loops 1 and 2)
• Computer set point bias (CSP(2) BIAS): 0 (for loops 1 and 2)
*See section 3 Configuration, in the Honeywell UDC3500 Product Manual for instructions on
accessing the control’s configuration menus and setting the abo e parameters as required.

Orion-M
3.2 FDC Orion-M CONFIGURING THE UDC3500 CONTROLLER
3.2 Input Type Assignments
The Honeywell UDC3500 controller provides universal input types for inputs 1 and 2. The Loop Inputs for the
corresponding controller in the Orion-M Configurator are set to match the selected input type for inputs 1 and
2 of the UDC control.
IMPORTANT: The Orion-M is unable to detect sensor break or input failure conditions on the Honeywell
UDC3500 controller. Therefore, a problem may exist with a controller input, but the Orion-M
will be unable to report the alarm condition.
If the failure of an input is a critical alarm condition that requires monitoring, the orion-M
provides 30 alarms that can be configured to any loop or monitor input. A process alarm can
be configured with alarm set points outside of the normal operating range for the input. A
failure of the input on the UDC3500 would result in a high scale or low scale break, which
could then be detected and reported by the alarm set in the Orion-M.
3.2.1 Input 1 and 2 Operation
When input 1 or 2 of the UDC3500 is a temperature input, i.e., RTD or thermocouple, the temperature units of
the input on the UDC3500 must be set to match the selection in the Orion-M on the Degrees C/F screen. The
Orion-M can not change the temperature units on the UDC controller. Thus, when you set up the UDC
controller, its temperature units must match that of the selection in the Orion-M. If the selections do not
match, the Orion-M may show units of degrees Centigrade while the actual value from the UDC control is in
degrees Fahrenheit.
In addition, if %RH (wetbulb) is selected for a Loop Input in the Orion-M Configurator, the temperature units in
the Orion-M must match the UDC controllers for the drybulb/wetbulb calculation to be performed correctly. If
the temperature units do not match, the relative humidity reading on the Orion-M will not be correct.
NOTE: It is recommended that the Degrees C/F selection screen be disabled in the Orion-M Configurator
once the proper temperature units selection has been made to prevent it from being accessed. This
will prevent the temperature units from being accidentally changed and causing operator confusion
when the units do not match between the UDC control and the Orion-M. See section 3.6 Orion
Functions/Startup View, in the Orion-M Configuration Manual for information on enabling and
disabling this item.
For either temperature or process (voltage/current/carbon) input types, the Orion-M will set the lower and
upper set point limits for the input to match the settings in the Orion-M Configurator. The decimal point
selection for the Loop Input in the Orion-M and the UDC controller do not have to be set to match; however, if
the loop controls are visible to the operator, it is recommended that the decimal point resolution of the Orion-
M and UDC controller match.
Loop Inputs set as temperature in the Orion-M Configurator allow a decimal point selection of 0 or 1. Process
type loop inputs can be displayed on the Orion-M with a resolution of 0 to 3 decimal points. The Orion-M has
a display range of -32 68 to 32 6 , -32 6.8 to 32 6. , -32 .68 to 32 .6 or -32. 68 to 32. 6 depending
upon decimal point selection. When selecting the decimal point resolution for the Loop Input in the Orion-M
Configurator, make sure that range of the UDC3500 does not exceed the range selected in the Orion-M or the
value may not be displayed correctly.
IMPORTANT: The lower and upper set point limits are set once, each time the Orion-M enters the runtime
application. Do not alter the values in the UDC3500 control once they have been set or the
Orion-M may not be able to set the correct set point to the controller.

Orion-M
CONFIGURING THE UDC3500 CONTROLLER FDC Orion-M 3.3
3.3 Control Output Assignments
The Orion-M uses a default resolution of 1 decimal point to display the percentage of output of all UDC
controllers attached to the system. Therefore, regardless of the display resolution set on the UDC3500, the
Orion-M will display a percentage of output of 0.0 – 100.0% for the output.
If the UDC controller is set for bimodal operation (heat/cool), a display value of 50.0% indicates that both heat
and cool outputs are off. Values from 50.0 to 100.0% represent the percentage of heat output from off to full
on and values from 50.0 to 0.0% represent the percentage of cool output from off to full on.
3.3.1 Auto-Tune and Auto/Manual Operation
The Orion-M provides the ability to switch each UDC3500 in the system between auto and manual output
operation. This function is accessed from the Orion-M runtime, Single Loop View screen via the ‘AM’ control
button.
The Orion-M cannot initiate the tune functions on the UDC3500 controller. Pressing the ‘AT’ button on the
Single Loop View screen in the Orion-M runtime will provide the appearance that it will activate the auto-tune
on the control, but once initiated, it will immediately turn off. Attempting to activate the auto-tune function will
not cause any malfunction or system error; however, it should be noted that the function is inoperative when
using the UDC3500 control.

Orion-M
3.4 FDC Orion-M CONFIGURING THE UDC3500 CONTROLLER
3.4 Loop Permissions
The Orion-M iSeries configuration provides permissions which can be set to allow the control loop set point,
auto/manual and auto tune operations to be performed at the loop control itself as well as through the Orion-
M. These can allow an operator to make changes at the loop control in cases where the Orion-M interface is
located in a remote location.
3.4.1 Set Point Permission Exception
If the control loop is configured to operate under cascade control or is configured as an RH wet bulb loop
type, the set point for the loop is generated by logic within the Orion-M. The loop will not function as
configured unless the se point is constantly set by the Orion-M. Thus, any change made at the loop control
will be overridden by the Orion-M. If local adjustment at the loop control may be required for any reason, loop
set point communications must be interrupted via a digital input to the Orion-M configured as ‘loop SP comms
disable’.
In addition, the Honeywell controls will enter the computer set point mode (CSP) once they receive any set
point command from the Orion-M. This will lock out adjustments from the keypad at the controller. The
Orion-M is designed to send the ‘shed timer reset’ command to the UDC controller to take it out of computer
set point control when the set point permission is enabled. This allows control via the keypad of the
controller. However, during profile operation and after the profile completes, the UDC will remain under
computer set point control. In order to deactivate CSP, a single set point must be sent from the Orion-M in
order to unlock it. Triggering a digital input configured as ‘loop SP comms disable’ will also take the UDC
controls out of computer set point control.
3.4.2 Auto/Manual Permission Requirement
The Honeywell controller provides the ability to initiate manual mode or ‘failure transfer mode’ through a
digital input on the controller. If this function is used, the loop permission for auto/manual operation must be
enabled. If this permission is not enabled, a communication error will occur at the Orion-M. This is due to the
fact that without the permission enabled, the Orion-M will try and force the controller back to auto mode if it
goes into manual operation via the digital input.
Since the digital input on the UDC controller is an override condition, it will deny the auto mode command
from the Orion-M. The Orion-M then has to respond with a communication error, since the controller did not
follow the command given. By enabling the auto/manual permission, the Orion-M will accept the manual
mode force at the UDC controller.

Orion-M
APPENDIX FDC Orion-M A.1
Appendix

Orion-M
A.2 FDC Orion-M APPENDIX
Software Usage Note:
The selection, application or use of Future Design Control products or software is the purchaser or
user's responsibility. No claims will be allowed for any damages or losses, whether direct, indirect,
incidental, special or consequential.
In addition, Future Design reser es the right to make changes without notification to purchaser or
user to materials or processing that do not affect compliance with any applicable specification.
Future Design makes no warranties when using the Orion-M system.
Warranty:
Future Design Controls products described in this book are warranted to be free from functional defects in
material and workmanship at the time the products shipped from Future Design Controls facilities and to
conform at that time to the specifications set forth in the relevant Future Design Controls manual, sheet or
sheets for a period of one year after delivery to the first purchaser.
Future Design Controls products are warranted to be free from functional defects in materials and
workmanship at the time the products shipped from Future Design Controls facilities and to conform at that
time to the specifications set forth in the relevant Future Design Controls manual, sheet or sheets for a period
of one year after delivery to the first purchaser for use.
There are no expressed or implied Warranties extending beyond the Warranties herein and above set forth.
Limitations: Future Design Controls provides no warranty or representations of any sort regarding the fitness
of use or application of its products by the purchaser. Users are responsible for the selection, suitability of the
products for their application or use of Future Design Controls products.
Future Design Controls shall not be liable for any damages or losses, whether direct, indirect, incidental,
special, consequential or any other damages, costs or expenses excepting only the cost or expense of repair
or replacement of Future Design Control products as described below.
Future Design Controls sole responsibility under the warranty, at Future Design Controls option, is limited to
replacement or repair, free of charge, or refund of purchase price within the warranty period specified. This
warranty does not apply to damage resulting from transportation, alteration, misuse or abuse.
Future Design Controls reserves the right to make changes without notification to purchaser to materials or
processing that do not affect compliance with any applicable specifications.
Return Material Authorization:
Contact Future Design Controls for Return Material Authorization Number prior to returning any product to our
facility:
7524 West 98th Place – Bridge iew, IL 60455 – Phone 888.751.5444 – Fax 888.307.8014
http://www.futuredesigncontrols.com
Table of contents
Other futuredesion Controllers manuals
Popular Controllers manuals by other brands

REPLIGEN
REPLIGEN XCell C410:V3 user guide

Sentiotec
Sentiotec CV F4 Installation and operating instructions

YASKAWA
YASKAWA motoman NX100 Operator's manual

Carrier
Carrier UC Open XP Installation and startup guide

Innovate Motorsports
Innovate Motorsports LC-1 quick start guide

JUMO
JUMO dTRON 16.1 B 70.3011 operating manual